4.4.7 Input delay time 

The input delay time defines the time that the input are triggered before an alarm is initiated. If the 
input returns to the non-alarm status within the delay time, no alarm is sent. The time can be set 
between 0 and 999 seconds. 
As default, the input delay time is set to 1 second. 
 
SMS command alarm delay input 1:  

<CODE>

 

DELAY1:xxx

 

SMS command alarm delay input 2:  

<CODE>

 

DELAY2:xxx 

4.4.8 Inactive time 

Th

e “inactive time” defines the time input 1 or input 2 is not active after an activation.  

In 

case the time is set to “0” (minutes), the input  is active again immediately after returning to the 
non-alarm status. In case the time is set to e.g. 30 minutes, the input remains inactive for the first 
30  minutes.  In  case  the  input  is  again  (or  still)  activated  after  these  30  minutes,  a  new  alarm 
message is sent. 
The time can be set between 0 and 60 minutes. As default, the inactive time is set to 

“0”. 

 
SMS command inactive time input 1:  

<CODE> INACTIVEIN1:xx 

SMS command inactive time input 2:  

<CODE> INACTIVEIN2:xx

 

4.4.9 Alarm repeat time 

In order to emphasize the urgency of the alarm messages, all alarms can be repeated. As long as 
the alarm status has not returned to the inactive status, the SMS alarm will be repeated after the 
‘alarm  repeat  time’.  The  time  can  be  set  between  0  and  24  hours.  As  default  the  alarm  repeat 
time is set to 4 hour. 
 
SMS command alarm repeat time:  

<CODE> REPEAT:xx

 

4.4.10 Test SMS text message 

The Mobeye PowerGuard can send regular test SMS messages 

(´keep alive’) to the 

administrator, to ensure the proper functioning of the unit. The test message function is only 
active in case the unit is armed. 
The interval between the test messages can be set between 0 days (no test message) and 30 
days. The default test interval is set to 0 (no test message).  
 
SMS command interval test message:  

<CODE> TEST:xx

 

4.5 RESET OF SYSTEM 

To reset the Mobeye PowerGuard to its factory settings: 
 

Remove the batteries and external power supply 

Press the outside button while entering the batteries. Keep it pressed for (about) another 
5 seconds 

Release the button immediately after the LED starts to flash 

Reconnect the external power supply  

 
After a successful reset, the status LED on the keypad will blink green to indicate that the module 
is not configured. The security code <CODE> is back to factory settings as well. 

Summary of Contents for PowerGuard CM2100

Page 1: ...USER MANUAL Mobeye PowerGuard CM2100 SW version 1 n...

Page 2: ...from moisture heat and water splashing The guidelines for the battery usage must be regarded Do not expose the device to strong vibrations Do not let it fall from height Do not use in an environment w...

Page 3: ...ossible General settings 6 4 4 1 Phone numbers 6 4 4 2 Identification text 7 4 4 3 Alarm text 7 4 4 4 Alarm notification type SMS or SMS call 7 4 4 5 Power failure delay time 7 4 4 6 Input type 7 4 4...

Page 4: ...rammed The SMS message contains the text Mobeye Power failure In case the power is restored the Mobeye PowerGuard sends a power restored SMS text message to the phone numbers as programmed In case one...

Page 5: ...hould be programmed 2 3 CONNECT THE UNIT TO THE EXTERNAL POWER SUPPLY Connect the external power adapter or any other regulated 12VDC power supply to the power input of the connector V black lead with...

Page 6: ...o switch off disarm the Mobeye PowerGuard Press the on off button at the upper side for 1 second The green LED switches off to indicate the armed status In order to switch on arm the Mobeye PowerGuard...

Page 7: ...nput 1 It does not matter which wire is connected to which connector If necessary the wires can be extended up to 5 meters using appropriate wire material When using a second input connect this to inp...

Page 8: ...be used The initial security code is 1111 In this manual this code is referred to as CODE 4 3 PROGRAMMING THE SETTINGS BY SMS The settings are programmed by SMS text messages Be sure the PowerGuard i...

Page 9: ...ult behaviour after a power failure or an activated input the Mobeye PowerGuard notifies by SMS text message followed by a telephone call beep signal The combination of SMS text and the call increases...

Page 10: ...size the urgency of the alarm messages all alarms can be repeated As long as the alarm status has not returned to the inactive status the SMS alarm will be repeated after the alarm repeat time The tim...

Page 11: ...NO Input type input 2 TYPEIN2 type NO NC NO Delay on input 1 DELAY1 sec 0 999 sec 1 Delay on input 2 DELAY2 sec 0 999 sec 1 Inactive time input 1 INACTIVEIN1 min 0 60 min 0 Inactive time input 2 INAC...

Page 12: ...The status message includes the ARMED NOT CONFIGURED status the status of the inputs and the status of the power and batteries 5 2 OVERVIEW GENERAL SETTINGS The general settings of the Mobeye PowerGu...

Page 13: ...removed Status feedback Status LED pattern Required action Module not configured Blinking 1 second on 1 second off Configure at least one telephone number Module is switched on powered by batteries 1...

Page 14: ...x ca 500 mA Dimensions 80 x 60 x 40 mm Ambient temperature 10 C until 50 C This manual is published by Mobeye All rights the translation included are reserved Any reproduction either photocopy microfi...

Reviews: