NATURAL GAS CONVERSION INSTRUCTION
15
16
After installing the conversion kit, verify the location of the Thermocouple and
Igniter Pin using the illustration below.
Thermocouple
Igniter Pin
5mm /
0.196”
Note to installation technicians. Verify the manifold pressure by using a
3/8” flared T-junction(not included) at the location marked by the arrow below.
Then usinga digital manometer verify that the pressure before the orifice is
7” W.C. Also verify that the orifice spud has the
3.1mm
marked. This will allow
you to verify that the input rating of the appliance is correct.
Installing at Altitude
!
For installations at elevations above 2000 ft. (610 m) contact your local dealer or gas
supplier before installing as input rating should be reduced approximately 4% for each
1000 ft. above sea level. Refer to the National Fuel Gas Code.
Contact the Ocean Rock USA for more information at 800-678-7294
IMPORTANT
!
The proper manifold pressure for this converted appliance is 7” W.C..
The maximum inlet gas pressure for this unit is 10.5 in wc (2.61 kPa)
The minimum inlet gas pressure for this unit is 3.5 in wc (0.87 kPa)
11 / 40
To Manometer
Burner Tube
Bellows
NG Orifice Spud