Step 1:
Construct a chase box around the vent penetration with interior
dimensions of 14 1/2" x 14 1/2" x 18" minimum in height, see
Figure 11.
Figure 11.
Chase box dimensions.
Vent Pipe
Vent Chase
Electrical Harness
with Connection
2 to 3” MAX
Step 2:
Install the Vent pipe female end up 2" to 3" maximum from the
top of the chase box. Install the electrical harness (EPVH-10-100) that will
communicate with the Power Vent module, see
Figure 11a.
Figure 11a.
Step 3:
Install the Power Vent Rough-in Kit (EPVRRF). Pull wire harness
through the supplied hole in the bottom corner of the rough-in box and snap
into the slot provided, see
Figure 11b
inset.
R520 & R620 Power Vent Indoor Gas Fireplace
Page 17
XG0771 - 040513.3
Installation
Section 3-2-1: Installing Roof Mounted Power Vent (EPVRR)
and Rough-in Frame (EPVRRF)