'12 • SRK-T-122
A
RWA000Z240
1. SPECIFICATIONS
Adapted to
RoHS
directive
Model
Item
SRK90CL-BN
Indoor unit
SRK90CL-BN
Outdoor unit
SRC90CL-BN
Cooling capacity (1)-(a)
(1)-(b)
W
8300
7550
Power supply
1 Phase, 220
~
240 V, 50Hz
Operation
data (1)
Power
consumption
Cooling (1)-(a)
(1)-(b)
kW
2.92 / 3.03 ( 220 / 240 V )
3.44 / 3.475 / 3.51 ( 220 / 230 / 240 V )
Running
current
Cooling (1)-(a)
(1)-(b)
A
14.0 / 13.8 ( 220 / 240 V )
16.3 / 16.0 / 15.8 ( 220 / 230 / 240 V )
Inrush current (1)-(a)
(1)-(b)
14.0 / 13.8 ( 220 / 240 V )
16.3 / 16.0 / 15.8 ( 220 / 230 / 240 V )
Max current
17.5
COP
Cooling (1)-(a)
(1)-(b)
2.84 / 2.74
2.19 / 2.17 / 2.15
Noise
level
Cooling
Sound level
dB(A)
51
57
Exterior dimensions (Height x Width x Depth)
mm
318 x 1098 x 248
750 x 880 x 340
Exterior appearance
( Munsell color )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
Net weight
kg
17
68
Refrigerant
equipment
Compressor type & Q'ty
—
2JD514D5AA03 (Twin Rotary type ) x 1
Motor (Starting method)
kW
—
2.4
Refrigerant oil
0.9 ( ATMOS NM56M or SUNISO 4GDID )
Refrigerant (3)
kg
R22 1.75 ( Pre-Charged up to the piping length of 7m )
Refrigerant control
Capillary tubes + Electronic expansion valve
Deice control
Microcomputer control
Air handling
equipment
Fan type & Q'ty
Tangential fan x 1
Propeller fan x 1
Motor
W
56
85
Air flow
Cooling
m
3
/min
20.5
60.0
Fresh air intake
Not possible
—
Air filter, Quality / Quantity
Polypropylene net ( washable ) x 2
—
Shock & vibration absorber
—
Cushion rubber ( for compressor )
Electric heater
—
—
Operation
control
Operation switch
Wireless-Remote control
—
Room temperature control
Microcomputer thermostat
—
Operation Display
RUN: Green , TIMER: Yellow , HI POWER: Green , ECONO: Orange
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Installation
data
Refrigerant piping size (O.D)
mm
Liquid line:
φ
6.35 ( 1/4" ) Gas line:
φ
15.88 ( 5/8" )
connecting method
Flare connecting
Attached length of piping
m
Liquid line : 0.70
Gas Line : 0.63
—
Insulation for piping
Necessary ( Both sides ), independent
Refrigerant line (one way) length
m
Max.25
Vertical height difference between
outdoor unit and indoor unit
Max.15( Outdoor unit is higher )
Max.15( Outdoor unit is lower )
Drain hose
Connectable ( VP 16 )
—
Power cable
—
Recommended breaker size
A
30
Connection wiring
Size x Core number
1.5mm
2
x 4 cores ( Including earth cable )
Connecting method
Terminal block ( Screw fixing type )
Accessories (included)
Mounting kit, Clean filter ( Natural Enzyme filter x 1, Photocatalytic washable deodorizing filter x 1 )
Optional parts
Interface kit ( SC-BIKN )
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling (a)
27˚C
19˚C
35˚C
24˚C
ISO-T1, JIS C 9612
Cooling (b)
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO 385/386
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220/230/240V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 7 m connecting piping.(Purging is not required even for the short piping. )
If the piping length is longer, when it is 7 to 25 m , add 25 g refrigerant per meter.
The pipe length is 7.5m.