These instructions should be read carefully and retained after installation by the end user for future reference and 

maintenance. 

These instructions should be used to aid installation of the following products: 

BT9ACTS / BT14ACTS / BT20ACTS 
SAFETY 

 

This product must be installed in accordance with the latest edition of the IEE Wiring Regulations 

(BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician 

 

Please isolate mains prior to installation or maintenance 

 

Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating 

of the circuit cable, fuse or circuit breaker 

 

Please note the IP (Ingress Protection) rating of this luminaire when deciding the location for 

installation 

 

This product is Class II double insulated 

 

This product is IP65 rated 

INSTALLATION 

Note - Microwave sensors may not be suitable for all installations, for example enclosed spaces, as they are able 

to detect movement through non-metallic surfaces like plasterboard and thin doors. 

  Provide power to the required point of installation. Suitable IP rated junction boxes should be used 

where required 

  Remove the diffuser by rotating bezel anti-clockwise (see Fig. 1) 

 

 

 

 

 

 

 

Fig. 1    

 

 

 

 

 

 

Fig. 2      

 

  Remove the fastening screw securing the LED plate and open the LED plate (see Fig. 2) 

  Mark the location of the fixing holes, and drill the holes ensuring not to infringe with any gas/water 

pipes or electrical cables

 

  Feed the cable via the rubber grommet to retain IP rating, and secure the baseplate to the surface

 

  Connect the Live (brown) and Neutral (blue) to the terminals on the terminal block (see Fig. 3) 

 

Fig. 3 

  Refasten the LED plate screw 

  Choose the required colour temperature by means of the DIP switch (see Fig. 6) 

 

Fig. 6 

  Reattach the diffuser by rotating clockwise 

  Switch on and check for correct operation, ensuring the green indicator LED is illuminated 

  We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

Note: this fitting shuts off power to the Lithium Ion battery periodically to prevent overcharging. 

Therefore, the green LED indicator has been set up to indicate that the emergency inverter is in good 

condition, not to indicate that the battery is charging. The installer must ensure that the battery is 

connected. 
WARNING 

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 

testing. Irreparable damage will occur if this instruction is not followed. 

GENERAL 

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities 

for where facilities exist. 

The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please contact the local 

authorities for the disposal of this toxic waste. 

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the 

product. 

This product is non-dimmable. 

WARRANTY

 

This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product in 

accordance with the current edition of the IEE Wiring Regulations, improper use, or removal of the batch codes 

will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place 

of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation 

costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the 

right to alter product specification without prior notice. 

TESTING FOR EMERGENCY LUMINAIRES 

Recommended routine test procedure in accordance with BS5266 

 

Daily check

 

 check LED charge indicator is illuminated 

 

Monthly functional test

 

 simulate a mains supply failure for approx. 30 seconds by operation of key 

switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge 

indicator is illuminated 

 

Annual 3-hour duration test

 - simulate a mains supply failure for a 3-hour continuous test by operation of 

key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge 

indicator is illuminated 

 

If the luminaire fails any of the above tests, please contact a qualified electrician 

 

• The additional terminal called Slave Live (L’) is available to enable the sensor to power on 
   additional luminaires. A max. LED load of 400W can be controlled by the sensor
• Please see DIP Switch Layout to set up sensor
• Refasten the LED plate screw
• Choose the required colour temperature by means of the DIP switch (see Fig. 4)

Fig. 3

Fig. 4

Summary of Contents for BT ACTS Series

Page 1: ...INSTALLATION MAINTENANCE MANUAL BTxxACTS ...

Page 2: ...e latest edition of the IEE Wiring Regulations BS7671 and current Building Regulations If in any doubt consult a qualified electrician Please isolate mains prior to installation or maintenance Check the total load on the circuit including when this luminaire is fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress Protection rating of this lumina...

Page 3: ...ding when this luminaire is fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress Protection rating of this luminaire when deciding the location for installation This product is Class II double insulated This product is IP65 rated LATION Provide power to the required point of installation Suitable IP rated junction boxes should be used where requ...

Page 4: ...w Choose the required colour temperature by means of the DIP switch see Fig 6 Fig 6 Reattach the diffuser by rotating clockwise Switch on and check for correct operation ensuring the green indicator LED is illuminated The additional terminal called Slave Live L is available to enable the sensor to power on additional luminaires A max LED load of 400W can be controlled by the sensor Please see DIP ...

Page 5: ...icate that the emergency inverter is in good condition not to indicate that the battery is charging The installer must ensure that the battery is connected SENSOR LAYOUT DIP SWITCH LAYOUT Switch on and check for correct operation ensuring the green indicator LED is illuminated We recommend on commissioning the installation a minimum charge period of 24 hours before carrying out an emergency durati...

Page 6: ...ht sensor will switch the lamp on when motion is detected regardless of the ambient light level DIP SWITCH SETTINGS Detection area Hold time This is the time period the lamp remains at 100 after no motion is detected Hold time This is the time period the lamp remains at 100 after no motion is dete This is the time period the lamp remains at 100 after no motion is detected ...

Page 7: ...eplaced by the end user and a control gear which can be replaced by a professional Clean with a soft dry cloth only do not use aggressive cleaning products or solvents which may damage the product Do not use any source of high pressure washers to maintain or clean this luminaire This product is non dimmable This product should be dismantled for disposal when it reaches the end of its life Please s...

Page 8: ... this product should fail within its warranty period it should be returned to the place of purchase for a free of charge replacement ML Accessories does not accept responsibility for any installation costs associated with the replacement product Your statutory rights are not affected ML Accessories reserve the right to alter product specification without prior notice ML Accessories Limited LU5 4LT...

Reviews: