background image

17

C

HIMNEY

 O

FFSET

 I

NSTALLATION

E

LBOW

 I

NSTALLATION

NOTE: If triple wall elbow is to be placed directly to the top of the fireplace, it will be necessary to bend a tab
over located on each of the four inlet air collar brackets. bend these tabs over only when using a triplewall
elbow to start a chimney run. The tabs may be easily bent with your fingers or pliers. See figure 16A.
The following are important points that should be observed when installing elbows on the fireplace:
1. The support straps of all elbows not installed directly on top of the fireplace should be nailed securely to the

surrounding structure.  This allows the support strap to carry the weight of the chimney above the elbow
and prevents this weight from breaking the elbow or chimney sections apart.  See  Figure 16.

2. Elbows should not be used in any combination that inclines the chimney more than 30 degrees from vertical.
3. The limitations on the quantity of elbows per chimney are as follows: If the total height of the fireplace and

chimney is — 16' 0" or more  —  two elbows may be used in the chimney.  21' 0" or more  —  four elbows
may be used in the chimney.

4. The inclined portions of chimneys that pass through living spaces likely to be used for storage should be

enclosed to avoid contact with and possible damage to the chimney.  The minimum air space of two inches
between the chimney and enclosing materials must be maintained.  Figures 17 and 18 illustrates elbow
installations.

5. The length of the inclined portion of chimney between elbows must not exceed 6 feet when unsupported or

20 feet if the chimney is supported at six-foot intervals with support such as metal support straps.

6. When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed

vertically to maintain the required two-inch minimum air space clearance to the chimney at the extremities
of the offset.  It is recommended that enclosing material not follow the inclined portions of the chimney.

O

FFSET

 I

NSTALLATION

 S

EQUENCE

1. Determine the location and amount of offset required, then select the combinations of chimney sections

and elbows required from the offset chart.  Refer to Table 2.

2. Install the first elbow by placing the crimped end into the mating part of the fireplace or chimney section.

Push down until the outside or inlet air duct of the elbow overlaps and the snaps lock the elbow into the
fireplace or chimney section.

3. Nail the support straps to the framing member with a minimum of two 8-penny nails per strap.
4. Install the sections of pipe between elbows until the proper number of chimney sections have been installed.
5. Install the second elbow to return the run of the chimney to vertical.
6. Nail the support straps of the second elbow to a building frame member.
7. Continue installing the vertical portion of the chimney.
NOTE:  If the inclined portion of the chimney passes through a floor or ceiling, an SF30 firestop spacer should
be installed to provide the firestop and support required.  Be sure proper spacing in maintained between the
chimney and combustibles.  See Figure 19.

53D9051. Rev 1 03/03

NOTE: If you intend to have a total fireplace installation of more than 30 feet, you must use a chimney support
at or below 30 feet to support the weight of additional chimney pipe. If it is impossible to nail the chimney
support to the load bearing framing of the builing at the 30 foot level, the chimney support may be installed at
a lower level if the height of the chimney above the support does not exceed 30 feet. Effective height of the
chimney support is 16-3/4 inches. Chimney supports must be installed at 30 foot intervals.
To install the chimney support, place the crimped end of the flue into the last section of chimney pipe (see
figure 15). Push down until the outside or inlet air duct of the chimney support overlpas and snaps and snap
locks the chimney support into the chimney section.
Nail the support straps tightly to a building frame member or ceiling joist as shown by figure 15. You must use
at least two 8 penny nails per strap.

f i r e - p a r t s . c o m

Summary of Contents for Corner Fireplace 624WBCL

Page 1: ...NTIAL INSTALLATION 53D9051 Rev 1 03 03 36 INCH BUILT IN WOOD BURNING CORNER FIREPLACE WITH OPTIONAL OUTSIDE AIR AND GLASS DOORS WARNING THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET TO REDUCE RISK OF FIRE OR INJURY DO NOT INSTALL AN UNVENTED GAS LOG SET INTO FIREPLACE fire parts com ...

Page 2: ...ry built fireplace properly can result in a house fire or other occurences that could cause deaths injuries and property damages It is very important that the persons installing and or supervising the installation of this fireplace have appropriate skills in using the tools and techniques required and reading and comprehension skills sufficient to read and follow these instructions These instructi...

Page 3: ...d to sit directly on a combustible floor The fireplace can be installed with zero clearances to combustible building materials at the side back and top spacers Only parts manufactured by Monessen Hearth Systems and labeled for use with this fireplace should be used in the installation of the fireplace except for special roof flashings that may be fabricated locally The use of improper parts in the...

Page 4: ...of this manual pertaining to outside combustion air assembly The fireplace also is equipped with a flue damper which must be open when the fireplace is in use The flue damper control lever is located inside the fireplace The counterweighted damper is operated by simply pushing up to open or pulling down to close the damper When the fireplace is not in use the damper should be closed to prevent col...

Page 5: ...5 6 CLEARANCES 53D9051 Rev 1 03 03 fire parts com ...

Page 6: ...chimney cap for contemporary installations Includes storm collar SCL Round telescoping chimney cap SQL8 Square telescoping chimney cap 612 0 6 12 pitch flashing for contemporary installation One required with SC round chimney cap on 0 6 12 pitch roof 1212 6 12 12 12 pitch flashing for contemporary installation One required with SC round chimney cap on 6 12 12 12 pitch roof SF 14 1 2 inch firestop ...

Page 7: ...7 53D9051 Rev 1 03 03 FIREPLACE INSTALLATION fire parts com ...

Page 8: ...S Chimney support required when chimney height exceeds 30 feet LFCC 1 Round termination cap for contemporary installation includes storm collar LFCCL 1 Round Termination cap for chase installation includes inlet air telescope 612 0 6 12 pitch flashing for contemporary installation One required with SC round chimney cap on 0 6 12 pitch roof 1212 6 12 12 12 pitch flashing for contemporary installati...

Page 9: ...roof influences the opening size required at the roof level table 1 should be used as a guide for sizing the roof opening Proper selection of a chimney outlet location is also important Objects such as overhanging or nearby trees adjacent building or embarkments or unusual roof designs can all create air turbulance and interfere with chimney performance and cause the fireplace to spill smoke into ...

Page 10: ...ent the crack from developing the hearth extension materials must be firmly fastened in place Wall ties should be screwed to the face of the fireplace and imbedded in the mortar joints of brick stone or other non combustible materials The metal safety strip packed with the fireplace must be placed beneath the fireplace and extended under the hearth extension or into a mortar joint of the hearth ex...

Page 11: ...11 53D9051 Rev 1 03 03 CLEARANCES fire parts com ...

Page 12: ...12 53D9051 Rev 1 03 03 FIREPLACE INSTALLATION fire parts com ...

Page 13: ...13 53D9051 Rev 1 03 03 FIREPLACE INSTALLATION fire parts com ...

Page 14: ...Check the face of the fireplace with a carpenter s level to make sure the fireplace is plumb If it is not plumb plumb it by placing shims under the edges of the fireplace 4 Block in the fireplace to prevent any shifting of the firebox Secure the fireplace with nails or screws through the flanges located on each side of the fireplace Install chimney and other fireplace components as needed NOTE Som...

Page 15: ...tisfied with the chimney location relative to ceiling and roof joists and or any other obstructions The roof opening center line should be marked by driving a nail through the roof from underneath that will penetrate the roof and can be located from the rooftop If the chimney is to penetrate a pitched roof the hole in the roof must be rectangular instead of square and should be sized according to ...

Page 16: ...16 CHIMNEY INSTALLATION 53D9051 Rev 1 03 03 fire parts com ...

Page 17: ...low the inclined portions of the chimney OFFSET INSTALLATION SEQUENCE 1 Determine the location and amount of offset required then select the combinations of chimney sections and elbows required from the offset chart Refer to Table 2 2 Install the first elbow by placing the crimped end into the mating part of the fireplace or chimney section Push down until the outside or inlet air duct of the elbo...

Page 18: ...18 CHIMNEY OFFSET AND CAP INSTALLATION 53D9051 Rev 1 03 03 fire parts com ...

Page 19: ...19 53D9051 Rev 1 03 03 CHIMNEY OFFSET AND CAP INSTALLATION fire parts com ...

Page 20: ...re that the proper minimum clearances are maintained 5 Nail the flashing securely in place with eight nails 6 Seal the crack between the top of the flashing and the chimney with mastic Leave some excess mastic at this area to be used in step eight NOTE Use pliers and wear gloves when performing step seven to minimize the danger of cutting your hands on the edge of the storm collar 7 Place the stor...

