MOBILTEX® DATA LTD.
TITLE:
Installation and Operating Instructions
Calgary, Alberta
DOCUMENT NO.:
SPI1-MAN-001
SHEET:
35 of 57
REV:
1.14
Figure 32 corTalk® Portable Interrupter Configuration Menu Page 2
CONFIG PG2[0]=MORE
[1]NO GPS INTERRUPT
[2]GPS SYNC ONCE
[3]FACTORY DEFAULTS
NO GPS INTERRUPTION
YES
1=YES,0=NO
Normally, the SPI1 will require GPS time lock to operate
the interruption control signal. This parameter allows the
unit to operate without GPS time lock. When this mode
is activated, the interruption control signal can not be
synchronized to other interruption equipment. If the
datalogger subsystem is activated on a schedule while
this mode is active, the resultant time stamp accuracy can
not be guaranteed. (Firmware 1.21 or higher)
This mode is reset to a disabled state each time the SPI1
is powered up.
GPS SYNC ONCE ONLY
YES
1=YES,0=NO
As with the prior option, normally the SPI1 will require
GPS time lock to operate the interruption control signal.
This parameter allows the unit to operate after an initial
GPS time synchronization has been achieved. When this
mode is activated, the interruption control signal will
initially be synchronized to other interruption equipment,
but will diverge over time.
This mode is reset to a disabled state each time the SPI1
is powered up.
FACTORY DEFAULTS
ENTER/OK TO CONTINUE
CANCEL/BACK TO ABORT
Reverts all configuration and scheduler parameters back
to factory default values.