background image

-

 61 

-

 '18 • SRK-T-250

 CAUTION

6.  Repair to intrinsically safe components

•  Do not apply any permanent inductive or 

capacitance loads to the circuit without ensuring 
that this will not exceed the permissible voltage and 
current permitted for the equipment in use.

•  Intrinsically safe components are the only types that 

can be worked on while live in the presence of a 

•  The test apparatus shall be at the correct rating.
• 

the manufacturer.

•  Other parts may result in the ignition of refrigerant 

in the atmosphere from a leak.

7.  Cabling

•  Check that cabling will not be subject to wear, 

corrosion, excessive pressure, vibration, sharp 
edges or any other adverse environmental effects. 
The check shall also take into account the effects 
of aging or continual vibration from sources such as 
compressors or fans.

8. 

•  Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 
refrigerant leaks.

•  A halide torch (or any other detector using a naked 

9.  Leak detection methods

•  Electronic leak detectors may be used to detect 

refrigerants, the sensitivity may not be adequate, or 
may need re-calibration. (Detection equipment shall 
be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of 

ignition and is suitable for the refrigerant used.

•  Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and shall 
be calibrated to the refrigerant employed, and the 
appropriate percentage of gas (25 % maximum) is 

• 

refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may 
react with the refrigerant and corrode the copper 
pipe-work.

• 

removed/extinguished.

•  If a leakage of refrigerant is found which requires 

brazing, all of the refrigerant shall be recovered 
from the system, or isolated (by means of shut off 
valves) in a part of the system remote from the 
leak.

• 

oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the 
brazing process.

10. Removal and evacuation

•  When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 

refrigerants it is important that best practice is 

•  The following procedure shall be adhered to:

– remove refrigerant;
– purge the circuit with inert gas;
– evacuate;
– purge again with inert gas;
– open the circuit by cutting or brazing.

•  The refrigerant charge shall be recovered into the 

correct recovery cylinders.

• 

the unit safe. 
This process may need to be repeated several 
times.

•  Compressed air or oxygen shall not be used for 

purging refrigerant systems.

• 

the working pressure is achieved, then venting to 

 

This process shall be repeated until no refrigerant 
is within the system.

• 

shall be vented down to atmospheric pressure to 
enable work to take place. 
This operation is absolutely vital if brazing 
operations on the pipe-work are to take place.

•  Ensure that the outlet for the vacuum pump is not 

close to any ignition sources and that ventilation is 
available.

11. Charging procedures

•  In addition to conventional charging procedures, the 

following requirements shall be followed.
– Ensure that contamination of different refrigerants 

does not occur when using charging equipment. 
Hoses or lines shall be as short as possible to 
minimise the amount of refrigerant contained in 
them.

– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

– Label the system when charging is complete (if 

not already).

refrigeration system.

•  Prior to recharging the system, it shall be pressure-

tested with the appropriate purging gas.

•  The system shall be leak-tested on completion of 

charging but prior to commissioning.

•  A follow up leak test shall be carried out prior to 

leaving the site.

12. Decommissioning

•  Before carrying out this procedure, it is essential 

that the technician is completely familiar with the 
equipment and all its detail. 

•  It is recommended good practice that all 

refrigerants are recovered safely. 

•  Prior to the task being carried out, an oil and 

refrigerant sample shall be taken in case analysis is 
required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and its 

operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure that:

– mechanical handling equipment is available, if 

required, for handling refrigerant cylinders;

– all personal protective equipment is available and 

being used correctly;

– the recovery process is supervised at all times by 

a competent person;

– recovery equipment and cylinders conform to the 

appropriate standards.

d) Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so 

that refrigerant can be removed from various parts 
of the system.

f)   Make sure that cylinder is situated on the scales 

before recovery takes place.

g)  Start the recovery machine and operate in 

accordance with manufacturer’s instructions.

h)  

volume liquid charge).

i)   Do not exceed the maximum working pressure of 

the cylinder, even temporarily.

j)   

and the process completed, make sure that the 
cylinders and the equipment are removed from site 
promptly and all isolation valves on the equipment 
are closed off.

k)  Recovered refrigerant shall not be charged into 

another refrigeration system unless it has been 
cleaned and checked.

13. Labelling

•  Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The 
label shall be dated and signed.

• 

ensure that there are labels on the equipment 

refrigerant.

14. Recovery

•  When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended 
good practice that all refrigerants are removed 
safely.

•  When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovery cylinders 
are employed.

•  Ensure that the correct number of cylinders for 

holding the total system charge are available.

•  All cylinders to be used are designated for 

the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of 
refrigerant).

•  Cylinders shall be complete with pressure relief 

valve and associated shut-off valves in good 
working order.

•  Empty recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

•  The recovery equipment shall be in good working 

order with a set of instructions concerning the 
equipment that is at hand and shall be suitable 
for the recovery of all appropriate refrigerants 

•  In addition, a set of calibrated weighing scales shall 

be available and in good working order.

•  Hoses shall be complete with leak-free disconnect 

couplings and in good condition.

•  Before using the recovery machine, check that it 

is in satisfactory working order, has been properly 
maintained and that any associated electrical 
components are sealed to prevent ignition in the 
event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the 

refrigerant supplier in the correct recovery cylinder, 
and the relevant Waste Transfer Note arranged. 
Do not mix refrigerants in recovery units and 
especially not in cylinders.

•  If compressors or compressor oils are to be 

removed, ensure that they have been evacuated to 

refrigerant does not remain within the lubricant.

•  The evacuation process shall be carried out prior to 

returning the compressor to the suppliers.

•  Only electric heating to the compressor body shall 

be employed to accelerate this process.

•  When oil is drained from a system, it shall be 

carried out safely.

15. Other safety precautions

•  A brazed, welded, or mechanical connection shall 

be made before opening the valves to permit 

parts.

•  Flammable refrigerant used, refrigerant tubing 

protected or enclosed to avoid mechanical damage 
(IEC/EN 60335-2-40/A1).

•  Tubing protected to extent that it will not be handled 

or used for carrying during moving of product (IEC/
EN 60335-2-40/A1).

•  Flammable refrigerant used, low temperature solder 

alloys, such as lead/tin alloys, not acceptable for 
pipe connections (IEC/EN 60335-2-40/A1).

• 

outdoor.

Summary of Contents for SRK 25ZS-W

Page 1: ...Manual No 18 SRK T 250 TECHNICAL MANUAL INVERTER WALL MOUNTED TYPE RESIDENTIAL AIR CONDITIONERS Split system air to air heat pump type SRK20ZS W WB WT 25ZS W WB WT 35ZS W WB WT 50ZS W WB WT...

Page 2: ...direction adjustment 65 5 Selection of the annual cooling function 64 63 4 Installing two air conditioners in the same room 63 3 Auto restart function 2 Unit ON OFF button 63 1 Operation control func...

Page 3: ...pacity 2 0kW Model name SRK Wall mounted type SRC Outdoor unit S W 101 11 OPTION PARTS 123 12 TECHNICAL INFORMATION 101 117 1 Wired remote control 2 Interface kit SC BIKN2 E 3 Superlink E board SC ADN...

Page 4: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Page 5: ...ir filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control W...

Page 6: ...Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control...

Page 7: ...lter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wirele...

Page 8: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Page 9: ...ossible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Page 10: ...possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote...

Page 11: ...ble Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote cont...

Page 12: ...uality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote control Wireless rem...

Page 13: ...possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remot...

Page 14: ...ot possible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Rem...

Page 15: ...ssible Air filter Quality Quantity Polypropylene net Washable x 2 Shock vibration absorber Rubber sleeve for fan motor Rubber sleeve for fan motor compressor Electric heater Operation control Remote c...

Page 16: ...1 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK35ZS WB 11 5 1 21 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK50ZS WB 12 0 1 21 0 00 0 33 0 88 0 00 0 00 0 00 0 00 SRK20ZS WT 11 5 1 21 0 00 0 33 0 88 0 00 0 00 0 00...

Page 17: ...n the right side of the unit 2 To connect the wired remote control the interface kit SC BIKN2 E is required 120 19 60 24 167 45 45 870 290 Outlet for downward piping Refer to the top view 230 3 60 13...

Page 18: ...7 42 5 40 40 138 4 33 5 15 8 290 540 20 14 6 16 4 260 130 270 Center of gravity Center of gravity Notes 1 The unit must not be surrounded by walls on the four sides 2 The unit must be fixed with ancho...

Page 19: ...14 6 16 4 145 270 Terminal block 97 7 42 5 15 8 595 275 40 40 138 4 33 5 Center of gravity 69 4 Center of gravity Notes 1 The unit must not be surrounded by walls on the four sides 2 The unit must be...

Page 20: ...19 18 SRK T 250 3 Remote control Unit mm 60 24 167 a Wireless remote control...

Page 21: ...ere the average room temperature cannot be detected Place near the equipment to generate heat Place affected by outside air in opening closing the door Place exposed to direct sunlight or wind from ai...

Page 22: ...2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y Sheath Upper cace Board Wiring Upper Lower Y X Tighten the screws after...

Page 23: ...WHITE RED YELLOW GREEN HEAT EXCHANGER 2 N 3 YELLOW GREEN ONLY 2 2 HEAT EXCHANGER 5 FUSE VARISTOR R AMP TERMINAL BLOCK MOTOR FAN LEFT MOTOR LOUVER MOTOR FLAP RIGHT MOTOR LOUVER HEAT EXCHANGER SENSOR 1...

Page 24: ...e x number TH4 Discharge pipe temp sensor TH3 Outdoor air temp sensor TH2 Heat exchanger sensor L Reactor FMo Fan motor EEV Electric expansion valve coil CM Compressor motor CNTH CNFAN CNEEV CN20S Con...

Page 25: ...ctor FMo Fan motor EEV Electric expansion valve coil CM Compressor motor CNTH CNFAN CNEEV CN20S Connector 20S 4 way valve coil Item Description BK Black Mark Color BL Blue RD Red WH White YE Yellow YG...

Page 26: ...eating 56 dB A Cooling Heating ISO5151 T1 H1 Rated capacity value 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB M...

Page 27: ...g 56 dB A Level Heating 58 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Page 28: ...g 61 dB A Level Heating 61 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Page 29: ...g 61 dB A Level Heating 63 dB A Cooling Heating ISO5151 T1 H1 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound power level dB Mid o...

Page 30: ...000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Mike po...

Page 31: ...N70 N20 10 20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pr...

Page 32: ...5 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Mike position at highest n...

Page 33: ...0 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave ba...

Page 34: ...20 30 40 50 60 70 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure lev...

Page 35: ...63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band...

Page 36: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Page 37: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band fr...

Page 38: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Page 39: ...0 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave ba...

Page 40: ...125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band f...

Page 41: ...10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x1...

Page 42: ...500 1000 2000 4000 8000 Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 N50 N30...

Page 43: ...ssure level dB Standard 2x10 5 Pa Mid octave band frequency Hz Sound pressure level dB Standard 2x10 5 Pa Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60...

Page 44: ...7D 5 PIPING SYSTEM Models SRK20ZS S 25ZS S Model SRK35ZS S Humidity sensor HD pipe pipe 4 way valve 4 way valve 5 PIPING SYSTEM Models SRK20ZS W 25ZS W SRK20ZS WB 25ZS WB SRK20ZS WT 25ZS WT Models SRK...

Page 45: ...h1 Th21 Gas TH2 Heat exchanger sensor TH1 EEV Capillary tube Heat exchanger Model SRK50ZM S Indoor unit Outdoor unit Flare connection Flare connection Liquid pipe 6 35 Gas pipe 12 7 Service valve Heat...

Page 46: ...e conditions as follows The net cooling and heating capacity can be obtained in the following way Net capacity Capacity shown on specification Correction factors as follows 1 Coefficient of cooling an...

Page 47: ...apacity Piping length m Cooling Heating 7 1 0 1 0 10 0 99 1 0 15 0 975 1 0 20 0 965 1 0 25 0 95 1 0 Air inlet temperature of outdoor unit in CWB Adjustment coefficient 15 0 95 0 95 0 94 0 93 0 91 0 88...

Page 48: ...56 2 34 2 64 2 33 2 70 2 31 2 84 2 44 2 95 2 40 32 2 18 2 07 2 31 2 15 2 50 2 32 2 58 2 31 2 64 2 29 2 79 2 43 2 90 2 38 34 2 11 2 00 2 25 2 12 2 44 2 29 2 53 2 29 2 59 2 27 2 74 2 41 2 85 2 37 35 2...

Page 49: ...48 18 SRK T 250 8 APPLICATION DATA 1 Installation of indoor unit RLF012A100 Model SRK20 25 35 50 R410A REFRIGERANT USED...

