C38-DV Gas Fireplace

Part  No.  XG0118C

Maintenance

Gas Control Valve (C38-DV)

Figure  27 

Sit  Nova  820 

gas  valve

.

Pilot Burner Adjustment (C38-DV)

1. Locate Pilot Adjustment Screw. 

(See figure 27.)

2. Adjust pilot screw to provide properly sized flame as shown in 

 figure

28).

3. After installing or servicing, leak test with a soap solution with main

burner on. Coat pipe and tubing joints, gasket etc. with soap solution.
Bubbles indicate leaks. Tighten any areas where the bubbles
appear until the bubbling stops completely.

Figure  28. 

Pilot  Burner

Manifold Pressure
Test Connection

Pilot Adjustment Screw

Inlet
Pressure

Power
Generator

Wall Switch

Troubleshooting

The  following  is  a  troubleshooting  chart  of  possible  problems:

PROBLEM

CORRECTIVE  ACTION

Noisy  Pilot  Flame

Locate  pilot  adjustement  screw  on
gas control valve. Flame is decreased by
turning  adjustment  screw  clockwise.

Pilot  won’t  ignite

Disconnect  remote  wires  and  try  to
light  pilot.  If  pilot  now  works,  remote
connections  are  faulty.  Check  wiring
diagram 

figure

 

27

.

Main  burner  will

1.  Check  wiring  (

see  figure  27

).

not  light

2.  Check  wall  switch  for  proper
connection.

C38-DV

Troubleshooting

If your fireplace still does not operate correctly, consult your dealer or
the manufacturer.

All service and repairs should be performed by a qualified
agency.

All spare parts, optional fans, and optional trim finishes are available
from your local dealer or the manufacturer.

HONEYWELL SV 9500 /SV9600

Troubleshooting Sequence

NOTE:

Before Troubleshooting, Familiarize Yourself With

The Startup And Checkout Procedure.

· Turn Gas Supply off

· Set thermostat to

call for heat

SV9500/SV9600

is powered

(24 VAC nominal)

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

START

Igniter warms up

and glows red.

Pilot Valve opens.

Turn gas on.

Pilot Burner lights?

Main Valve opens?

SYSTEM OK

Unplug Pilot Burner Cable,

Measure Voltage at

SV9500/SV9600 HSI

Terminals (24 VAC

Nominal, See INSET)

Replace Igniter/

Flame Rod Assembly.

Replace Igniter/

Flame Rod Assembly.

Replace SV9500/SV9600

Measure Voltage to SV9500

/SV9600. Voltage must

be at least 19.5 VAC

Discard old Igniter/

Flame Rod Assembly.

Replace Igniter/Flame

Rod Assembly and retain.

Restart Troubleshooting

Sequence. Does main

valve open?

Replace

SV9500/

SV9600

Check

Transformer

Line Volt

Supply

Replace

SV9500/

SV9600.

Save old

Igniter/Flame

Rod Assembly

for service.

INSET

HSI

Terminals

CHECK:

· Line voltage power

· Low voltage transformer

· Limit Controller

· Thermostat

· Wiring

· Air proving switch on

combustion air blower system

· Vent damper (if used) is open

and end switch made

C34-DV-I

Summary of Contents for C38-DV

Page 1: ...your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serv...

Page 2: ...o the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulatingfankitisinstalled itmustbeelectricallygroundedin accordance with CSA C22 1 Canadian Elect...

Page 3: ...Vent Rear Vent Figure 3 Corner framing dimensions Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framing depth may be reduced to 16 7 8 Framing WARNING When this appliance...

Page 4: ...ne Gas requires a minimum inlet gas supply pressure of 11 W C a manifold pressure of 10 W C Provision must also be made for a 1 8 N P T plugged tappingandbeaccessiblefortestgaugeconnectionimmediately...

Page 5: ...1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach...

Page 6: ...lation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termina tion is 84 this would NOT be an acceptable installation Figure 7 Ve...

Page 7: ...Figure 10 and 11 C flex sections and D rigid sections may be used in conjunction with oneanothertoobtaindifferentpossiblehorizontallengthinstallations NOTE Flex section with no vertical rise must not...

Page 8: ...required adaptor n A maximum of two offsets each offset has two 90 bends may be madeandshallnotexceedtotallengthof25 oftheverticalventheight when measured center to center of piping Example Typicalve...

Page 9: ...supplied with a 20 extension pipe PXT 20 with female female connections For shorter installations cut the PXT 20 to the desired length For extended installations use the PXT 20 section as supplied fo...

Page 10: ...tical dimension from the hearth is 90 and the horizontal run to the wall flange of the vent termination is 126 this would be an acceptable installation Example C Unacceptable Installation If the verti...

Page 11: ...ntel hearth or surround New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficie...

Page 12: ...t plug to motor Wiring for the optional Fan Kit All C38 DV fireplaces may be equipped with optional fan kits Part no RFK1001 RFK1003 RFK1006 or RFK1007 for circulating heat into the living space Insta...

Page 13: ...he trim over to the retainer clips on either side of the fireplace Push the bottom edge firmly inwards and the trim will snap on See figure 25 Remember to slide the baffle into the top trim piece See...

Page 14: ...el C38 DV 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information abo...

Page 15: ...ight any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn of...

Page 16: ...ing Instructions See pages 14 and 15 Burner Adjustment TheC38 DV millivoltmodelonly isequippedwithanadjustable burner allowingyoutoraiseorlowertheflames Toadjusttheflames locatetheblackknobmarked Hi L...

Page 17: ...t your dealer or the manufacturer All service and repairs should be performed by a qualified agency All spare parts optional fans and optional trim finishes are available from your local dealer or the...

Page 18: ...ultinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobliga...

Page 19: ...ited States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 B...

Page 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0118C Rev 00 04 03...

Reviews: