Current Limiting Data according to UL 489
Instructions for Field Wiring
Terminal Kit System for NZM 10 (C)NA and NZM 10 N/B-NA
Circuit Breaker
Threshold Current
Circuit Breaker
Wire Size
Max. A-Rating
TighteningTorque
Intermediate Current
Frequency
High Interrupting Capacity
Type
Bolt-on
Terminal Cover (3) 2Z1213-651.28 L1; L2; L3
600 A
50 Nm
K2x240W-NZM 10
K2x240IP-NZM 10
Terminal Cover (3) 2Z123-651.28
Insulating Plate (1) 4Z 123-651.1003
Auxiliary Terminal
2xAWG2-2x500MCM
AWG 18-14
50 Nm
1,2 Nm
Cu + Al
Cu only
Cu only
600 A
500 A
350 A
K2x120-NZM 10
Auxiliary Terminal
2xAWG3/0-2x250MCM
AWG 18-14
K300-NZM 10
Auxiliary Terminal
250MCM-500MCM
AWG 18-14
NZM10H
600
Max. Frame
Size A
RMS
SYM
kA
Peak
kA
I
2
dt
10
3
A
2
s
MAXIMUM
RMS
SYM
kA
Peak
kA
I
2
dt
10
3
A
2
s
MAXIMUM
RMS
SYM
kA
60 Hz
Voltage (V)
Peak
kA
I
2
dt
10
3
A
2
s
MAXIMUM
39
39
39
125
65
42
200
100
50
34.0
42.0
40.0
2800
5500
5500
50.0
52.0
45.0
3500
6600
7200
55.0
61.0
48.0
4000
8000
8000
240
480
600
8 Nm
1,2 Nm
8 Nm
1,2 Nm