Monogram JXBC57 Installation Instructions Manual Download Page 14

14

Installation

Downdraf t Vent Systems

1

Install
Downdraft
Vent

Step

2

Install the
Ductwork

Step

Place the downdraft vent into the countertop
cutout, against the back side.
• Secure the downdraft to the countertop

supplied brackets. See illustration.

– Fasten brackets to top screws on the front

side of the vent, secure to cabinet side wall
just below the countertop. Or,

– Fasten one bracket to vent side and secure

to cabinet back wall.

– Install two brackets on the bottom of the

vent. Attach brackets to slide screws on the
vent and to the floor using wood screws
(not supplied).

• When installing in a tile countertop surface,

it may be necessary to apply a locally
approved caulking to cover any gaps.

• The downdraft blower system is designed for

use with 3-1/4" x 10" ductwork. It can be
transitioned to 6" round.

• Ductwork MUST be vented to the outside –

never into a crawl space, attic or other
enclosed space.

• 6" PVC duct should be used when installing

under a concrete slab.

Note:

 Local building code must be followed

for installation and in specifying approved
type and schedule of PVC duct used.

• DO NOT USE flexible plastic ducting.
• Always use appropriate roof or wall cap with

damper. Laundry type wall caps should
never be used.

• Use the straightest duct run possible.
• For satisfactory performance the duct run

should not exceed 150 ft. or its equivalent

Duct Tape
Over Seam and Screw

Screw

Air

Flow

Secure the Lower Brackets

to Blower Housing

Preferred Method
Secure the Upper
Brackets With Screws
Located on the side of
Case and Attach to
Back Wall of Cabinet

Optional Method
Secure to Cabinet
Side With Top
Screw on Case

Or Use Second Screw

length when bends or various fittings are
used. Refer to the table of equivalent
lengths to calculate your installation.

• Install ductwork so the piece of duct nearest

the downdraft unit slots INTO the next
piece of the duct. Secure the joints with self-
tapping screws and apply duct tape around
the joints to ensure an airtight seal.

Summary of Contents for JXBC57

Page 1: ...ram We bring good things to life If you have questions call 800 GE CARES or visit our website at www monogram com Installation Instructions Downdraft Vent Systems 36 Wide Models ZVB36 30 Wide Models Z...

Page 2: ...evice such as a tag to the service panel Do not attempt to repair or replace any part of the downdraft system unless it is specifi cally recommended in this book All other servicing should be performe...

Page 3: ...white black and stainless steel JXRB57 optional accessory for indoor remote location of the blower motor assembly Use this kit when the blower and motor assembly will be located outside or below the c...

Page 4: ...the countertop Include the trim thickness when measuring front edge to cutout requirement By adding the trim the cooktop can be moved forward providing additional countertop depth and interior cabine...

Page 5: ...efully Gas or electrical outlets cannot be placed on the back wall of the cabinet because it may interfere with the downdraft plenum Install a standard electrical outlet within reach of the vents two...

Page 6: ...ollow as a cutting guide Measure and mark cooktop and vent overlaps to be sure there is enough flat countertop depth ZEU769 Electric Cooktops with 36 Vent Countertop Cutout Requires 22 1 2 flat counte...

Page 7: ...4 3 4 2 1 2 to Cutout ZEU30 Cooktop 1 7 8 DOWNDRAFT VENT 20 3 8 Cabinet Requires 23 inside cabinet depth See Creative Solutions install in an island or move cabinet base forward 34 Cooktop and Vent Cu...

Page 8: ...ombustible Surface 6 Min Cutout to Side Walls 3 4 22 3 4 to Back Wall 22 to Support Rail 24 3 4 2 1 2 to Cutout ZGU36 Cooktop 1 7 8 3 4 Thick Support Rail 20 1 16 DOWNDRAFT VENT 35 5 16 Cooktop Area C...

Page 9: ...30 Min 18 Min 8 Min to Wall When Installed 8 Min to Installed Wall When Electric Cooktop Models Gas Cooktop Models Tools and Materials Required Large flat blade screwdriver Jig saw Carpenter s square...

Page 10: ...t A properly grounded 3 prong receptacle should be located within reach of the vents two foot power cord Locate the receptacle inside the cabinet on the right side wall The receptacle cannot be placed...

Page 11: ...ower mounting plate can be adjusted 3 1 2 to the left or right This will help to align vent discharge to house ductwork 30 Rotation For even more flexibility the entire blower can be rotated up to 30...

Page 12: ...rge Remove and turn the blower to the right or left Reinstall the 4 nuts To locate the ductwork holes in the cabinet floor or side walls Temporarily place vent into the countertop opening Push the ven...

Page 13: ...lengths Flexible ducting If flexible metal ducting is used all the equivalent feet values in the table should be doubled The flexible metal duct should be straight and smooth and extended as much as p...

Page 14: ...nclosed space 6 PVC duct should be used when installing under a concrete slab Note Local building code must be followed for installation and in specifying approved type and schedule of PVC duct used D...

Page 15: ...side of countertop and thread the wire lead into the end of the wire box Peal film from the back of the switch trim to expose the adhesive Press trim onto the mounting bracket to set the adhesive Peal...

Page 16: ...fan OFF before lowering the vent The fan will auto matically turn off when the vent is lowered When the fan is not turned off before lower ing the vent it will automatically come on at the previously...

Page 17: ...upplied This kit provides for the installation of the blower and motor outside of the cabinet such as below the floor Use this kit for indoor remote installations only Note A 3 1 4 x 10 transtion to 6...

Page 18: ...sed parts If the appliance is relocated at a later time parts may be needed Blower Blower Mounting Plate Blower Box Hidden Screws 2 Determine Blower Location Step 1 continued Step Determine location o...

Page 19: ...ct to the 6 round inlet on the blower Tape to seal all joints Use electrical cable and connectors that conform to local codes 14 gauge min is recommended Use a length to reach between the vent and the...

Page 20: ...nd connectors sufficient length to connect the downdraft vent to the remote blower location 14 guage min is recommended must conform to local codes Tools required Pencil or chalk Measuring tape Drill...

Page 21: ...wiring or hidden utilities Check for interference with floor joists and stud walls If necessary locate the base to provide a secure installation Place a 6 round duct through the hole extending approxi...

Page 22: ...of the right side Reverse plates for a right side discharge A transition is required to connect the 3 1 4 x 10 duct to the 6 round inlet on the blower Tape to seal all joints 4 Connect Blower Wires St...

Page 23: ...w wiring Use wire nuts to secure the wire to the 3 remaining wires with plug Insert the plug into the mating plug on the vent Reinstall wire box with original screws Mount the blower onto the mounting...

Page 24: ...glasses or goggles should be worn For Monogram local service in your area call 1 800 444 1845 NOTE Product improvement is a continuing endeavor at General Electric Therefore materials appearance and...

Reviews: