© MOBATIME
78 / 108
801104.05
9.3.5
Alive Notification
[dts4132Alive]
Sent out in a configurable interval.
This
Notification
is always sent out, as soon as SNMP and the alarm traps are
activated and a destination address is configured.
The
Notification
sent out contains the following data:
Field
Type
Size
Description
Example
dts4132SysStatus
Unsigned Int
4 Bytes
Contains the internal
system status
66309
dts4132SysAlarms
Byte Array
8 Bytes
64 Bit Alarm flags
1.Byte Bit 0..7
2.Byte Bit 8..15
::
8.Byte Bit 56..63
FFF870FF.FFFFFFFF
¦ ¦ ¦
¦ ¦ 5.Byte
¦ 2.Byte
1.Byte
9.3.6
Alarm Notification
[dts4132Alarm]
Sent out if alarm status changes, i.e.
Notification
is sent out when an alarm flag is set
or deleted.
This
Notification
is always sent out, as soon as SNMP and the alarm traps are
activated and a destination address is configured.
The
Notification
sent out contains the following data:
Field
Type
Size
Description
Example
dts4132TrapAlMsgErrorNr
Byte
1 Byte
No. of the alarm bit (0..63)
3
dts4132TrapAlMsgErrorState
Byte
1 Byte
0 = alarm bit was deleted
1 = alarm bit was set
1
dts4132TrapAlMsgErrorTime
Unsigned
Int
4 Bytes
PC-time in seconds since
01.01.1970 00:00:00
946684805
dts4132TrapAlMsgErrorText
Text
59
Bytes
Error text
Failure supply 1