background image

Instructions 

APD 2065

Calibration

Front-mounted Zero and Span potentiometers for each channel 
can be used to compensate for load and lead variations.
1.  Apply power to the module and allow a minimum 30 minute 

warm up time.

2. Using an accurate voltmeter on terminals 22 and 24 adjust

the excitation voltage fine adjustment potentiometer to the
strain gauge manufacturer's recommended value.

3. Using an accurate calibration source, provide an input to

the module equal to the minimum input required for the
application.

4. Using an accurate measurement device for the output,

adjust the Zero potentiometer for the exact minimum output 
desired. The Zero control should only be adjusted when the 
input signal is at its minimum. This will produce the cor-
responding minimum output signal. For example: 4 mA for
a 4-20 mA output or –10 V for a ±10 V output.

5.  Set the input at maximum, and then adjust the Span pot for 

the exact maximum output desired. The Span control should 
only be adjusted when the input signal is at its maximum.
This will produce the corresponding maximum output
signal. Example: for 4-20 mA output, the Span control will
provide adjustment for the 20 mA or high end of the signal.

6.  Repeat adjustments for both channels for maximum accuracy.

Output Test Function

When the Test button is depressed it will drive the output with a 
known good signal that can be used as a diagnostic aid during 
initial start-up or troubleshooting. When released, the output 
will return to normal.
Each Test Cal. potentiometer is factory set to approximately 
50% output. Each can be adjusted to set the test output from 
0 to 100% of the output span. Press and hold the Test button 
and adjust the corresponding Test Cal. potentiometer for the 
desired output level.
They may optionally be externally wired for remote test opera-
tion or a manual override. See wiring diagram at right.

Operation

The APD 2065 accepts one AC voltage or current input and 
one strain gauge input and provides two optically isolated DC 
voltage or current outputs that are linearly related to the inputs. 
Green LoopTracker

®

 input LEDs provide a visual indication that 

each signal is being sensed by the input circuitry of the module. 
They also indicates the input signal strength by changing in 
intensity as the process changes from minimum to maximum.
If an LED fails to illuminate, or fails to change in intensity as 
the process changes, check the module power or signal input 
wiring.
Two red LoopTracker output LEDs provide a visual indication 
that the output signals are functioning. They become brighter 
as the input and each corresponding output change from 
minimum to maximum. 
For a current output the red LED will only light if the output loop 
current path is complete. For either current or voltage outputs, 
failure to illuminate or a failure to change in intensity as the 
process changes may indicate a problem with the module 
power or signal output wiring. Note that it may be difficult to 
see the LEDs under bright lighting conditions.

28 Power AC or DC –
26 Earth Ground
25 Power AC or DC +

26

25

27

28

APD 2065

Channel 1 

Channel 2 

AC to DC  

Strain Gauge to DC 

Isolated Transmitter 

Isolated Transmitter

Test Cal.

Span

Zero

Test

Output

Loop
Tracker

Test Cal.

Span

Zero

Test

Output

Input

Loop
Tracker

Loop
Tracker

Input

Loop
Tracker

Channel 1

Channel 2

®

Excitation

To maintain full isolation avoid combining power supplies in 

common with inputs, outputs, or unit power.

14

13

15 16

10

9

11 12

External 

Contacts  

for Test 

Function

– 

+ 20V

– 

+ 20V

mA 

Device 2

R

i

mA 

Device 1

R

i

6

5

7

8

2

1

3

4

Ch. 1

Ch. 2

Voltage 

Output

– 

+

Voltage 

Device 1

– 

+

Voltage 

Device 2

2

1

3

4

Ch. 1

Ch. 2

6

5

7

8

– 

+

mA 

Device 2

R

i

Loop 

Power 

Source 2

– 

+

+

 –

mA 

Device 1

R

i

Loop 

Power 

Source 1

Ch. 1

Ch. 2

2

1

3

4

6

5

7

8

+

 –

Precautions

WARNING! All wiring must be performed by a qualified electrician 
or instrumentation engineer. See diagram for terminal designa-
tions and wiring examples. Consult factory for assistance. 
WARNING! Avoid shock hazards! Turn signal input, output, and 
power off before connecting or disconnecting wiring, or remov-
ing or installing module.

Précautions

ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de 
câblage. Consulter l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal 
d'entrée, le signal de sortie et l'alimentation électrique avant 
de connecter ou de déconnecter le câblage, ou de retirer ou 
d'installer le module. 

Electrical Connections

Polarity must be observed for signal wiring connections. If the 
input and/or output do not function, check wiring and polarity.
Each product is factory configured to your exact input and 
output ranges as indicated on the serial number label. 

Outputs

For milliamp ranges determine if your devices provide power 
to the current loop or if the loop must be powered by the APD 
module. Typical voltage may be 9-24 VDC at your device's 
terminals if it provides power to the loop.

AC Input 

1

18

17

19

20

+15 VDC, 25 mA 

sensor power 

available at 
terminal 18

Ch. 1 

AC Voltage or mA 

Input

22

21

23 24

Excitation

 +

Strain 

gauge

Signal 

Excitation

 

See manufacturer's 

specifications for 

wiring designations.

Shield wires should 

be grounded at one 

end only.

Device for Output Channel 1

Terminal Terminal

Measuring/recording device accepts a 

voltage input.

3 (

–)

(

+)

Measuring/recording device has 

an unpowered or passive mA input. 

 

APD module provides the loop power.

3 (

–)

(+20 V)

Measuring/recording device has a mA 

input and powers the current loop. 

2 (

–)

(

+)

Device for Output Channel 2

Terminal Terminal

Measuring/recording device accepts a 

voltage input.

7 (

–)

(

+)

Measuring/recording device has 

an unpowered or passive mA input. 

 

APD module provides the loop power.

7 (

–)

(+20 V)

Measuring/recording device has a mA 

input and powers the current loop. 

6 (

–)

(

+)

AC Input Channel 1

Terminal

Terminal

Device with an AC voltage or  

AC milliamp output.

17

19

Transmitter power supply.

18 

(

+15 VDC)

19

Input 1, AC

Any polarity may be used for an AC input. A transmitter DC 
power supply is available at terminals 22 and 23, but is not 
commonly used with an AC input.

Bridge Input Channel 2

– Te Terminal

Strain gauge signal input

21 

(

+)

23  (

–)

Excitation voltage

22 (

–)

24 

(

+)

Input 2, Bridge, Strain Gauge, Load Cell

Refer to wiring diagram at right and strain gauge manufac-
turer’s data sheet for wiring and color-coding. Polarity must 
be observed when connecting input. Sensor shield wire (if 
equipped) should be grounded at one end only.
The excitation voltage is factory set and should match the sensor 
manufacturer's recommendations. A front potentiometer allows 
approximately ±10% fine adjustment of the excitation voltage.
CAUTION: Never short the excitation leads together. This will 
cause internal damage to the module.

Mounting to a DIN Rail

Install module vertically on a 35 mm DIN rail in a protective 
enclosure away from heat sources. Do not block air flow. Allow 
1" (25 mm) above and below housing vents for air circulation.
1.  Tilt front of module down and

position the lower spring clips
against the bottom edge of DIN rail.

2.  Push front of module upward until

upper mount snaps into place.

Removal

Avoid shock hazards! Turn signal 
input, output, and power off.
1.  Push up on bottom back of module.
2. Tilt front of module downward

to release upper mount from top
edge of DIN rail. 

3.  The module can now be removed 

from the DIN rail.

Spring Clips

Upper Mount

Module Power Terminals

Check label for module operating voltage to make sure it 
matches available power. The power supplies are fuse protect-
ed and the unit may be returned to API for fuse replacement.
When using DC power, either polarity is acceptable, but for 
consistency, wire positive (+) to terminal 25 and negative (–) 
to terminal 28.

Cu 60/75°C 

conductors 

14 AWG 

max.

To avoid 

damage to 

the module, 

do not 

make any 

connections 

to unused 

terminals

Wire terminal torque 

0.5 to 0.6 Nm or 4.4 to 5.3 in-lbs

API maintains a constant effort to upgrade and improve its products. 

Specifications are subject to change without notice. See api-usa.com for 

latest product information. Consult factory for your specific requirements.

WARNING:

 This product can expose you to chemicals includ-

ing nickel, which are known to the State of California to cause 

cancer or birth defects or other reproductive harm. For more 

information go to www.P65Warnings.ca.gov

Current 

Sourcing 

Output

Current 

Sinking 

Output

Module 

powers mA 

output loop

Module mA 

output is  

unpowered

www.mod-tronic.com | [email protected] | 1-800-794-5883

Summary of Contents for DupPak APD 2000

Page 1: ...and provides two optically isolated DC voltage or current outputs that are linearly related to the inputs The input ranges and the output ranges for each channel are independent and can be specified a...

Page 2: ...stance ATTENTION viter les risques de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d connecter le c blage ou de retirer ou d installer le mod...

Page 3: ...nearly related to the inputs The input ranges and the output ranges for each channel are independent and can be specified as required This provides an economical two channel solution in one device Typ...

Page 4: ...1 25 mm above and below housing vents for air circulation 1 Tilt front of module down and position the lower spring clips against the bottom edge of DIN rail 2 Push front of module upward until upper...

Page 5: ...nt and can be specified as required This provides an economical two channel solution in one device Typical applications include signal conversion isolation and redundancy i e to prevent failure of the...

Page 6: ...meter must be connected to all three signal input terminals as shown 0 100 of the potentiometer range must be used A stable 1 VDC source to excite the potentiometer Voltage drop is measured across the...

Page 7: ...ulated 25 mADC may be connected for sinking or sourcing mA input Input com mode rejection 120 dB minimum Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor...

Page 8: ...Bridge Input Channel 2 Terminal Terminal Strain gauge signal input 21 23 Excitation voltage 22 24 Input 2 Bridge Strain Gauge Load Cell Refer to wiring diagram at right and strain gauge manufac turer...

Page 9: ...e 50 typical Input com mode rejection 120 dB minimum Current input voltage burden 1 25 VDC max at 20 mA Input loop power supply 15 VDC 10 regulated 25 mADC may be connected for sinking or sourcing mA...

Page 10: ...e current loop or if the loop must be powered by the APD module Typical voltage may be 9 24 VDC at your device s terminals if it provides power to the loop AC Input Channel 2 Terminal Terminal Device...

Page 11: ...DC voltage or current outputs that are linearly related to the inputs The input ranges and the output ranges for each channel are independent and can be specified as required This provides an economic...

Page 12: ...ge of DIN rail 2 Push front of module upward until upper mount snaps into place Removal Avoid shock hazards Turn signal input output and power off 1 Push up on bottom back of module 2 Tilt front of mo...

Page 13: ...des two optically isolated DC voltage or current outputs that are linearly related to the inputs The input ranges and the output ranges for each channel are independent and can be specified as require...

Page 14: ...exemples de c blage Consulter l usine pour assistance ATTENTION viter les risques de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d connecte...

Page 15: ...nput ranges and the output ranges for each channel are independent and can be specified as required This provides an economical two channel solution in one device Typical applications include signal c...

Page 16: ...esigna tions and wiring examples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing...

Page 17: ...rature range in F or C RTD resistance Typically 10 to 2000 2 or 3 wire Excitation current Typically 10 10 mA 100 2 mA 1000 0 5 mA 2000 0 2 mA Leadwire comp 0 05 of span per 1 change in leadwire resist...

Page 18: ...ARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par...

Page 19: ...A 2000 0 2 mA Leadwire comp 0 05 of span per 1 change in leadwire resistance 3 wire sensor Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor range 0 1 mV t...

Page 20: ...mples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTIO...

Page 21: ...392 etc Temperature range in F or C RTD resistance Typically 10 to 2000 2 or 3 wire Excitation current Typically 10 10 mA 100 2 mA 1000 0 5 mA 2000 0 2 mA Leadwire comp 0 05 of span per 1 change in l...

Page 22: ...ns and wiring examples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr...

Page 23: ...000 0 2 mA Leadwire comp 0 05 of span per 1 change in leadwire resistance 3 wire sensor Channel 2 Frequency Input Range Factory configured please specify input range Frequency 0 25 Hz to 0 20 kHz Any...

Page 24: ...rminals if it provides power to the loop APD 2017 Channel 1 Channel 2 RTD to DC Frequency to DC Isolated Transmitter Isolated Transmitter Test Cal Span Zero Test Output Loop Tracker Test Cal Span Zero...

Page 25: ...output ranges for each channel are independent and can be specified as required This provides an economical two channel solution in one device Typical applications include signal conversion isolation...

Page 26: ...ues de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d connecter le c blage ou de retirer ou d installer le module Electrical Connections Pola...

Page 27: ...ximum range 0 1 M Input impedance 100 to 1 M minimum Input com mode rejection 100 dB minimum Channel 2 RTD Input Range Factory configured please provide complete sensor specifica tions and temperature...

Page 28: ...WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu p...

Page 29: ...Consult factory for other ranges and configurations Minimum range 0 100 Maximum range 0 1 M Input impedance 100 to 1 M minimum Input com mode rejection 100 dB minimum Channel 2 Potentiometer Input Ra...

Page 30: ...mov ing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par un lec tricien ou ing nieur en instrumentation qualifi Voir le dia gramme pour d signations des bornes et des ex...

Page 31: ...mode rejection 100 dB minimum Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor range 0 1 mV to 0 2000 mV Millivolt output range is determined by the sensi...

Page 32: ...lectrique avant de connecter ou de d connecter le c blage ou de retirer ou d installer le module Electrical Connections Polarity must be observed for signal wiring connections If the input and or out...

Page 33: ...meter Consult factory for other ranges and configurations Minimum range 0 100 Maximum range 0 1 M Input impedance 100 to 1 M minimum Input com mode rejection 100 dB minimum Channel 2 AC Input Range Fa...

Page 34: ...r assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit t...

Page 35: ...e rejection 100 dB minimum Channel 2 Frequency Input Range Factory configured please specify input range Frequency 0 25 Hz to 0 20 kHz Any waveform with 5 microsecond min pulse 100 mV min amplitude ch...

Page 36: ...ectrical Connections Polarity must be observed for signal wiring connections If the input and or output do not function check wiring and polarity Each product is factory configured to your exact input...

Page 37: ...excitation voltage total mV range Input impedance 1 M minimum Input com mode rejection 100 dB minimum Channel 1 Excitation Voltage Range 4 to 10 VDC factory set please specify Adjustment 10 via front...

Page 38: ...ples de c blage Consulter l usine pour assistance ATTENTION viter les risques de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d connecter le...

Page 39: ...V range Input impedance 1 M minimum Input com mode rejection 100 dB minimum Channel 1 Excitation Voltage Range 4 to 10 VDC factory set please specify Adjustment 10 via front potentiometer Maximum outp...

Page 40: ...xamples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENT...

Page 41: ...ion voltage total mV range Input impedance 1 M minimum Input com mode rejection 100 dB minimum Channel 1 Excitation Voltage Range 4 to 10 VDC factory set please specify Adjustment 10 via front potenti...

Page 42: ...output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par un lec tricien ou ing nieur en instrumentat...

Page 43: ...mA Stability 0 01 per C Designed for one 350 W or greater sensor Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor range 0 1 mV to 0 2000 mV Millivolt outp...

Page 44: ...er off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par un lec tricien ou ing nieur en instrumentation qualifi Voi...

Page 45: ...mV V sensitivity X excitation voltage total mV range Input impedance 1 M minimum Input com mode rejection 100 dB minimum Channel 1 Excitation Voltage Range 4 to 10 VDC factory set please specify Adjus...

Page 46: ...ring examples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions...

Page 47: ...mum output 10 VDC maximum at 30 mA Stability 0 01 per C Designed for one 350 W or greater sensor Channel 2 Frequency Input Range Factory configured please specify input range Frequency 0 25 Hz to 0 20...

Page 48: ...nnecter le c blage ou de retirer ou d installer le module Electrical Connections Polarity must be observed for signal wiring connections If the input and or output do not function check wiring and pol...

Page 49: ...mAAC Measurement type True RMS Frequency 40 Hz to 1000 Hz sinusoidal Voltage input impedance 220 k minimum Current input voltage burden 1 0 VRMS maximum Channel 2 DC Input Range Factory configured pl...

Page 50: ...es et des exemples de c blage Consulter l usine pour assistance ATTENTION viter les risques de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d...

Page 51: ...e RMS Frequency 40 Hz to 1000 Hz sinusoidal Voltage input impedance 220 k minimum Current input voltage burden 1 0 VRMS maximum Channel 2 RTD Input Range Factory configured please provide complete sen...

Page 52: ...diagram for terminal designa tions and wiring examples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or r...

Page 53: ...0 1 mAAC to 0 1000 mAAC Measurement type True RMS Frequency 40 Hz to 1000 Hz sinusoidal Voltage input impedance 220 k minimum Current input voltage burden 1 0 VRMS maximum Channel 2 Potentiometer Inpu...

Page 54: ...r assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module Pr cautions ATTENTION Tout le c blage doit t...

Page 55: ...VRMS maximum Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor range 0 1 mV to 0 2000 mV Millivolt output range is determined by the sensitivity of the sen...

Page 56: ...nieur en instrumentation qualifi Voir le dia gramme pour d signations des bornes et des exemples de c blage Consulter l usine pour assistance ATTENTION viter les risques de choc Fermez le signal d ent...

Page 57: ...0 1000 mAAC Measurement type True RMS Frequency 40 Hz to 1000 Hz sinusoidal Voltage input impedance 220 k minimum Current input voltage burden 1 0 VRMS maximum Channel 2 AC Input Range Factory configu...

Page 58: ...ions and wiring examples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or remov ing or installing module P...

Page 59: ...igured please specify input range Frequency 0 25 Hz to 0 20 kHz Any waveform with 5 microsecond min pulse 100 mV min amplitude change 100 mV to 150 VRMS amplitude Channel 2 Sensor Power Supply 15 VDC...

Page 60: ...vant de connecter ou de d connecter le c blage ou de retirer ou d installer le module Electrical Connections Polarity must be observed for signal wiring connections If the input and or output do not f...

Page 61: ...nd one DC voltage or current input and provides two optically isolated DC voltage or current outputs that are linearly related to the inputs The input ranges and the output ranges for each channel are...

Page 62: ...ARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or removing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par...

Page 63: ...aracteristics Impedance at max sensitivity 10 kW nom Impedance at min sensitivity 100 kW nom Sensitivity hysteresis adjustment Multi turn potentiometer Sensitivity hysteresis range 25 mV to 2 5 V typi...

Page 64: ...xamples Consult factory for assistance WARNING Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or removing or installing module Pr cautions ATTENTI...

Page 65: ...25 mADC 10 mVRMS max ripple Channel 1 Characteristics Impedance at max sensitivity 10 kW nom Impedance at min sensitivity 100 kW nom Sensitivity hysteresis adjustment Multi turn potentiometer Sensitiv...

Page 66: ...g wiring or removing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par un lectricien ou ing nieur en instrumentation qualifi Voir le diagramme pour d signations des borne...

Page 67: ...on 600 V input to ground Channel 2 Bridge Input Range Factory configured please specify sensor mV V and mV range Sensor range 0 1 mV to 0 2000 mV Millivolt output range is determined by the sensitivit...

Page 68: ...viter les risques de choc Fermez le signal d entr e le signal de sortie et l alimentation lectrique avant de connecter ou de d connecter le c blage ou de retirer ou d installer le module Electrical Co...

Page 69: ...vity 10 kW nom Impedance at min sensitivity 100 kW nom Sensitivity hysteresis adjustment Multi turn potentiometer Sensitivity hysteresis range 25 mV to 2 5 V typical Normal mode protection 200 of inpu...

Page 70: ...G Avoid shock hazards Turn signal input output and power off before connecting or disconnecting wiring or removing or installing module Pr cautions ATTENTION Tout le c blage doit tre effectu par un le...

Page 71: ...el 2 Characteristics Impedance at max sensitivity 10 kW nom Impedance at min sensitivity 100 kW nom Sensitivity hysteresis adjustment Multi turn potentiometer Sensitivity hysteresis range 25 mV to 2 5...

Page 72: ...ine if your devices provide power to the current loop or if the loop must be powered by the APD module Typical voltage may be 9 24 VDC at your device s termi nals if it provides power to the loop Inpu...

Reviews: