16
73D4125
KSTDV Series Gas Fireplace
A
B
10’
90°
FP2546
Horizontal run
reduction
VenTInG InSTallaTIon
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 270°
Figure 14 -
Maximum Elbow Usage
1
2
3
4
1
2
3
4
FP1180
max bends
24" Minimum
FP1180
Below GraDe InSTallaTIonS
When it is not possible to meet the required vent terminal
clearances of 12" above grade level, a snorkel kit is recom-
mended. It allows installation depth down to 7" (178 mm)
below grade level. The 7" (178 mm) is measured from the
center of the horizontal vent pipe as it penetrates through
the wall.
ensure that sidewall venting clearances are observed.
If venting system is installed below ground, we recom-
mend a window well with adequate and proper drainage
to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is neces-
sary. The maximum horizontal run with the 24” vertical pipe
is 36". This measurement is taken from the collar of the
fireplace (or transition elbow) to the face of the exterior wall.
See the Sidewall Venting Graph for extended horizontal
run if the vertical exceeds 24".
1. Establish vent hole through the wall.
2. Remove soil to a depth of approximately 16" below base
of snorkel. Install drain pipe. Install window well (not
supplied). Refill hole with 12" of coarse gravel leaving
a clearance of approximately 4" below snorkel.
Figure
15
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
7. Level the soil so as to maintain a 4" clearance below
snorkel.
Figure 15
Figure 13 -
Horizontal Run Reduction
FP2546
FP2134
below grade install
FP2134
Figure 15 -
Below Grade Installation
Screws
Minimum
4" Clearance
Ground
Window Well
Gravel
Drain
Foundation Wall
Firestop
24"
Minimum