INSTALLATION - HIGH ALTITUDE ACCESSORY KIT
If the heating value of the gas being supplied is different than
the values shown in Tables 16.1 and 16.2, use the following
equation to determine the appropriate manifold pressure for the
altitude and gas heating value being supplied.
Equation 17.1 - Manifold Pressure for Derated Gas
WHERE:
MPACT =
Manifold Pressure (in. W.C.) at Altitude –
Manifold pressure setting for the heater
being installed
BTUTBL =
BTU/ft
3
Content of Gas –
Obtained from Tables 16.1 or 16.2
(whichever is applicable)
BTUACT =
BTU/ft
3
Content of Gas –
Obtained from the local utility company
MPSL = Manifold Pressure (in. W.C.), at Sea Level –
Use 3.5" W.C. for natural gas and 10.0" W.C. for
propane gas
NOTE: Only the primary manifold pressure should be adjusted
on units equipped with 2-stage or modulating gas controls. No
adjustments to the low fire manifold pressure are necessary on
these units.
Table 17.1 - High Altitude Kits for IPT
Conversion IPT - LP
50
60
75
100
125
150
175
200
0-2000 FT
77839
77840
77841
77842
77843
77844
77845
77846
2001-3500 FT
77847
3501-4000 FT
4001-4500 FT
4501-5000 FT
5001-5500 FT
77850
77851
77852
77853
5501-6000 FT
6001-6500 FT
77854
77855
6501-7500 FT
Conversion IPT - Natural Gas
50
60
75
100
125
150
175
200
0-2000 FT
77823
77824
77825
77826
77827
77828
77829
77830
2001-3500 FT
77831
77832
3501-4000 FT
77834
4001-4500 FT
4501-5000 FT
5001-5500 FT
77836
5501-6000 FT
6001-6500 FT
77838
6501-7500 FT
77837