01/02 AWB8230-1413GB
Motor data
149
Type of motor stop
Specify here, how the motor is to decelerate when the OFF button
is pressed:
Fan control
With PNU b092, you can specify when the fan will operate.
If you enter the value 01 here, the fan runs for one minute after
the frequency inverter power supply is switched on, allowing you
to make sure that the fan is working correctly. The fan also
continues to run for five minutes after the connected motor has
stopped to dissipate residual heat.
Debug mode
Under PNU C091, set debug mode.
Motor data
To ensure that the DF6 frequency inverter controls the motor
correctly and generates the greatest possible torque, you can enter
the following motor data:
• Motor rating
• Number of motor poles
• Motor stabilization constant
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b091
Type of motor
stop
–
–
00
Deceleration using the deceleration ramp
00
01
Free run stop (coasting)
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
b092
Fan control
–
–
00
Fan is always switched on
00
01
Fan is switched on only while the connected motor is
running.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C091
Debug mode
–
j
00
Debug mode is displayed.
00
01
Debug mode is
not
displayed.
PNU
Name
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
H003
H203
Motor rating
–
–
0.2 to 160 kW
Enter the motor rating.
• 0.2 to 75 kW DF6-340-11K to DF6-340-55K
• 0.2 to 160 kW: from DF6-340-75K
Depen-
ding on
DF6
H004
H204
Number of
motor poles
–
–
2/4/6/8
Enter the number of motor poles
4
H006
H206
Motor
stabilization
constant
j
j
0 to 255
0 function is not active
100
efesotomasyon.com - Klockner Moeller - inverter