Environmental Considerations
Units with supply water temperatures below +5°C (41°F)
● Glycol is recommended when a supply water temperature of +5°C (41°F) or below is required or when static water
can be exposed to freezing temperatures.
Unit pipework subject to ambient temperatures lower than 0°C (32°F)
•
Glycol of an appropriate concentration
(1)
must be used within the system to ensure adequate freeze protection.
Please ensure that the concentration is capable of protection to at least 3°C (5.4°F) lower than ambient.
•
Water / glycol solution should be constantly circulated through all waterside pipework and coils to avoid static
water from freezing.
•
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C
(5.4°F) of the solution freeze point
(1)
(i.e. if the solution freezes at 0°C (32°F), the pump must be operating at 3°C
(37.4°F) ambient).
•
Additional trace heating is provided for interconnecting pipework.
(1)
Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
•
Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
•
Train personnel in sound environmental practices.
•
Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
•
Manufacture products in a responsible manner with minimum impact on the environment.
•
Reduce our use of chemicals and minimise their release to the environment.
•
Measure, control and verify environmental performance through internal and external audits.
•
Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following:
Electromagnetic Compatibility Directive (EMC)
2014/30/EU
Machinery Directive (MD)
89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED)
2014/68/EU
Ecodesign
2009/125/EC
UL 1995
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
This system has been designed to be connected to a TN type distribution system. For alternate distribution type
systems, contact Airedale.