background image

INSTALLATION DATA SHEET

Remove 3 x M3 screws and the base plate from the body. 

Pierce the cable grommet.

Insert supply/signal cable (maximum 7mm diameter) through the grommet,

pull back slightly (10mm), for the grommet to form a weatherproof seal.

Connect cable to terminal block.

Terminal Block

No Mode

1 Power 

Input 

 +24v 

dc 

   

2 Return 

 

    0v

Signal - Sounder   

+24v (high) 

0v (low) 

Signal - Green LED  

+24v (high) 

0v (low) 

Signal - Amber LED 

+24v (high) 

0v (low) 

Signal - Red LED 

+24v (high) 

0v (low) 

Secure the supply/signal cable to the base with the cable grip. 

Replace base plate, ensuring the gasket is in place and aligned to the ‘lead exit position’. 

Secure with 3 x M3 screws.

General Installation Notes

•  The DC supply must be fully rectified and smoothed.  If the supply is used to power

  other equipment, particulary inductive loads, additional suppression will be

  required. Typical suppression units would be RS 219-2921 or RS 240-696.

•  Installation must be carried out, in accordance with latest codes and regulations, by a    

  qualified electrician.  

•  Ensure power source is disconnected prior to installation or maintenance to avoid

  electric shock.

•  Do not handle internal electronic components whilst wiring up.

•  Environmental exposure conditions during installation should be dry not  

 

 

  moist or wet conditions.

•  The lens material of the beacon is VO rated Polycarbonate UV stable plastic. Do not    

  clean with petroleum based cleaners.

•  The beacon is weatherproof to IP65 only when mounted with the lens uppermost

  ie above the black base.

•  Use 3 in total, 4mm diameter fixings (not supplied) to secure Beacon to its mounting. 

•  Avoid mounting the beacon where it will be subject to excessive vibration.

  

Gasket

Terminal Block

(No 1 to 6)

Position of Cable Grip

Cable Grommet

Lead Exit Position

Lens

Black Base

SIDE VIEW

OF BEACON

EXTERNAL 

UNDERSIDE 

VIEW OF BASE

INTERNAL 

VIEW OF BASE

3 Holes x 4.5 DIA

on 88 pcd for 

mounting

Piezo 

Buzzers

11

o

 Side knockout position

4 x 6.5 mm wide

11 mm

Lead exit 

position - 

5mm max 

cable size

27.6

ø98mm

162mm

Reviews: