background image

4

Non-Metallic Ducts:

If the 

Dust

Alarm

®

ES

is to be mounted in a non-metallic pipe or

duct, the following special precautions must be taken to prevent

the detection of stray electric fields:

1)  Light Dusting

- If the unit is to be installed after a dust col-

    lector where only a light dust loading is present, an electro-

    static (Faraday) shield must surround the pipe or duct for 

    a distance equal to three times the duct diameter both up 

    and down stream.  The shield must make contact with the 

    external ground screw on the 

Dust

Alarm

®

ES

and a reliable 

    earth ground. Hardware cloth, screen material or rabbit 

    wire are satisfactory shield material.

2)  Heavy Dusting

- If a heavy dust loading is present, the unit 

    must be installed in a section of metallic pipe or duct.  This 

    section should extend as far up stream as possible or down

    stream for a distance equal to two times the duct diameter 

    and must be connected to a reliable earth ground.  

    

NOTE:

The 

Dust

Alarm

® 

ES

mounting must be provided with 

ELECTRICAL INSTALL ATION

1)          Hazardous  Location  Precautions

-  Observe  the  regulations

listed in the NEC (USA) or CEC (Canada) and all others with site juris-

diction regarding equipment in hazardous locations when installing the

hazardous location models of the 

Dust

Alarm

®

ES

sensor in hazardous

classified  locations.  Wiring  and  all  installation  methods  must  be  per-

formed according to the authority having site jurisdiction and is the sole

responsibility of the installer to ensure such.

            Haz-Loc Versions: External circuits connected to RELAY-1 & RELAY-2

terminals shall be provided with fuses conforming to the IEC 60127 series and

UL 248 series. Fuses shall be rated for 5A max, 250VAC or 30VDC.

            Ensure power is disconnected from the sensor, or the area has

been cleared of hazardous conditions before the cover is removed. A

locking mechanism on the back of the enclosure is provided to prevent

removal of the cover without the use of a tool. 

Electrostatic charges:

The equipment shall not be installed in a location where the external condi-

tions are conducive to the build-up of electrostatic charges. 

l

Avoid all materials which could be capable of generating electrostatic 

charges at the installation location 

l

The equipment shall only be cleaned with a damp cloth and allowed to dry

l

Make sure that the equipment is properly connected to a stable ground 

potential either at the external or internal grounding connection

            It is important to note that the hazardous location models are

certified with two protection concepts: The probes and wires from the

probes to the sensing electronics board within the enclosure are an

intrinsically safe circuit. The enclosure and main electronics within are

not intrinsically-safe; Therefore, protection is by dust-ignition proof

enclosure. One conduit entry is provided with a metallic plug, factory

installed. This plug (blanking element) cannot be substituted or

replaced with other than that acquired from the factory.

Conduit fittings must be rated IP64 minimum for hazardous locations-only.

2)  Factory Wiring

- The probe wires internal to the housing are connected

to the front side of the PCB. 

DO NOT

alter this connection. Doing so will

likely cause improper operation or permanent damage to the device. 

3)  Permanently Connected Equipment

- Disconnecting devices shall

be included in the system installation. In installations where multiple cir-

cuits are used (i.e. independent circuits for power input and relay out-

put), individual disconnects are required. The disconnects shall be with-

in close proximity of the equipment, accessible to operators, and marked

appropriately as the disconnect for the associated circuit. Ensure the

disconnect ratings are appropriately sized to the circuit protected (See

Specifications). The MAINS power that connects to the sensor MUST

provide circuit protection and NOT exceed 20A total.

4)  Disconnects Separation

- It is recommended to span from 

the disconnects to the sensor with a long enough section of 

flexible conduit that will allow the probe to be removed from 

ducting for easy inspection and cleaning.

5)  Circuit Separation

- Two cable/conduit entry locations are 

provided to aid in maintaining separation of “hazardous live” 

(typical mains voltages such as 115VAC or 230VAC) and limited cir-

cuits (typically control voltages less than 30Vrms or 42.5VDC).  It is

required that all wiring used must have an insulation rating of 300v

minimum, and a temperature rating of 221˚F (105˚C) minimum.

2)  Vibration

- The unit is designed for use in conjunction with 

    baghouse and dust collector systems.  As such it is provided

    with a rugged cast aluminum enclosure.  However, care 

    should be taken to protect the unit from excessive vibration, 

    which can cause physical damage to the electrical circuit 

    boards and connections.

3)  Temperature Limits

- The operational temperature limits must 

     be maintained to ensure reliable operation (See Specifications). 

     Enclosure surface temperature is dependent on the process 

     temperature.  At  a  process  temp  of  200

o

C  and  the  enclosure 

     housing & the electronics outside of the process, the maximum 

     enclosure surface temp "T" rating of 85

o

C applies.

4)  Other Location Considerations 

- The location should be a 

     sufficient distance from the stack exit so that outside atmospheric

     conditions will not affect the sensor.  For example, heavy rain may

     cause a false signal if the sensor is located in a vertical stack.

MECHANICAL INSTALL ATION

The 

DustAlarm

®

ES 

mounts to a tri-clamp quick-disconnect fer-

rule  (also  available  from  Monitor Technologies)  that  has  to  be

installed into the air duct for easy installation and maintenance of

the sensor. The ferrule is typically welded to the duct. Be sure to

remove the gasket and clamp from the ferrule before welding.

Also before welding, ensure that when the 

DustAlarm

®

ES

sensor

is installed such that the probe insulator protrudes into the duct at

least 0.75” [19mm] and is exposed to airflow. (See Figure 3). 

WR'

'

'

&/$03(',13/$&(

72'8&7

,172$,5)/2:

:,7+*$6.(7

)(558/(:(/'('

352%(

,168/$725352758',1*

$&7,9(

'8&7:$//

02817,1*48,&.',6&211(&7&/$03

Figure 3

    a local earth ground, either through the duct-work and 

    

Dust

Alarm

®

ES

mounting or by a separate means connected

    to the mounting. The safety (protective earth) ground is 

     provided through the electrical power supply connection.

Test Port:

For negative pressure systems, to aid in troubleshooting, it is recommend-

ed that a test port be installed upstream from the sensor  as a means to

inject sample dust material. The port’s distance from the sensor should be

approximately equal to two times the duct diameter and on the same side

of the duct.  A plugged half coupling is sufficient.
Failure to correctly install the 

Dust

Alarm

®

ES

may prevent the unit from

operating  reliably;  therefore,  any  modifications  to  these  procedures

should be discussed with the factory.

DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS

(Suggested Min. 0.75” [19mm])

(Recommended)

Summary of Contents for DustAlarm ES

Page 1: ...uipment and the safety of all personnel Before discarding shipping container please inspect it thoroughly and verify that all parts ordered are accounted for Sometimes smaller parts become stuck under carton flaps and other packaging materials In the event that information contained herein does not completely satisfy your requirements or answer your questions you may contact Technical Support on o...

Page 2: ...m of a dust collec tion system Signal output is varied as the measured dust changes When the signal generated by moving dust particles exceeds a preset threshold an alarm output is generated Influence of Particle Material The signals transmitted by different types of dust particles can vary greatly from one material to another For example Inorganic electro conductive materials metals create the lo...

Page 3: ...cting where there is laminar flow and the dust particles are evenly dis persed within the air stream This ensures the sensor probe is exposed to a particle stream in an area where the most stable airflow condition exists Such an area has no airflow disturbance caused by elbows duct size transitions diverter valves etc In the event there are such flow disturbances near the selected mounting area en...

Page 4: ...ion In installations where multiple cir cuits are used i e independent circuits for power input and relay out put individual disconnects are required The disconnects shall be with in close proximity of the equipment accessible to operators and marked appropriately as the disconnect for the associated circuit Ensure the disconnect ratings are appropriately sized to the circuit protected See Specifi...

Page 5: ...n be daisy chained to multiple sensors on the same RS 485 network to minimize the amount of wiring Protocol used on this network is Modbus RTU The RS 485 network cabling should be a single route that travels from device to device with no branches that form T s or stars A network termination should be activated on any device that is at the physical end of an RS 485 network For the dust sensor model...

Page 6: ...minutes and is indicated by a flashing green LED Ensure no unusual events occur that could provide for false measurements during this auto setup period At the end of the of the period the green LED will become constantly lit 5 Using the Auto Set up method will automatically configure these parameters Running average of measured signal 100 sec time constant default Alarm 1 threshold 5x measured val...

Page 7: ...Pressure Insulation Material Probe Material Probe Length Ship Dims Weight Approvals MET US C ATEX IECEx Conformity 95 240VAC 10 50 60 Hz 18 28VDC 10 5VA AC 2 5W DC 1500A 250VAC 300A 30VDC 6 562 ft 2000m max II 2 Max 392 F 200 C at probe location CLll Class III installations Process tempera ture must not exceed 325 F 164 C 4 to 149 F 16 to 65 C 22 to 149 F 30 to 65 C Max 95 RH non condensing 3A 250...

Page 8: ...B U L L E T I N 764A Monitor Technologies LLC 44W320 Keslinger Rd t Elburn IL 60119 t 630 365 9403 t 800 766 6486 t monitor monitortech com t www monitortech com ARB JSC MAR 19 2021 DOC 001 764A 4 ...

Reviews: