ATH15-520.2

Rigging Instructions

Four 1.5" eye bolts at the top of the unit in each corner are 

supplied to facilitate lifting the unit. For either crane or helicopter 

lift of the equipment to the rooftop, connect sturdy steel cables 

or chains with eye loops as illustrated in Figure 5.1. For stability 

in lifting and lowering and to prevent damage to the eye bolt 

lifting points, include a spreader bar as illustrated in Figure 5.1.

RIGGING INSTRUCTIONS / UNIT INSTALLATION

Figure 5.1 - Typical Rigging for ERM Unit

Unit Installation

Follow site preparation instructions for the roof curb before 

installation. Check the Serial Plate of unit with plans to be sure 

unit is properly located (see page 15). Although units may 

look outwardly similar, their function, capacities, options, and 

accessories will often vary. Check dimensions. 

 

The MPR unit must already be installed on its curb following the 

instructions in the Installation and Service Manual that shipped 

with the MPR unit.  This must be completed prior to installation 

of the ERM unit. 
If unit is to be installed on a factory-supplied curb:
1.  The roof curb and the MPR unit must be installed prior to 

the installation of this ERM unit.

2.  Install roof curb using instructions on page 4.
3.  Thoroughly clean and dry the top of the curb surface.
4.  Place the factory supplied gasketing on the top perimeter 

of the roof curb and place a bead of weather resistant 

caulk on the flange of the factory installed ERM to MPR 

unit transition duct.

5.  Orient the hoisted unit so the transition ductwork is lined up 

with the inlet of the MPR unit and set it down evenly  

on curb.

6.  Secure the transition duct to the MPR unit using the 28 

sheet metal screws provided through the pre-drilled holes 

in the transition duct flange.

7.  Make final unit connections to the electric power supply 

and remote control circuits.

EXHAUST AIR

GRAVITY DAMPER

& OUTLET HOOD

RAINHOOD

ACCESSORY

(FIELD INSTALL)

(4) 1.50" LIFTING EYE BOLTS

      (EACH CORNER OF UNIT)

SPREADER BAR

AND LIFTING CHAINS

BY INSTALLER

ADJUST CHAIN

LENGTH SO UNIT IS

LEVEL WHEN LIFTED

THE MAIN UNIT MUST BE

INSTALLED BEFORE THE

ENERGY RECOVERY UNIT

CAULK FLANGE OF DUCT 

TRANSITION PRIOR TO 

CONNECTION TO THE MAIN UNIT

INLET AIR 

END VIEW

75°

APPROX.

IF SEPARATE FACTORY SUPPLIED

ROOF CURBS ARE USED, REFER

TO THE INSTALLATION INSTRUCTIONS

SHIPPED WITH THE CURBS FOR

PROPER PLACEMENT.

Summary of Contents for Atherion ERM

Page 1: ...ving parts and may cause equipment damage 3 When the dead front disconnect switch es for main unit model MPR and or powered convenience outlet option is in the OFF position supply power remains energi...

Page 2: ...ble Material and Service Clearances 3 Roof Curb Installation Duct Utility Connections 4 Rigging Instructions Unit Installation 5 Electrical Connections 6 Start Up Procedure 7 8 Unit Features Options L...

Page 3: ...S Units are sometimes built with special features as requested by the customer This manual only covers standard features and does not include any changes made for special feature requests by the custo...

Page 4: ...ightness If roof is pitched it will be necessary to construct a sub base on which to install the curb All corners must be square 4 When installing roof curbs for both the MPR unit and the ERM unit spa...

Page 5: ...pplied curb 1 The roof curb and the MPR unit must be installed prior to the installation of this ERM unit 2 Install roof curb using instructions on page 4 3 Thoroughly clean and dry the top of the cur...

Page 6: ...on the serial plate is not 5 greater than rated voltage ELECTRICAL CONNECTIONS 1 Installation of wiring must conform with local building codes or in the absence of local codes with the National Electr...

Page 7: ...he dead front disconnect switch es The switch body is located inside of another junction box to protect against contact with the live wiring The junction box must not be disassembled unless the main p...

Page 8: ...ed in the owners manual on the bearing sheave and blower wheel to avoid damage to the unit Optional Dirty Filter and or Wheel Pressure Switch es The optional dirty filter pressure switch and or wheel...

Page 9: ...op switch not shown 12 O Electric preheat assembly with power control compartment 13 S Outside air filters 14 O Outside air filters pressure drop switch 15 S Blower door switch not shown 16 S Outside...

Page 10: ...WHEEL ECONOMIZER BY PASS DAMPERS WITH ACCESS DOOR AND TOP MOUNTED ACTUATOR 12 10 25 87 69 18 72 36 93 54 36 77 139 22 102 45 65 92 31 98 4 24 63 93 71 60 4 10 27 47 86 19 60 14 64 28 80 56 84 64 90 2...

Page 11: ...S UNIT BASE BASE ASSEMBLY AS VIEWED FROM BOTTOM INSIDE BASE ASSEMBLY DETAIL VIEW BASE ASSEMBLY AS VIEWED FROM SIDE LANDING AREA FOR ROOF CURB 90 28 2 53 1 37 4 09 2 53 2 53 59 22 85 22 90 28 Figure 11...

Page 12: ...Figure 12 1 Roof Curb Dimensions 1 12 14 0 OR 24 0 SEE SCHEDULE 83 75 80 25 INSIDE 54 25 INSIDE 1 75 1 75 57 75 1 75 1 75 Table 12 1 Roof Curb Weight approx lbs Section Description Weight Roof Curb 1...

Page 13: ...cedures must be performed by a qualified service agency Outdoor Air Sensor 1 Remove sensor from mounting bracket 2 Remove any dust or dirt that may be clogging the screen material covering the air sam...

Page 14: ...r voltage too low 4 Check and correct 5 Supply power line sizing too small 5 Check and correct 6 Controls are in Unoccupied mode 6 Wait for Occupied mode or override 7 Controller alarm 7 Check and cor...

Page 15: ...MAIN UNIT DATA PLATE DO NOT POWER THIS SECTION SEPARATE FROM THE MAIN UNIT 45 Table 15 2 Unit Model Nomenclature Digits Indicates Description Value 1 2 3 Unit Type Energy Recovery Module for MPR C Cab...

Page 16: ...en Avenue Racine WI 53403 Phone 1 800 828 4328 HEAT www modinehvac com Modine Manufacturing Company 2021 As Modine Manufacturing Company has a continuous product improvement program it reserves the ri...

Reviews: