Table 6:
Circuit-breaker communication status
The following applies to all status bits:
• 1 = Condition fulfilled
• 0 = Condition not fulfilled
Byte 0
Bit 0
1 if circuit-breaker detected with new serial number and the Stop mode is acti-
vated.
Otherwise 0
Bit 1
1 if parameters of DMI and LS are not identical
Otherwise 0
Bit 2
1 if parameters set for motor protection function, but no NZM-ME type
is connected
otherwise 0
Bit 3 and bit 4
Reserved
Bit 5
1 after initialisation of the interface, until an LS ID (01
hex
) or PC ID is detected
while establishing the connection.
Otherwise 0
Bit 6
1 after initialisation of the interface, until the ID block (1E
hex
)
is correctly received when making the connection.
Otherwise 0
Bit 7
1 after initialisation of the interface, until the first transfer command (3F
hex
) is
received while making the connection.
Byte 1:
Bit 0 to bit 3
Number of the last data record entered in the diagnostics data (0 to 9)
Bit 4
“0” DMI has received latest operating data from NZM
“1” DMI has received latest diagnostics data from NZM
Bit 5 to Bit 7
Reserved