General Safety
CAUTION:
It is essential that all instructions in this manual be
followed to ensure proper operation of the equipment and safety
of operating personnel. The use of this symbol is used through-
out manual to highlight important safety issues. Please pay par-
ticular attention to these items.
Electrical Shock Caution:
Certain
Dust
Alarm
®
ES
monitors are powered with HIGH VOLT-
AGE. No operator serviceable parts are inside. All servicing is
to be performed by qualified personnel. Each
Dust
Alarm
®
ES
unit is provided with a "protective conductor terminal"
which shall be terminated to earth ground potential (See
Electrical Installation). This product's design complies with
EN61010-1 installation category 1 (230VAC unit), category II
(115VAC unit), category III (VDC unit) and pollution degree 2.
Electromagnetic Compatibility (EMC) for Emissions & Immunity
The
Dust
Alarm
®
ES
was tested and found compliant according
to applicable standards:
IEC/EN 61326-1
Electrical Equipment for Measurement, Control &
Laboratory Use - EMC Requirements
SAFET Y
SPECIFICATIONS - CONTINUED
WARRANT Y
Monitor Technologies LLC warrants each
Dust
Alarm
®
ES
Broken
Bag Detector it manufactures to be free from defects in material and
workmanship under normal use and service within two (2) years from
the date of purchase. The purchaser must give notice of an defect to
Monitor Technologies LLC within the warranty period, return the prod-
uct intact and prepay transportation charges. The obligation of
Monitor Technologies LLC under this warranty is limited to repair or
replacement at its factory. This warranty shall not apply to any prod-
uct which is repaired or altered outside of the Monitor Technologies
LLC factory, or which has been subject to misuse, negligence, acci-
dent, incorrect wiring by others or improper installation. Monitor
Technologies LLC reserves the right to change the design and/or
specifications without prior notice.
Power Requirements:
Power Consumption:
Fuse Breaking Capacity:
(Haz-Loc Rating)
Altitude:
Installation Category:
Pollution Degree:
Process Temperature:
Starting Ambient Temp.:
Running Ambient Temp.:
Ambient Humidity:
Relay Outputs:
(2 Isolated SPDT)
Relay Setpoint:
Relay Threshold Range:
Relay Time Delay:
Fail-Safe State:
Digital Link, Hardware:
Digital Link, Protocol:
Running Averaging:
Local Indicator:
Conduit Connections:
Housing:
Mounting:
Pressure:
Insulation Material:
Probe Material:
Probe Length:
Ship Dims & Weight:
Approvals:
MET
US/C
:
ATEX/IECEx:
Conformity:
95-240VAC (±10%), 50/60 Hz;
18-28VDC (±10%)
≤ 5VA (AC); ≤ 2.5W (DC)
1500A @ 250VAC;
300A @ 30VDC
6,562 ft (2000m) max
II
2
Max: 392°F (200°C) at probe location. (CL ll)
Class III installations: Process tempera-
ture must not exceed 325°F (164°C)
4° to 149°F (-16° to 65°C)
-22° to 149°F (-30° to 65°C)
Max 95% RH, non-condensing
3A @ 250VAC max each
3A @ 30VDC max each
Factory default:
Alarm-1: 5x ref value
Alarm-2: 20x ref value
1,000,000,000 Max Units
0 to 60,000 sec
(30 sec factory default)
Alarm
RS-485 (3-wire, half duplex, isolated)
Modbus RTU
(Default serial:
Baud Rate: 38.4K
Data bits: 8
Parity: N
Stop Bits: 2)
0 to 6,553 sec time constant
(100 sec factory default)
Bi-color LED:
Green On = Power Applied
Green Flashing = Auto Setup
Red On = Pre-Alarm
Red Flashing = Alarm
Alternating Red / Green = Error
No Light = No Power
(2) 1/2” NPT
Powder coated die-cast aluminum;
NEMA 4X, ENCLOSURE TYPE 4X,
IP66
1” Tri-Clamp Type Quick-Disconnect,
316 SS
87 psi maximum
PPS
0.39” diameter, 316 Stainless Steel
Cust. Specified Length - CSL:
4.75” (121mm) to 20” (508mm)
[Solid coupling extensions up to 24”
(610mm) available.]
35.5”Lx8”Wx8”H; 7 lbs Approx.
(902x203x203mm; 3.2kg Approx.)
Ordinary Locations;
Hazardous Locations with intrinsically
safe probe [Ex ia]
US/CAN
: Class II, Division 1, Groups E,F,G
T85°C…T201°C -30°C≤T
amb
≤+65°C
Class III T85°C…T165°C
-30°C≤T
amb
≤+65°C
US
: Zone 20 AEx ia ta IIIC
T85°C…T201°C Da -30°C≤T
amb
≤+65°C
CAN
: Ex III 1D Ex ia ta IIIC T85°C…
T201°C Da -30°C≤T
amb
≤+65°C X
Ex II 1D Ex ia ta IIIC
T85°C… T201°C Da -30C≤Tamb≤+65C X
CE Mark;
CHINA RoHS 2
Probe Cleaning Procedure:
1)
Clean the sensor probe and especially the insulator with
a damp rag and allow to dry; do not use liquids – install the
sensor in the duct or the Faraday shield. If the red LED is on
or flashing, the sensor was fouled by a build-up of conductive
material over the insulator.
2)
If cleaning did not eliminate the false signal, consult the
factory for assistance.
If the preceding information and procedures contained within
the Troubleshooting and Maintenance sections do not prove
sufficient, contact the factory.
7
SPECIFICATIONS
Fuses -
External circuits connected to RELAY-1 &
Haz-Loc Versions: RELAY-2 terminals:
shall be provided with fuses
conforming to the IEC 60127 series and UL 248 series.
Fuses shall be rated for 5A max, 250VAC or 30VDC.
AC Mains Supply:
AC input power terminals shall
be protected by a fuse value no greater than 85mA.
DC Supply:
DC input power terminals shall be
protected by a fuse value no greater than 250mA.