Page 21: ...ough the duct See Figure 22 for methods of installing the outside air for combustion assemblies 2 The combustion air assembly should be located at an exterior location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet assembly should never be mounted in a garage or stor...

Page 22: ...ency and safety Do not use a combustible duct Always use UL listed Class 0 or 1 duct material 5 If the duct is the insulated type push the insulation back from one end of the duct approximately two inches See figure 25 6 Slip the exposed end of the duct over the flange tube of the fireplace 7 Place the duct clamp around the exposed end of the aluminum duct 8 Slip the band through the housing then ...

Page 23: ...gas piping should only be installed by a licensed gas appliance installer See Figure 11 for the gas line opening dimensions on the fireplace 6 The installer should advise the persons who will use the appliance to set the fireplace damper in the full open position when the appliance is in use The following instructions only apply to passing the gas line through the fireplace wall Follow the instruc...

Page 24: ...ld be fastened to the face of the fireplace with sheet metal screws and placed in the mortar joints of masonry trim Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face Seal the face of the fireplace to the surrounding wall with non combustible caulk or trim materials to prevent cold air leakage around the fireplace CAUTION No...

Page 25: ...4WBCL OR 624WBCR MODELS NON COMBUSTIBLE MAY BE INSTALLED TO THE TOP OF THE FIREPLACE OPENING THIS FACING MATERIAL MUST BE SECURED AND SEALED TO THE FACE OF THE FIREPLACE FAILURE TO PROPERLY SECURE AND SEAL NON COMBUSTIBLE FACING MATERIALS TO THE FIREPLACE CAN CAUSE A POSSIBLE FIRE HAZARD AND WILL VOID THE WARRANTY 53D9051 Rev 1 03 03 fire parts com ...

Page 26: ...The first three fires should be of moderate size to allow the fireplace to adjust and the bricks to cure before being subjected to larger fires First make sure your room is well ventilated your damper open and the flue is unobstructed Then make sure your wood is dry and seasoned Unseasoned wood burns poorly and coupled with poor ventilation or an obstructed chimney leads to smoking problems If you...

Page 27: ...r some individuals Use hemlock spruce juniper and other resinous woods with caution They contain moisture pockets which upon heating pop with considerable vigor Always use a fire screen And always bank a fire or at least push all unburned fuel to the rear of the grate before leaving a fire unattended Do not use this fireplace as an incinerator Because the termination of the chimney above the roof ...

Page 28: ...ldup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection maintenance and cleaning by removing three screws from the support legs and lifting upward When the fireplace is first in use inspect the chimney frequently and clean the chimney any time an accumulation is observed on the flue walls The frequency of...

Page 29: ... the fireplace to prevent excessive heat loss from the fireplace 5 Do trim the face of the fireplace only with noncombustible materials 6 Do attach the noncombustible face trim material firmly to the face of the fireplace 7 Do block in or fasten the fireplace to prevent the possibility of the fireplace shifting out of position 8 Do connect the air circulation blower to a properly grounded and fuse...

Page 30: ... or place flammable liquids gases or pressurized containers near the fireplace 17 Don t neglect to instruct all responsible persons in the proper and safe operation of the fireplace 18 Don t fail to instruct all persons especially children and elderly persons concerning the hazards of improper operation and unauthorized tampering with the fireplace 19 Don t use this fireplace to burn paper cardboa...

Page 31: ...2 Retainer 2 Z19901 3 Firebrick Side Assy Right 1 014012 4 Rod Outside Air 1 020293 5 Firebrick Back Assy 1 014048 6 Hearth Refractory 1 029986 7 Screen Panel 2 026400 8 Screen Pull 2 026391 9 Rod Screen Weld Assy 1 021673 10 Panel Upper Ptnd 1 021541 11 Rod Damper 1 037390 12 Damper Weldment 1 037393 KEY MPL MPL NO PART NAME QTY PART NO 1 Retainer Side Brick 1 020270 2 Retainer 2 Z19901 3 Firebri...

Page 32: ...53D9051 Rev 1 03 03 ATTENTION APPLIANCE INSTALLER PLEASE RETURN THIS INSTRUCTION MANUAL TO THE CONSUMER fire parts com ...

Reviews: