MJK 202925 Manual Download Page 8

8

Manual

Manual Expert 1400/3400 GB 0704

MJK Automation A/S

Byageren 7
DK-2850 Naerum 
Denmark 
Tel.:  +45 45 56 06 56 
Fax:  +45 45 56 06 46 
[email protected] 
www.mjk.com

Appendices

Mechanical dimensions

Cable bracket

MJK model 3400 

Level transmitter

Cable bracket

MJK model 1400 

Level transmitter

135

135

15

2

65

Demands for cables in explosive areas

Using the the KFD0-CS-Ex1.50P isolator (MJK order 

no.: 202993) the max cable length can be calculated.
The Cmax and Lmax for the isolator in explosion group 

IIC are: Cmax : 2,41 μF, Lmax : 4 mH. The capacity of 

MJK cable type 691005 or 691014 < 800 pF/m and 

the inductance is < 1,5 μH/m and the capacity and the 

inductance of the Expert Level Transmitter is Ci = 3,5 nF 

Li = 7 μH. Cable length based on the capacity:

Max.cable length = (Cmax-Ci)/Ccable = 129 m

Cable length based of the inductance:

Max. cable length = (Lmax-Li)/Lcable = 2862 m

In this case the capacitance sets the limit of the cable 

length to 129 m. If another approved isolator or another 

cable is used the max. cable length must be recalculated.
Using The Z788 Zener Barrier (MJK Order no. 202995) 

the max cable length can be calculated. The Cmax and 

Lmax for the zener barrier in explosion group IIC are: 

Cmax : 83 nF, Lmax : 3,05 mH. The capacity of MJK 

cable type 691014 is < 800 pF/m and the inductance is 

< 1,5 μH/m and the capacity and the inductance of the 

Expert Level Transmitter is Ci = 3,5 nF Li = 7 μH.  

Cable length based on the capacity: 

Max. cable length = (Cmax-Ci)/Ccable = 99 m 

Cable length based on the inductance:

Max. cable length = (Lmax-Li)/Lcable = 2,0 km

In this case the capacitance sets the limit of the cable 

length to 99 m. If another Atex-approved isolator or 

another cable is used the max. cable length must  

be recalulated.

Summary of Contents for 202925

Page 1: ...l 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com As our products are continuously improved we reserve the right to make any change in the stated specifications and dimensions without prior...

Page 2: ...ct complies with the requirements concerning electromagnetic compatibility EMC stipulated in Council directive no 89 336 EEC of 3rd May 1989 altered at directive no 92 31 EEC on the approximation of t...

Page 3: ...air 4 Mechanical mounting 5 Model 1400 5 Model 3400 5 Model 3400 with thread top 5 Electrical mounting 6 Cable length vs supply voltage 6 Designation of wires cutting stripping the cable 6 Explosion h...

Page 4: ...s are printed on a label on the transmitter housing For all versions the pressure range is indicated on the label Safety instructions 1 Read this manual carefully 2 Be aware of the environment on the...

Page 5: ...itting by sliding the two plastic jaws upwards place the cable between the jaws and slide the jaws downwards until the cable locks Secure the cable fitting by pulling the cable downwards 3 Lower the p...

Page 6: ...transmitter or make any attemt to program the tranmitter while the transmitter is located in an explosion hazardous zone Electrical mounting Cable length vs supply voltage The cable can be lengthened...

Page 7: ...r The Z788 Zener Barrier MJK part no 202995 has a safety fuse which will blow if the current exceeds the limit The voltage protection in the Zener barrier contains a number of zener diodes which are c...

Page 8: ...ength Cmax Ci Ccable 129 m Cable length based of the inductance Max cable length Lmax Li Lcable 2862 m In this case the capacitance sets the limit of the cable length to 129 m If another approved isol...

Page 9: ...ur or mists Equipment category Explosive gas air mixtures G Category 1 Zone 0 1 or 2 Category 2 Zone 1 or 2 Category 3 Zone 2 Designation of explosion protection EEx ia IIC T6 Electrical apparatus wit...

Page 10: ...02993 the max cable length is 129 m Using The Z788 Zener Barrier MJK Order no 202995 the max cable length is 99 m Alternatively other cable types with equivalent specifica tions may be used If a cable...

Page 11: ...mechanical parameters 4 Install the device only in media for which the wetted materials have sufficient durability 5 Expert transmitter type 1400 3400 hydrostatics level transmitter may not be used i...

Page 12: ...tter than 0 2 FS 0 2 FS Measurement accuracy Better than 0 1 FS 10 to 30 C Better than 0 2 FS full temperature range Long time stability Better than 0 1 FS per year Materials Housing stainless steel A...

Page 13: ...op 203955 Expert 3400 range 0 10 mWG 203963 Expert 3400 range 0 3 m 1 RG top 203956 Expert 3400 range 0 30 mWG 202925 Expert 3400 w special meas range MJK Expert 3400 Hydrostatic Level Transmitter Nom...

Page 14: ...14 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com This page intentionally left blank...

Page 15: ...15 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com This page intentionally left blank...

Page 16: ...16 Manual Manual Expert 1400 3400 GB 0704 MJK Automation A S Byageren 7 DK 2850 Naerum Denmark Tel 45 45 56 06 56 Fax 45 45 56 06 46 mjk mjk com www mjk com...

Reviews: