Hardware
Device Description Embedded HMI-PLC XV-23x-57
Commissioning
4.6.2 MPI
(P
ROFIBUS
DP)
The MPI (Profibus DP) interface is a non-isolated RS485 interface.
Connector assignment
Pin no.
Signal
Description
1
TERM B
Internal termination Data B
2
LINE B
Receive/Transmit Data B
3
LINE B
Receive/Transmit Data B
4
REP CTL
Repeater Control
5
0 V
Reference potential for the terminating
resistors and the potential equalisation
line 1)
6
5 V
Power supply for the bus terminating
resistors
7
LINE A
Receive/Transmit Data A
Connector
9pole
8
LINE A
Receive/Transmit Data A
DSub female
9
TERM A
Internal termination Data A
5
9
4
8
3
7
2
6
1
1) The 0V terminal must always be wired.
The MPI (Profibus DP) is not isolated.
The max. baud rate is 1.5 Mbit/s.
The terminating resistors should be provided externally in the plug connector, in
accordance with the Profibus standard. Alternatively the termination in the plug
connector can be implemented using jumpers between LINE A and TERM A, as
well as LINE B and TERM B.
The 5V must not be used as a power supply for systems of other suppliers. It is
neither overload nor short-circuit proof.
Î
Further information: Installation instructions, General wiring instructions [1]
12/05 AWB2776-1581GB
© by Moeller GmbH