40
www.modine.com
Model SRE
24
44
64
84
25
45
65
85
26
46
66
Fan motors
n. x ø mm
2x500
4x500
6x500
8x500
2x560
4x560
6x560
8x560
2x630
4x630
6x630
A
3,5
7
10,5
14
4,4
8,8
13,2
17,6
8
16
24
W
1720
3440
5160
6880
2500
5000
7500
10000
4200
8400
12600
RPM
1400
1400
1400
1400
1300
1300
1300
1300
1380
1380
1380
Connection scheme and fan motor absorption
( * ) Inner protection thermal contacts
The thermal contacts are temperature sensing, switching ele-
ments built directly into the windings of the motors. They interrupt
an electrical contact when maximum admissable sustained tem-
perature has been reached.
The thermal contacts must be connected to the control circuit of
the mains contactor to prevent automatic reconnection of the
motor in the event of a fault.
Caution
Application of adequate thermal control systems on feeder lines
is mandatory.
Performance of all electric heaters must be periodically control-
led to avoid damage due to ice build-up.
The manufacturer is not liable in any way for defects caused by
non detected malfunctions.
Orange
Brown
Red
Light
blue
Grey
Black
Green/yellow
Orange
Brown
Red
Light
blue
Grey
Black
Green/yellow
Orange
Brown
Red
Light
blue
Grey
Black
Green/yellow
SRE Ø 500
~3 400V
∆
/Y 50 Hz
SRE Ø 560
~3 230-400V 50 Hz
SRE Ø 630
~3 230-400V 50 Hz