Page 50: ...49 18 SRK T 250...

Page 51: ...50 18 SRK T 250...

Page 52: ...51 18 SRK T 250...

Page 53: ...52 18 SRK T 250...

Page 54: ...53 18 SRK T 250...

Page 55: ...54 18 SRK T 250...

Page 56: ...55 18 SRK T 250...

Page 57: ...56 18 SRK T 250 2 Installation of outdoor unit RWC012A068...

Page 58: ...57 18 SRK T 250...

Page 59: ...58 18 SRK T 250...

Page 60: ...59 18 SRK T 250...

Page 61: ...Where electrical components are being changed At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assi...

Page 62: ...gerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that...

Page 63: ...switch selects the CLEAN operation display brightness adjustment and PRESET operation ON TIMER button This button selects ON TIMER operation TIMER button This button is used for setting the current t...

Page 64: ...t one unit can be operated with only one remote control a Setting the wireless remote control i Slide the cover and take out the batteries ii Disconnect the switching line next to the battery with wir...

Page 65: ...n for 15 minutes continuously The wireless remote control displays HIGH POWER mark and the FAN SPEED display disappears a During the HIGH POWER operation the room temperature is not controlled When it...

Page 66: ...the power suppressed in order to avoid an excessive cooling or heating The unit operate 1 5 higher than the setting temperature during cooling or 2 5 lower than that during heating The wireless remote...

Page 67: ...uto operation a i ii Cooling Air flow selection Operation mode AUTO HI MED LO Heating Room temp Setting temp 5 C Room temp Setting temp 5 C Setting temp Room temp 5 C Setting temp Room temp 5 C HIGH P...

Page 68: ...eration is set the unit operates by dropping the outdoor fan speed and the compressor speed 13 Night setback operation When the night setback operation is set the heating operation starts with the set...

Page 69: ...This function can be used when it is necessary to adjust the brightness of unit display Note 1 When the unit displays self diagnosis or service mode brightness level is always LV2 Brightness level Run...

Page 70: ...d air are satisfied is satisfied Total compressor operation time After finish of defrost operation C or less for 3 minutes continuously Total compressor operation time 20 115rps 20 115rps 20 86rps 20...

Page 71: ...ls SRK35 50 Max 17 minutes and 30seconds Depends on an operation condition the time can be longer than 7 minutes 2 7 minutes Hot keep operation i Setting ii Contents of control Signal of wireless remo...

Page 72: ...is selected during heating cooling or DRY mode the unit is operated in the previous operation mode d Setting temperature can be adjusted within the following range There is the relationship as shown...

Page 73: ...d direction control is performed a When the vertical wind direction is set at other than the vertical swing the flaps change to the horizontal position b When the horizontal wind direction is set at o...

Page 74: ...erature is in the range of P2 P3 the speed is reduced by 6 rps at each 30 seconds 2 When the temperature is P3 or higher the compressor is stopped 3 When the outdoor heat exchanger temperature is in t...

Page 75: ...ature 50 50 44 30 50 Range A Range B 50 44 60 60 27 Release Release SRK20 25 35 SRK50 2 It checks the outdoor temperature TH2 once every hour to judge the operation range When either of the following...

Page 76: ...with the fuzzy calculation exceeds the upper limit the upper limit value is maintained The lower limit of compressor speed is set to 27 rps and even if the calculated result becomes lower than that a...

Page 77: ...shown in the figure below 3 Reset conditions 1 2 10 Reset conditions When either of the following condition is satisfied 1 The outdoor air temperature TH2 becomes 6 C 2 The compressor speed is 0 rps...

Page 78: ...rps 20 rps 20 rps item i ii is satisfied Once the unit is stopped by this function it is not min 1 100 110 C 90 100 C 90 100 C SRK20 35 SRK50 i ii i ii i ii air conditioning has elapsed air condition...

Page 79: ...st operation ii Contents of control 1 iii Reset condition When the compressor has been turned OFF 2 When the conditions of i above are satisfied the compressor stops Error stop occurs when the compres...

Page 80: ...G PROCEDURES FOR ELECTRICAL EQUIPMENT 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooting procedure If the air conditioner does not run at all Important YES YES YES NO NO NO NO YES Re...

Page 81: ...80 18 SRK T 250 09 SRK DB 087D 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 81 82 88 82 88 service service...

Reviews: