![Mold-Masters TempMaster XL-2 Series User Manual Download Page 29](http://html.mh-extra.com/html/mold-masters/tempmaster-xl-2-series/tempmaster-xl-2-series_user-manual_1823674029.webp)
XL-2 Manual
Troubleshooting
Revision 1.1
Mold-Masters
®
Page 29
Fans
Every Cabinet has auxiliary fans to ensure adequate cooling. If
any fan has stopped working then first inspect the unit to see if
there are any blockages or objects fouling the impellors. Once you
are certain that the fan is free to rotate then proceed to check its
supply fuse that is located on the main termination rail.
Class 1
1/4
“ Glass Fuse Antisurge
Rating 2A
Controller Cards
There is a protection fuse for power input on the controller card.
Fuse Rating
500mA
Output Overload Protection Fuse
On the back of 4, 12, 18 zones cabinet, there are fuses for
protecting the heating load output.
Class Fast
blow
Rating 16A