wrong
correct
[G]
Ø
[H]
MWF
Microwave level measurement
M LLET
Füllstandtechnik
GmbH
MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Operating instruction
03/20
©
by MOLLET
MWF-BA-07
07
Protruding nozzle diameter
[G]
100 mm
Installation in consideration of filling
Protruding nozzle height
[H]
€
200 mm
Installation with protruding nozzle
Choose the mounting position in such a way that the probe will not be
touched by the filling stream.
By use of thermally insulated vessels the nozzle should be also insulated
in order to avoid condensation.
The protruding nozzle should be short and inside flush with the silo roof.
Installation in silos made of concrete
In case of installation in a concrete floor the process connection should
be flush with the bottom edge of the floor.
Fixing of the wire rope probe could be necessary, when:
- wire rope probe touches sometimes the silo wall, the cone, internal
installations or other metallic parts,
Smaller diameters and heights >200 mm could restrict the measuring
capability.
- wire rope probe gets closer than 500 mm to a concrete wall.
For fixing a threat M12 is provided at the bottom of the tensioning weight.
- rope starts swinging due to vibrations,
The rope must be loose in order to avoid a heavy tensile load and with it
the danger of a rope breakage and
Installation with fastened wire rope probe
In silos made of concrete a minimum distance
[A]
of 500 mm between
the concrete wall and the probe should be kept. A distance of at least
1000 mm is recommended.
either reliably grounded or reliably isolated.
17. Installation advices
200
200
002-1006
002-1008
002-1009
002-1007
Reliably grounded fixing
Reliably isolated fixing
Mounting
brackets
provided
on site
M12
Plastic rope