Figure 16 - External Regulator with Vent Pointing 

Down (Propane/LP Only)

Use only new black iron or steel pipe. 
Internally  tinned  copper  or  copper 
tubing can be used per National Fuel 
Code,  section  2.6.3,  providing  gas 
meets  hydrogen  sulfide  limits,  and 
where permitted by local codes. Gas 
piping system must be sized to provide 
minimum inlet pressure (listed on data 
plate) at the maximum flow rate (BTU/
hr). Undue pressure loss will occur if 
the pipe is too small.

CAUTION

For propane/LP units, never connect 
fireplace  directly  to  the  propane/LP 
supply.  This  burner  system  requires 
an  external  regulator  (not  supplied). 
Install the external regulator between 
the  burner  system  and  propane/LP  
supply. 

CAUTION

FIREPLACE INSTALLATION 

CHECK GAS TYPE

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install fireplace. See dealer 

where you purchased the fireplace for proper fireplace according to your gas type.

INSTALLING GAS PIPING TO FIREPLACE LOCATION

A qualified installer or service person 
must connect appliance to gas supply. 
Follow all local codes. 

W

ARNING

INSTALLATION ITEMS NEEDED

Before installing, make sure you have the items listed below.
•  External regulator (supplied by installer)  •  Tee joint
•  Piping (check local codes) 

•  Pipe wrench

•  Sealant (resistant to propane/LP gas) 
•  Test gauge connection* 
•  Sediment trap (optional but recomended)
•  approved flexible gas line with gas connector (if allowed 

by local codes — not provided)

* A CSA design-certified equipment shutoff valve with 

1

/

8

NPT tap is an acceptable alternative to test gauge connection. 

Purchase the CSA design-certified equipment shutoff valve 

from your dealer.

External 

Regulator 

100 gal. (min) 

Propane/LP 

Supply Tank 

Vent 

Pointing 

Down

When  using  copper  or  flex  connectors  use  only  fittings 

approved  for  gas  connections.  The  gas  control  inlet  is 

3

/

8

" NPT.

For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce incoming 

gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming 

gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown 

in

 Figure 16. 

Pointing the vent down protects it from freezing rain or sleet. 

External regulators may be necessary 
for  natural  gas.  One-  or  two-pound 
systems  will  damage  this  appliance 
and may cause fire hazzard.

W

ARNING

Summary of Contents for B-VENT BBV400

Page 1: ...ed installer service agency or the gas supplier WARNING Improper installation adjustment alteration servicesormaintenancecancauseinjuryor property damage Refer to this manual For assistance or additio...

Page 2: ...ition Wiring 22 Final Installation 23 Rock Wool Placement 23 Log Placement 23 Lava Rock and Ember Placement 23 Operating Instructions 24 What To Do If You Smell Gas 24 Lighting Pilot for the First Tim...

Page 3: ...replace must be properly installed by a quali ed service person CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the u with head aches dizziness and or nausea If you h...

Page 4: ...se with a thermostat 22 This appliance must be installed with draft hood in same atmospheric pressure zone as the combustion air inlet to the appliance 22 For Massachusetts Residents Only This product...

Page 5: ...lation code ANSI Z223 1 NFPA 54 in the USA CAN CGA B149 in Canada The appliance must be properly connected to a venting system The appliance is not approved for closet or recessed installations PRODUC...

Page 6: ...ot install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplace Firebox and Burner Sy...

Page 7: ...or raised on a platform of an appropriate height When the rebox is installed directly on carpeting tile or other combustible material other than wood ooring the rebox shall be installed on a metal or...

Page 8: ...ir Kit 23 16 1 2 or 5 8 Drywall Spacers 71 4 Electrical Gas Access 141 2 Framing Dimension D Framing Dimension B C TOP VIEW FRONT VIEW SIDE VIEW 40 163 4 401 4 Framing Dimension PRE INSTALLATION INFOR...

Page 9: ...nsion B C TOP VIEW FRONT VIEW SIDE VIEW 40 23 16 PRE INSTALLATION INFORMATION Figure 4 SBV400 and SBV500 Dimensions FIREPLACE DIMENSIONS SBV400 and SBV500 SBV400 SBV500 A 2413 16 3013 16 B 36 42 C 40...

Page 10: ...woodwork and windows Minimum clearances to combustibles must be maintained This replace may be installed along a wall across a corner or use an exterior chase Location should be out of high traf c are...

Page 11: ...uctions exactly can create a re hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood ooring If installed on carpet or vinyl ooring the appliance shal...

Page 12: ...r Use four 4 screws to attach replace to framing The side brackets are adjustable from 1 2 to 5 8 to accommodate different thickness of material SECURING FIREPLACE TO FLOOR OR FRAMING Figure 6 Securin...

Page 13: ...n on rooftops Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthoriz...

Page 14: ...been listed by a nationally recognized testing agency See B Vent Pipe Sizing chart for proper elbow offset runs Locate chimney center line dimension from a combustible back wall See Figures 3 and 4 p...

Page 15: ...you would the outside walls of your home This is especially important in cold climates Insulation should be considered a combustible material Maintain proper clearances to all combustible materials NO...

Page 16: ...ocation Make sure the location cannot be accidentally blocked Locate assembly above snow line to prevent snow from blocking assembly 3 Never mount combustion air inlet assembly in garage or storage ar...

Page 17: ...duct with a standard pocket knife See Figure 14 DO NOT remove the cover if the outside air will not be connected WARNING Figure 13 Attaching Outside Air Starting Collar to Left Side of Fireplace Figur...

Page 18: ...ITEMS NEEDED Before installing make sure you have the items listed below External regulator supplied by installer Tee joint Piping check local codes Pipe wrench Sealant resistant to propane LP gas Tes...

Page 19: ...ap Approved Flexible Gas Line UL CSA Design Certi ed Equipment Shutoff Valve with 1 8 NPT Tap Sediment Trap Drip Leg Natural Gas From Gas Meter 5 W C to 10 5 W C Pressure Propane LP From External Regu...

Page 20: ...e gas meter to the replace for leaks Use a solution of 50 50 water and soap or a gas sniffer 4 To adjust ame height turn HI LO knob to HI to get maximum pressure to burner Turn HI LO knob to LO to get...

Page 21: ...al code Figure 19 Wiring Diagram for Wall Switch ELECTRICAL INSTALLATION ELECTRICAL WIRING Electrical connections should only be performed by a quali ed licensed electrician Main power must be off whe...

Page 22: ...TIONAL DC REMOTE SYSTEMS These instructions replace the section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with the remote 1 Plug in remote connector wire to remote...

Page 23: ...ertical Grate Bar Right Vertical Grate Bar Center Vertical Grate Bar Log Mounting Pins ROCK WOOL PLACEMENT 1 Place rock wool on burner to provide glowing embers For best results pull the rock wool apa...

Page 24: ...air may result in a re or explosion D Do not use this appliance if any part of it has been under water Immediately call a quali ed service tech nician to inspect the appliance and to replace any part...

Page 25: ...it is possible to start the lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARNING 1...

Page 26: ...n burner without using the gas valve knob Make sure the button is in the ON position to light the main burner See Figure 24 LIGHTING THE BURNER Depress and turn the knob counterclockwise to the ON pos...

Page 27: ...hand B BEFORE OPERATING smell all around the appli ance area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Turn o...

Page 28: ...patterns to vary Figure 30 Burner Flame Appearance CLEANING AND MAINTENANCE BURNER PILOT AND CONTROL COMPARTMENT Keep the control compartment logs and burner areas surrounding the logs clean by vacuu...

Page 29: ...ogs with a brush attachment If logs must be removed for cleaning handle carefully by holding gently at each end Gloves are recommended to prevent skin irritation from ceramic bers If skin becomes irri...

Page 30: ...30 62D4036 1 2 3 4a 4b 4c 5 7 6 ILLUSTRATED PARTS LISTS FIREBOX COMPONENTS...

Page 31: ...16 62D2016 4c Right Refractory Floor 1 n a 62D1017 62D2017 Optional Field Installed Accessories 5 Firebrick Assembly 1 FBBV400W n a n a 6 Outside Air Kit 1 OAC4 OAC4 OAC4 7 Black Glass Door Assembly 1...

Page 32: ...32 62D4036 ILLUSTRATED PARTS LISTS 1 2 3 4 5 6 7 8 10 12 13 STANDING PILOT MILLIVOLT CONTROL 2T 2I 2C 9 11...

Page 33: ...48 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 62D3006 62D3005 62D3004 20H3143 62D3003 59D0094 8 Burner Assembly 1 54D0200 54D0200 54...

Page 34: ...34 62D4036 ILLUSTRATED PARTS LISTS 1 2 3 4 5 6 7 9 ELECTRONIC IGNITION 8 10 11 12...

Page 35: ...23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Injector 1 62D3006 62D3005 62D3004 20H3143 62D3003 59D0094 7 Burner Assembly 1 54D02...

Page 36: ...ntrol or wire B Pilot ame too small C Defective or malfunctioning ther mopile D Defective valve A Check switch and wire for proper connection Place jumper wires across terminals of switch If burner co...

Page 37: ...locked B Check electrical connections between module and pilot operator on gas control C Check for 24VAC across PV MVPV terminals If voltage is correct replace gas control If voltage is not correct re...

Page 38: ...Replace with proper size H Construct a single venting system for each appliance 3 Poor draft due to termination cap A Cap obstructed by a decorative enclosure B Cap is crushed damaged or miss ing A R...

Page 39: ...ve finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of ins...

Page 40: ...d in whole or in part for residential purposes c MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manu facturer of Product Approved side wall horizontally vented gas equipment...

Page 41: ...62D4036 39 NOTES...

Page 42: ...th the installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and...

Reviews: