background image

Page 3 of 21

W3400 Gas Fireplace

Installing The Fireplace Shell

The fireplace may be installed in any location that is free of air
conditioning ducts, electrical wiring and plumbing. Safety, as well as
efficiency of operation, must be considered when selecting the
fireplace location. Try to select a location that does not interfere with
room traffic, has adequate ventilation, and offers an accessible
pathway for Direct Vent installation. Refer to page 4 - 

Vent Installation

for more information.

The fireplace dimensions are shown below:

Installation

When installing a shelf over the top of  the fireplace, the following
guidelines must be adhered to:  For Rear Vent models 

(W3400R)

, the

minimum clearance from the top of the fireplace to a shelf is 7". For
Top Vent models 

(W3400DT)

, the minimum clearance is 13".

(

Minimum 1" clearance must still be maintained around the vent

pipes.

)

Figure 3.  

Corner framing dimensions.

Figure 2.  

Framing dimensions.

* When sheetrock is
not used behind the
fireplace, framing
depth may be
reduced to 15"

Framing

WARNING:

When this appliance is installed directly on carpeting, tile or any
combustible material other than wood flooring, it must be installed
on a metal or wood panel extending the full width and depth of
the appliance.

Rear Vent

Clearances

The 

W3400 

clearances to combustible materials are:

Top - Rear Vent*

7"

Top - Top Vent*

13"

Back

0"

Side

1"

Floor

0"

Mantle**

10"

*

Clearance from the top of the fireplace to a combustible
ceiling within the fireplace enclosure.

** Refer to page 11.

If special short elbow (SEL90) is used with the Low Clearance
Sleeve (CRS30) the Top Clearance is 13".
If the standard elbow (MEL90) is used with the Low
Clearance Sleeve (CRS30) the Top Clearance is 15".

If the Low Clearance Sleeve (CRS30) is 

NOT 

used

over the elbow, the Top Clearance is 35".

Top Vent

34

24 1/2

32

12 1/8

4 3/4

4 3/4

Front View

Figure 1.

Fireplace dimensions.

15

26 1/8

32

Ø7

Ø4

34

C

15

31 1/2

Ø7

Ø4

8 3/4

33

15 3/4

36

22 1/4

42

33

59 3/8

Unprotected combustible walls which are perpendicular to the
fireplace opening, must not project beyond the shaded area shown in
Figure 19b.

For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapour barrier. This will
reduce the possibility of a cold-air convection current on the fireplace.

Figure 4.  

Framing for shelves over the fireplace.

W3400DT

W3400R

Summary of Contents for Wildfire MW34-DV

Page 1: ... Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serviceormaintenancecancause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For ...

Page 2: ...Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulating fan kit is installed it must be electrically grounded in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA must conform to local codes or in the absense of local codes to the National Fuel Gas Code ...

Page 3: ...directly on carpeting tile or any combustible material other than wood flooring it must be installed on a metal or wood panel extending the full width and depth of the appliance Rear Vent Clearances The W3400clearances to combustible materials are Top Rear Vent 7 Top Top Vent 13 Back 0 Side 1 Floor 0 Mantle 10 Clearancefromthetopofthefireplacetoacombustible ceilingwithinthefireplaceenclosure Refer...

Page 4: ...ately upstream of the gas supply controls to the appliance The fireplace gas connection and the main operating gas valve is located behind the removable brass trim at the bottom of the unit and need only be attached to the gas line with an approved fitting as required by the applicable installation codes Installation Figure 6 Fireplace locations and vent terminations Note After gas line is connect...

Page 5: ...s high rises where the termination may not be easily installed from the building s exterior 1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach by screwing through the four pilot holes in the termination 12 12 12 MOSR Installing Terminations with MSR or...

Page 6: ...the vertical dimension from the floor of the fireplace is 78 and the horizontal run to the wall flange of the vent termination is 108 this would NOT be an acceptable installation Top Vent 0 12 24 36 48 60 72 84 96 108 132 120 144 156 168 180 Horizontal Run in Hearth 0 12 24 36 48 60 72 84 96 108 Heat Shields Due to high flue temperatures heat shields are required on all 34 Series Modular Direct Ve...

Page 7: ...ure 9a Typical Top Vent installation If the 90 elbow is installed directly on the fireplace the height to the center of the termination is 44 Horizontal Venting Figure 9b Typical Top Vent installation The solid sections can be used in various combinations to obtain the desired vent run The vent run must fall within the limits set by the venting graph 90 Elbow MEXT Section Heat Shield Example 2 A 1...

Page 8: ... maintained Figure 13 Straight vertical venting using required PXT 10 adaptor Amaximumoftwooffsetswith90 bendsmaybemadeandshallnot exceedtotallengthof25 oftheverticalventheight whenmeasured center to center of piping Example Typical vent installation 20 vertical vent 2 2 offsets required 25 of 20 5 max offset allowed This venting configuration meets requirements A Termination PVTK 1 B Flex section...

Page 9: ...ons theW3400Rmaybeinstalled with 2 90 elbows and up to 15 of horizontal run If using this installationoption youmustadheretothefollowingguidelines the first 90 elbow must be placed directly on the flue collar you must have a minimum vertical lift of 50 measured from the hearth your vent run must fall within the limits set by Figure 19 Before you install any venting you must determine whether the v...

Page 10: ... frame BSR 4 4 brick frame BSR 6 6 brick frame MOSR stucco can D Flex sections PFL 1 12 section PFL 2 24 section PFL 3 36 section PFL 4 48 section E Solid sections PEXT 1 12 section PEXT 2 24 section PEXT 3 36 section PEXT 4 48 section F 90 degree elbow MEL 90 90 elbow NOTES All dimension lengths for vertical or horizontal runs are measured from center of the vent pipe Venting runs must fall withi...

Page 11: ... over coats Top of fireplace Combustible Facing Combustible construction allowed in shaded area 1 2 3 4 5 6 7 8 9 10 11 12 Figure 19a Combustible mantles and facings Mantels Surrounds NOTE National Canadian Gas Association mantel test requirements are for fire hazard prevention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted u...

Page 12: ...Gas Control SV9501M Gas Control Connector Fuse Limit Switch Wall Switch Fan Plug Receptacle Junction Box Junction Box Cover White Black Green 40 VA Transformer 115VAC 24VAC Grnd Screw Figure 20 Wiring for the W3410 with Honeywell gas control and pilot Wiring for the optional Fan and Blower Kits This fireplace may be equipped with an optional fan pack or blower for circulatingheatintothelivingspace...

Page 13: ... pull the bottom outwards and lift upwards until the slots A are clear of tabs B in the door You may need to use a flat screwdriver to pull the door surround outwards See figure 23a Machine Screws Door Rail Tabs Glass door frame Removing the door To install remove the glass door simply attach remove the ten 10 machine screws that hold door in place See figure 23b Ensure that a good seal is maintai...

Page 14: ...00 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up lower brass trim 1 Turn off remote switch 2 Flip down lower brass trim 1 STOP Read the safety information above on this label 2 Flip down lower brass trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smell gas...

Page 15: ...ppliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down lower brass trim 3 Turn the switch on the gas control to Off 4 Flip up brass trim 1 STOP Read the safety information above on this label 2 Flip down lower brass trims 3 Turn switch o...

Page 16: ...nob marked Hi Lo in the centre of the gas control valve See Figure 27 To raise the flame height turn the black knob located behind the lower trim counterclockwise To lower the flame height turn clockwise Gas Control Knob Shown in Pilot postion Hi Lo Adjustment Knob Figure 24 Hi Lo Adjustment on Model W3400 gas valve Cleaning When the fireplace is first activated there may be some smoking and a vis...

Page 17: ... SV9500 SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transformer Limit Controller Thermostat Wiring Air proving switch on combustion air blower system Vent damper if used is open and end switch made Gas Control Valve Figure 25 Sit Nova 820 gas valve Pilot Burner Adjustment 1 ...

Page 18: ...fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s exclusive remedy under this Warranty under any other warranty expressed o...

Page 19: ...uard MTKOG 7 Wildfire 4 piece Logset 8 4 Piece Picture Frame Surround PFS 9 3 Piece Picture Frame Surround PFO 10 Horizontal Trim Kits 11 Door Cover Square DF0 12 Door Cover Arched DFA 13 ControlModuleforModelW3400 14 ControlModuleforModelW3400 I 15 Aluminum Tubing 1 4 dia 16 Locking Nuts 17 Spacer 18 Bulkhead Fitting 19 90 Elbow 20 Burner Orifice 21 Burner Tube 13 10 11 14 17 18 19 21 16 15 20 7 ...

Page 20: ...Page 20 of 21 W3400 Gas Fireplace Appendix B Termination Locations 16 ...

Page 21: ...Page 21 of 21 W3400 Gas Fireplace Notes ...

Page 22: ...Page 22 of 21 W3400 Gas Fireplace Canadian Heating Products Inc Surrey BC V3W 2V6 Montigo Del Ray Corp Ferndale WA 98248 XG0107 Rev 02 04 99 ...

Reviews: