background image

• Refasten the cover
•  Switch on and check for correct operation ensuring 

the green indicator LEDs are illuminated

•  We recommend, on commissioning the installation, a 

minimum charge period of 24 hours before carrying 
out an emergency duration test

•  The indicator lamp marked 

“CHARGE”

 will be lit 

when the battery is charging. If it is not lit, check that 
the battery is connected to the PCB, and that there 
is a 230V mains supply. The indicator lamp marked 

“LAMPS”

 will be lit if the lamp circuit is complete 

and the lamps are healthy. (NB the indicator lamps 
will not work when the fitting is in emergency mode, 
only while it is connected to the mains supply)

3

             

 

Fig. 2       

  Refasten the cover 

  Switch on and check for correct operation ensuring the green indicator LEDs are illuminated 

  We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

The indicator lamp marked “CHARGE” will be lit when the battery is c

harging. If it is not lit, check that the battery 

is connected to the PCB, and that there is a 230V mains supply. 

The indicator lamp marked “LAMPS” will be lit if 

the lamp circuit is complete and the lamps are healthy. (NB the indicator lamps will not work when the fitting is in 

emergency mode, only while it is connected to the mains supply) 

WARNING 

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 

testing. Irreparable damage will occur if this instruction is not followed 

GENERAL 

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities 

for where facilities exist 

If the batteries have been left in a discharged state for a long period of time, we recommend that one or more 

charge and discharge cycles are performed, to restore the battery to its full capacity 

The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact local 

authorities for the disposal of this toxic waste 

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the 

product 

WARRANTY

 

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product in 

accordance with the current edition of the IEE Wiring Regulations, improper use, or removal of the batch codes 

Fig. 2

WARNING

GENERAL

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 
testing. Irreparable damage will occur if this instruction is not followed

This product should be recycled in the correct manner when it reaches the end of its life. Check local 
authorities for where facilities exist
If the batteries have been left in a discharged state for a long period of time, we recommend that one or 
more charge and discharge cycles are performed, to restore the battery to its full capacity
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact local 
authorities for the disposal of this toxic waste
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may  
damage the product

This product is non-dimmable

WARRANTY

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this 
product in accordance with the current edition of the IEE Wiring Regulations, improper use, or removal of 
the batch codes will invalidate the warranty. If this product should fail within its warranty period it should 
be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept 
responsibility for any installation costs associated with the replacement product. Your statutory rights are not 
affected. ML Accessories reserve the right to alter product specification without prior notice.