C38-VF Gas Fireplace

Part No. XG0317

Installing The Gas Line

The gas line must be installed before finishing the C38-VF Fireplace. 

Natural gas

 requires a minimum  inlet gas supply  pressure of 5.5" 

W.C. & a manifold pressure of 3.5" W.C. 

Propane gas

 requires a 

minimum inlet gas supply pressure of 11" W.C. & a manifold pressure 

of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged 

tapping and be accessible for test gauge connection immediately 

upstream of the gas supply controls to the appliance. The fireplace 

gas connection and the main operating gas valve is located behind 

the removable brass trim at the bottom of the unit and need only be 

attached to the gas line  with an approved fitting, as required by the 

applicable installation codes

.

Installation

Note:

  After gas line is connected, 

each 

appliance connection

,

 

valve and valve train

 must be checked while under normal 

operating pressure with either a liquid solution, or leak 
detection  device,  to  locate  any  source  of  leak. Tighten 
any areas where bubbling appears or leak is detected until 
bubbling stops completely or leak is no longer detected. 

DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The 

C38-VF'

s gas valve, located behind the lower trim, may be 

connected to a wall switch. The valve generates its own power on

 a 

millivolt circuit. Use only low voltage wire, and DO NOt

 connect 

any external power to it.
Refer to Figure 13 for wiring requirements.

Note:

  The switch location must not exceed 30' from the fireplace.

Figure 6.  

Gas line access.

The appliance and its individual shutoff valve must be disconnected 

from the gas supply piping system during any pressure testing of that 

system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by 

closing its individual manual shutoff valve during any pressure testing 

of the gas supply piping system at test pressures equal to or less than 

1/2 psig (3.5 kPa).

WARNING:

Do not allow fans to blow directly into the fireplace. Avoid 

any drafts that alter burner flame patterns.
Keep appliance area clear and free from combustion mate-

rials, gasoline and other flammable vapors and liquids.

Unusually tight construction is defined as construction where:

  Walls and ceilings exposed to the outside atmosphere have a 

continuous water vapour retarder  with a rating of 1 perm ( 6x 10 

-11

 

kg per pa-sec-m

2

) or less with openings gasketed or sealed, and

  Weather Stripping has been added on openable windows and 

doors, and

  Caulking or sealants are applied to areas such as joints around 

window doors and frames, between sole plates and floors, be-

tween wall-ceiling joints, between wall panels, at penetrations for 

plumbing, electrical and gas lines, and at other openings.

4 1/2

Gasline access

3 ¼ x 2 1/2"

1

Summary of Contents for C38-VF

Page 1: ... exactly a fire or explosion may result causing property damage personal injury or loss of life For Your Safety Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate com bustion and ventilation air must be provided Refer ...

Page 2: ...or servicing an ap pliance must be replaced prior to operating the heater Installationandrepairshouldbedonebyaqualifiedservice person The appliance should be inspected before use and at least annually by a professional service person Morefrequentcleaningmayberequiredduetoexcessive lint from carpeting bedding material etc It is imperative that control compartments burners and air circulating WARNIN...

Page 3: ... fireplace to a combusti ble ceiling within the fireplace enclosure Refer to page 5 Unprotected combustible walls which are perpendicular to the fire place opening must fall within the limits outlined in Figure 7b For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection ...

Page 4: ...s own power on a millivolt circuit Use only low voltage wire and DO NOT connect any external power to it Refer to Figure 13 for wiring requirements Note The switch location must not exceed 30 from the fireplace Figure 6 Gas line access The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures i...

Page 5: ...D IN ANY WAY to do so restricts the air supply for the control compartments and heat exchanger it also prevents access for servicing controls The face of the fireplace may be painted to match the room decor provided you use a heat resistant paint Decorative facing must not extend past the fireplace opening at all because it will interfere with the access to retainers for removal of screen door Fig...

Page 6: ...e installing the door To re install the door tilt the top edge towards you and line up the tabs of the bottom of the door with the slots on the fireplace Place the tabs into the slots and tilt the top of the door back towards the fireplace as far as it will go Close the latches by hooking Part B onto the groove at the top of the door and pushing Part A down completely Figure 8b Removing the door I...

Page 7: ...Operating Instructions 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you ...

Page 8: ...d service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water Operating Instructions Lighting Instructions See page 7 Burner Adjustment The C38 VF is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve S...

Page 9: ...nections are faulty Check wiring diagram figure 11 Main burner will 1 Check wiring see figure 11 not light 2 Check wall switch for proper con nection Figure 13a Wiring for optional air circulating fan kit Wiring for the optional Fan Kit All C38 VF fireplaces may be equipped with an optional fan kit Part no RFK1002 or RFK1003 for circulating heat into the living space Kits are available with manual...

Page 10: ...roduct If they can not supply original replacement part s Call toll free at 1 800 378 3115 Canadian Heating Products Montigo Delray Corp 27342 Gloucester Way Langley BC V4W 4A1 When contacting dealer or Montigo please have the following ready Your name and address Part number and description of part or acces sories to be replaced Model and serial numbers of your heaters Type of Gas used Natural Ga...

Page 11: ...g from the use of any components not manufactured or supplied by Montigo DelRay Corp 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liab...

Page 12: ...XG0317 Rev 0 9 2002 Installed and Serviced by Montigo Del Ray Corp 6955 Salashan Parkway 27342 Gloucester Way Ferndale WA 98248 Langley BC ...

Reviews: