Mobeye CM4410 User Manual Download Page 9

When using the Mobeye SIM card:

  

The supplied SIM card has a PIN code protection, which means that it can only be 
used in the Mobeye device. 

Note:

 do not place it in another device. 

 

When using your own SIM card:

  

An own 

SIM card has a “micro” format, is suitable for the 2G network and can make 

calls and send text messages. The PIN code is "0000", or the SIM is PIN code free.  

(A  PIN  code  can  be  changed  or  removed  by  putting  the  SIM  card  in to  any  mobile  phone  and 
entering the 'security' menu.)  

 

 
NB: The settings are saved in the device memory. 
 

Insert the batteries 

Insert  the  two  batteries  (CR123)  in  the  module.  Use  the  +/-  indication  for  the 
correct placement. 

3.2

 

NETWORK CONNECTION AND PROGRAM MODE 

After  placing  the  batteries  the  Mobeye  CM4410  will  search  for  the  network.  The 
LED  flashes  green  and  red.  This  process  normally  takes  10-30  seconds,  in  a  new 
device  this  can  take  some  minutes.  When  the  network  has  been  established  the 
LED will first blink green rapidly and next stay green (or flashes 1 sec. on/1 sec. off 
in case the unit has not been configured yet). 
After 3 minutes a time-out occurs, after which the communication module switches 
off in order to save the batteries. In this low power mode the LED flashes once per 
3 seconds. It will search for network connection once it needs to send notifications. 
It can been forced to establish a network connection by re-inserting the batteries. 

Summary of Contents for CM4410

Page 1: ...USER MANUAL Mobeye CM4410 fire alarm communicator Accessory for Ei Electronics fire detectors SW version 1 n Incl CM4400...

Page 2: ......

Page 3: ...bers 10 5 2 Test message 10 5 3 Call and or SMS own SIM cards 11 6 Mount the CM4410 and perform a test 12 6 1 Mount the CM4410 housing to the ceiling 12 6 2 Connect the EI detector and close the cover...

Page 4: ...an 40 C The device is intended for use in dry and clean places with a residential function Protect the device from moisture heat and water splashing The guidelines for the battery usage must be regard...

Page 5: ...roviders per country In case of a network problem it will switch to another provider or fall back to 2G In addition the Mobeye SIM card offers access to the Mobeye Internet Portal This management envi...

Page 6: ...these are not received in time the portal sends an exception message to the service contacts Chapter 5 describes how to influence the standard behaviour Communication between the Mobeye CM4410 and the...

Page 7: ...i Electronics fire detector activates the input of the Mobeye communicator CM4410 the alarm module sends an alarm SMS text message and calls the phone numbers as programmed in by the user When the bat...

Page 8: ...ctivate the SIM card and the device c Enter the program mode d Program the options and synchronise e User of the portal and the app 3 Programming when using your own SIM card a Enter the program mode...

Page 9: ...module Use the indication for the correct placement 3 2 NETWORK CONNECTION AND PROGRAM MODE After placing the batteries the Mobeye CM4410 will search for the network The LED flashes green and red Thi...

Page 10: ...info mobeye com 4 2 REGISTER THE MOBEYE SIM CARD To activate the Mobeye SIM card in the Mobeye Internet Portal choose activate SIM card on the Add Device screen Fill in the SIM card number This is the...

Page 11: ...regular test message alarm low batteries 2 reinserting batteries 4 4 BASICS OF THE MOBEYE INTERNET PORTAL Dashboard With multiple devices the dashboard shows all devices with the alarm messages in the...

Page 12: ...cluded in reports Alarm dispatch In the block Contacts for messages you link the contact persons who receive alarm and service messages via push notification call text message and or e mail Service me...

Page 13: ...fire alarm communica tor CM4410 can send regular test messages keep alive to the Mobeye Internet Portal to ensure the proper functioning of the unit The test message will also be sent if the unit is...

Page 14: ...time of programming The test time can also be programmed The interval between the test messages can be set between 0 days no test message and 30 days The default test interval is set to 0 no test mess...

Page 15: ...move the back cover from the Ei Electronics detector The CM4410 will be used as back cover Press the green cabled connector to the pins of the Ei Electronics detector Next to the pins the text 1 2 is...

Page 16: ...TUMM button of the Ei detector during a few seconds this can take up to 5 seconds Hold it for another two seconds after the siren starts sounding Now the communicator will establish network connection...

Page 17: ...y in case the first telephone number has been configured During the first 3 minutes the communication module remains active ready to receive SMS commands After 3 minutes a time out occurs and the comm...

Page 18: ...ble to send messages up to 5 telephone numbers The first telephone number TEL1 is mandatory This number will receive next to alarm message also system messages such as battery low and keep alive messa...

Page 19: ...1111 Set telephone number for alarm messages TEL1 TEL5 Empty Delete telephone number DEL1 DEL5 Identification text NAME 20 characters Mobeye Interval test SMS TEST 0 30 days 0 Time test message TESTT...

Page 20: ...f the input power and batteries SMS command status request STATUS example 1111 STATUS LIST OF SETTINGS The settings can be requested by sending following SMS text message SMS command list basic settin...

Page 21: ...ernal power is restored or the adapter is plugged in a socket batteries do not need to be replaced delayed message If delayed message is added to the SMS text messages the message couldn t be sent ear...

Page 22: ...rk can be all connectable detectors from the 600 and 650 series If the CM4410 is used stand alone without linking to other fire detectors this is also possible with the Ei650C and Ei650iC 8 2 SEVERAL...

Page 23: ...st click the name of the device to go to the details screen Next choose Device Click delete to delete the device and confirm the option The SIM card will be disconnected from the device and visible on...

Page 24: ...the network connection is established 2 flashes red every 3 seconds No GSM connection Try the SIM card in any mobile telephone replace SIM card using other telecom provider try the module at another l...

Page 25: ...00 mA Ambient temperature 0 C until 40 C This manual is published by Mobeye All rights the translation included are reserved Any reproduction either photocopy microfilm or saved in an automated data d...

Page 26: ......

Page 27: ...1...

Page 28: ......

Reviews: