C38-DV Gas Fireplace

Part  No.  XG0118C

Vent  Installation

This section covers the installation of direct venting and terminations.

Installation Requirements

n

C38-DV fireplaces are certified for use with Montigo Premium Series
(5" / 8") venting components. The C38-DV Top Vent may be used
with Standard Series (4"/7") components on vertical vent runs only.

n

Minimum 1" clearance to combustibles required for vent pipes

n

Use  only 

certified  Montigo  vent  components.

  (Use  of  other

parts  will  void  the  Montigo  warranty,  and  may  impede  the
operation  of  the  fireplace.)

n

All joints must be secured with a minimum of two screws per joint

n

Vent terminations must not be recessed in walls or siding

n

Horizontal runs must be supported by a minimum of two supports
per horizontal run. A minimum of one screw on each side of
support is also required

n

Flex vent sections may be stretched up to 50% of their total length
(eg. a 24" section may be stretched to 36")

n

Maximum horizontal run for a flex section with no vertical rise is 3 feet.

n

Flex vent sections over 3 feet must fall within the limits set by the
venting graph and must have a minimum vertical rise of 3 inches
per foot of flex.

n

Solid vent sections may be cut less than half way from the tapered end

n

Venting components can be used in any combination of solid/rigid
pipe or flex pipe and in any orientation (Male connectors can face
in any direction)

Vent Terminations

Selecting A Termination Location

Choosing your vent termination location will help to determine whether
you need to use a top vent or rear vent fireplace. Figure 6, below,
shows typical fireplace locations and the venting options they provide.

For a more detailed diagram of allowed termination locations, see

Appendix A

.

Cautions:

Cautions:

Cautions:

Cautions:

Cautions:

Installing The Gas Line

The gas line must be installed before finishing the C38-DV Fireplace.
Natural Gas requires a minimum  inlet gas supply  pressure of 5.5"
W.C. & a manifold pressure of 3.5" W.C. Propane Gas requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace gas
connection and the main operating gas valve is located behind the
removable brass trim at the bottom of the unit and need only be
attached to the gas line  with an approved fitting, as required by the
applicable installation codes.

Installation

Figure 6.

  

Fireplace locations and vent terminations.

Note:

After gas line is connected, each 

appliance connection

,

valve  and  valve  train

  must  be  checked  while  under

normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.
DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The C38-DV's gas valve, located behind the lower brass trim, may be
connected to a wall switch. The valve generates its own power on a
millivolt circuit. Use only low voltage wire, and DO NOT
 connect
any external power to it.

Refer to Figure 27 for wiring requirements.

Note:  The switch location must not exceed 30' from the fireplace.

Figure 5.  

Gas line access.

The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).

n

Vent terminations can be very hot. If the termination is less than
7 feet above a public walkway, it should be fitted with a certified
Montigo Heat Guard. (Part no. PTKOG)

n

Do not obstruct, or attempt to conceal, the vent termination.
These actions will affect the operation of the fireplace, and may
be hazardous.

n

In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.

Summary of Contents for C38-DV

Page 1: ...your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration serv...

Page 2: ...o the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations If the optional air circulatingfankitisinstalled itmustbeelectricallygroundedin accordance with CSA C22 1 Canadian Elect...

Page 3: ...Vent Rear Vent Figure 3 Corner framing dimensions Figure 2 Framing dimensions When sheetrock is not used behind the fireplace framing depth may be reduced to 16 7 8 Framing WARNING When this appliance...

Page 4: ...ne Gas requires a minimum inlet gas supply pressure of 11 W C a manifold pressure of 10 W C Provision must also be made for a 1 8 N P T plugged tappingandbeaccessiblefortestgaugeconnectionimmediately...

Page 5: ...1 Frame the termination opening to 12 x 12 2 Fasten the MOSR frame to the interior side of the studs using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here and attach...

Page 6: ...lation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termina tion is 84 this would NOT be an acceptable installation Figure 7 Ve...

Page 7: ...Figure 10 and 11 C flex sections and D rigid sections may be used in conjunction with oneanothertoobtaindifferentpossiblehorizontallengthinstallations NOTE Flex section with no vertical rise must not...

Page 8: ...required adaptor n A maximum of two offsets each offset has two 90 bends may be madeandshallnotexceedtotallengthof25 oftheverticalventheight when measured center to center of piping Example Typicalve...

Page 9: ...supplied with a 20 extension pipe PXT 20 with female female connections For shorter installations cut the PXT 20 to the desired length For extended installations use the PXT 20 section as supplied fo...

Page 10: ...tical dimension from the hearth is 90 and the horizontal run to the wall flange of the vent termination is 126 this would be an acceptable installation Example C Unacceptable Installation If the verti...

Page 11: ...ntel hearth or surround New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficie...

Page 12: ...t plug to motor Wiring for the optional Fan Kit All C38 DV fireplaces may be equipped with optional fan kits Part no RFK1001 RFK1003 RFK1006 or RFK1007 for circulating heat into the living space Insta...

Page 13: ...he trim over to the retainer clips on either side of the fireplace Push the bottom edge firmly inwards and the trim will snap on See figure 25 Remember to slide the baffle into the top trim piece See...

Page 14: ...el C38 DV 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information abo...

Page 15: ...ight any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn of...

Page 16: ...ing Instructions See pages 14 and 15 Burner Adjustment TheC38 DV millivoltmodelonly isequippedwithanadjustable burner allowingyoutoraiseorlowertheflames Toadjusttheflames locatetheblackknobmarked Hi L...

Page 17: ...t your dealer or the manufacturer All service and repairs should be performed by a qualified agency All spare parts optional fans and optional trim finishes are available from your local dealer or the...

Page 18: ...ultinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobliga...

Page 19: ...ited States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 B...

Page 20: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0118C Rev 00 04 03...

Reviews: