73D4125
9
KSTDV Series Gas Fireplace
clearanceS
clearanceS To coMBuSTIBleS
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring, the
appliance shall be installed on a metal, wood or noncombustible material
panel extending full width and depth of the appliance.
45°
1”
4”
5”
6”
”
3”
FP2410
mantel leg clearance
ManTel clearanceS
noTe:
The combustible area above the facing must not protrude
more than 1/2" from the facing. If it does, it is considered a mantel
and must meet the mantel requirements listed in this manual.
w
arn
In
G
never obstruct or modify the air inlet or
outlet grilles (louvers). This may create a
fire hazard.
Figure 5 -
Mantel Clearance
72”
(1829 mm)
Min.
Ceiling
12”
(305 mm)
Max. Depth
16”
(406 mm)
Min.
6”
(152 mm)
Min.
FP2544
DVKST ceiling wall clearance
8” Min.
(203 mm)
Noncombustible
Figure 4 -
Ceiling and Side Wall Clearances
Combustible Mantel
FP2544
Stud
Finish Wall
Combustible
Material Area
FP2488
Top View
w
arn
In
G
CFM146d
mantel chart
16”
12”
10”
12”
6”
2
56O
”
Side View
Noncombustible
Material to Top of
Standoffs
CFM146d
Top of Fireplace
Opening