Explanation of symbols

:  Conduct the cleaning and adjustment according to the inspection result

:  In case of abnormality after inspection, replace or repair the corresponding part.

:  Conduct the periodic replacement (consumable components)

 :  Random failure

 :  Wear-out failure

Part Name

Regular Inspection

Preventive Maintenance*

Remarks

Part Name

Details of Inspection

Inspection Method

Criteria <Standard>

Details of Maintenance

Inspection 

Interval

Maintenance Interval

(Used Hours/Duration)

Elapsed Years

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15

Electric and 
electronic 
parts

Crankcase heater

- Conductivity check
-  Insulation resistance measurement
- Appearance check

Tester
500 V mega
Visual inspection

-  It should be in a conducting state
-  The resistance value should be 1 M

 or more

-  There should be no abnormality

-  Replace it if it is not in a conducting state
-  Replace it if the resistance value is 1 M

 or less

Every year

Before 

the air-

conditioning 

season

8 years

Consumable 
components

Anti-freezing heater

- Conductivity check
-  Insulation resistance, appearance check

Tester
500 V mega, visual 
inspection

-  It should be in a conducting state
-  The resistance value should be 1 M

 or more, 

there should be no abnormality

-  Replace it if it is not in a conducting state
-  Replace it if the resistance value is 1 M

 or less

20,000 Hr

Electric component box 
(including inverter)

-  Circuit insulation resistance check

-  Terminal part, connector looseness check

500 V mega

Driver, visual 
inspection

-  The resistance value should be 1 M

 or more

-  There should be no looseness at the connecting 

part

-  Clean with a brush in case of extreme dust adhesion
-  Replace it if the resistance value is 1 M

 or less

-  Retighten or re-insert it if there is looseness

25,000 Hr

Electrolytic 
capacitor

-  Capacitor (electrolytic) appearance check

Visual inspection

-  There should be no liquid leakage or deformation

-  Appearance check, replace it if there is liquid 

leakage

Smoothing 
capacitor

-  Measurement of electrical capacitance and 

insulation resistance

- Appearance check

Electrostatic 
instrument, 500 V 
mega Tester

-  Should be of specifi ed volume or more
-  The resistance value should be 1 M

 or more

-  Replace parts regularly
-  Replace it if the resistance value is 1 M

 or less

10 years

Consumable 
components

Terminal 
block

-  Terminal part screw looseness, deposit of dirt

Driver, visual 
inspection

-  It should not be loose
-  There should be no deposited foreign matter

-  Retighten it if it is loose.
-  Clean with a brush in case of deposited foreign 

matter adhesion

25,000 Hr

Electrical 
component
(including 
boards, etc.)

-  HIC board short circuit check
-  Visual check of dirt adhesion to the board, etc.

-  Self-diagnosis mode, appearance check

Tester
Visual inspection
Visual inspection

-  Should be of a specifi ed resistance value
-  There should be no deposited foreign matter

-  There should be no abnormal display

-  Replace it if it is outside the specifi ed resistance value
-  Clean with a brush in case of deposited foreign 

matter adhesion

-  Replace or correct the part

25,000 Hr

Pressure sensor, 
temperature sensor

-  Open, short circuit, earth, appearance check

Tester, visual 
inspection

-  Should be of a specifi ed resistance value
-  There should be no cracking or discoloration

-  Replace it in case of disconnection and short 

circuit

5 years

Switch, etc.
(including 
FFB, ELB)

Electromagnetic 
switch
Overcurrent relay

Auxiliary relay, etc.

-  Operation, appearance check

-  Rough contact surface

Visual inspection

Visual inspection

-  There should be no deformation

-  It should operate as prescribed, there should be no 

deformation

-  There should be no deformation or discoloration

-  Replace it in case of malfunction, deformation, and 

discoloration

25,000 Hr

Switching power source 
transformer

-  Output voltage measurement

Tester

-  Output voltage should be within a specifi ed value

-  Replace it if there is voltage abnormality

10 years

Cooling fan

-  Insulation resistance, abnormal sound generation

500 V mega, audible 
inspection

-  The resistance value should be 1 M

 or more, 

there should be no abnormal sound

-  Replace it if the resistance value is 1 M

 or less

-  Replace it in case of fan lock

20,000 Hr

Fuse

- Appearance check

Visual inspection

- There should be no deformation or discoloration

- Replace it when it is shutdown

10 years

Consumable 
components

Note 1)  Random fault is an unexpected failure which occurs before 

the wear is progressed, within the service life of the parts and 
equipment. It is difficult to establish a technological measure 
against the random fault. At the moment, statistical handling is the 
only measure against the random fault.

Note 2)  The elapsed year marked with * assumes the operating time 

as 10 hours/day and 2500 hours/year in a normal operating 
condition without frequent start/stop. This may vary according to 
the operating condition. Please check the calculation basis of the 
elapsed year when making a maintenance contract.

Note 3) 

 illustrates the estimated timing when the wear-out 

failure starts and how the failure rate increases as the time passes.

Summary of Contents for RC-E5

Page 1: ... συμβατότητας EMC και την οδηγία LV 2006 95 ΕΚ Tο οήμα CE ισχύει μόνον σε περιοχές όπου η τροφοδοσία είναι 50 Hz Ceiling cassette 4 way FDT Ceiling cassette 4 way Compact 600 600mm FDTC Duct connected High static pressure FDU FDUS Duct connected Middle static pressure FDUM Ceiling Suspended FDE Floor Standing FDF USER S MANUAL ENGLISH MANUEL DE L UTILISATEUR ANWENDERHANDBUCH DEUTSCH ISTRUZIONI PER...

Page 2: ... BUTTON OPERATION 18 INSTALLATION RELOCATION AND INSPECTION MAINTENANCE 18 OPERATION RANGE 18 MAINTENANCE AND INSPECTION GUIDELINE OF MAIN PARTS OF PACKAGED AIR CONDITIONER 19 INSTALLATION PRECAUTIONS DANGER Make sure to have the installation done by your dealer or a specialist If you install by yourself and the unit is not properly installed water leakage electric shock fire and injuries caused b...

Page 3: ... But if it leaks and contacts fire such as fan heater space heater or cooking heater it may produce toxic chemicals Do not insert fingers or sticks even if air blower does not operate It may suddenly operate and cause injuries OPERATION PRECAUTIONS DANGER This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of e...

Page 4: ...y lead to injuries Do not place any other electric appliances or household goods below or around the air conditioner Dripping from the unit may lead to failure or contamination Do not touch the aluminum fin Otherwise it may lead to injuries Do not clean the inside of the indoor unit by yourself Make sure to consult your dealer or user inquiry counter specified by our company If you select incorrec...

Page 5: ...t address setting CHECK button This button is only used by service engineers for installation purposes TEST button This button is used during test operation NAMES AND FUNCTIONS OF REMOTE CONTROL BUTTONS Wired remote control Wired remote control The figure below shows the remote control with the cover opened Note that the items in the liquid crystal display LCD area are shown for explanation purpos...

Page 6: ...s prohibited When you start to operate the unit for the first time after turning the power supply on the default settings are listed below You can change them as you like Central control Turned off Operation changeover With auto mode auto cooling Without auto mode cooling Set temperature 23 C Fan speed Louver position Horizontal ATTENTION 1 Press button The unit starts operating 2 Press MODE butto...

Page 7: ...r entering the timer mode the timer mode ends and the display returns to the original one If you press button while timer mode is under setting timer mode is canceled and the display will return to the original one If you do not press any button for several minutes after entering the timer mode the timer mode ends and the display returns to the original one ATTENTION After a certain period of time...

Page 8: ...splay returns to the original one NOTICE EXAMPLE Number 1 Number 2 Number 3 Number 4 Four operations can be set with only ON timer or only OFF timer HOW TO PERFORM THE TIMER OPERATION WIRED REMOTE CONTROL 1 Press TIMER button 2 Press button for three times 3 Press SET button EXAMPLE flashes lights 4 Press or button Set the preferred time to start the operation Set Hour If you press or button for a...

Page 9: ... timer mode the timer mode ends and the display returns to the original one NOTICE HOW TO PERFORM THE TIMER OPERATION WIRED REMOTE CONTROL 5 Press SET button mark next to a number lights or is displayed The settings so far are effective and the display changes as shown on the left 6 Press or button Press button and is displayed Press button and is displayed Select either of the above two Press the...

Page 10: ...to temporarily disable each day s timer setting by using the Holiday Setting When the Holiday Setting is cancelled the timer setting is enabled again 1 In the Weekly timer mode select and set See Selection of Weekly timer mode step 1 to 5 on page 7 is displayed in the display area is flashing is displayed 2 Press or button Move the mark displayed above the days of week to the day which you want to...

Page 11: ...ay Canceling Silent Mode Setting Select in step 2 press SET button and silent setting is canceled ending the silent mode is displayed SILENT MODE Silent Mode Setting If you press button while timer mode is under setting timer mode is canceled and the display will return to the original one Note that the setting which has not been completed is canceled HOW TO PERFORM THE TIMER OPERATION WIRED REMOT...

Page 12: ...louver No The louver No to be set is confirmed and the display shows the upper limit of the movable range EXAMPLE If No 1 louver is selected current upper limit position 6 Press or button selection of upper limit position Select the upper limit of louver movable range position 1 is the most horizontal and position 6 is the most downwards position is to return to the factory setting If you need to ...

Page 13: ... The cooling heating capacity will get reduced Moreover it leads to waste of electricity and larger operation noise It may cause failure Dew may form and drop during cooling Do not block the inlet and outlet grilles of the indoor and outdoor units Excessive load to the unit may cause failure Keep moderate room temperature Too much cooling or heating is not good for your health It will also waste t...

Page 14: ...icates set temperature FILTER display Indicates for two seconds when FILTER button is pressed OFF TIMER display Indicates when OFF TIMER is set See page 14 OPERATION MODE select button Every time this button is pressed displays switch as below AUTO COOL HEAT FAN DRY ROOM TEMP TIME SETTING button Sets room temperature by pressing or button Sets time when setting the time ACL switch Used to reset th...

Page 15: ...off the power supply Power is distributed to the crankcase heater even if the compressor is stopped This keeps the compressor warm and prevents failures caused by accumulation of liquid refrigerant The operation of remote control must be performed slowly and steadily HOW TO USE WIRELESS REMOTE CONTROL ATTENTION 4 1 5 3 2 AUTO COOL HEAT DRY FAN Guideline of room temperature setting COOL 26 to 28 C ...

Page 16: ...form them address No and error code symptom of the trouble air conditioner type and model name etc Press the ON OFF button to stay the air conditioner on the stop mode lights for 0 5 seconds and blinks for 0 5 seconds Timer check indicator lamp WHEN LONG FLASHING LIGHT IS SHED FROM THE TIMER CHECK INDICATOR LAMP YELLOW Clean the filter See page 16 When cumulative running time reaches to 120 hours ...

Page 17: ...t in the way indicated with arrow mark 4 2 Ensure to insert the holders of the grille into the filter s holes until clicking sounds are heard How to mount the grille 1 Mount the hooks of the grille to the holes on the panel The hooks on the grille can be mounted in all 4 directions 2 Close the grille while pressing the stoppers on the grille 2 places to the OPEN direction Then release the stoppers...

Page 18: ...ted when the compressor is activated deactivated during operation or when the operation is stopped These are the sounds of the refrigerant flowing through the system Sounds of rustling or gurgling may be heard from a stopped indoor unit These sounds can be heard when the air conditioning system is performing automatic control The supply air from the indoor unit smells bad The supply air from the i...

Page 19: ... do by yourself Is the system installed in a well ventilated place Are there any obstacles If so it leads to the decrease of the efficiency and the increase of operation noise Avoid the place where cool warm air and operation noise cause problems to your neighbors INSTALLATION LOCATION Normally the efficiency of the air conditioning system will become lower after a while because dirt accumulates i...

Page 20: ...ega There should be no abnormal sound generation The resistance value should be 1 M or more When a bearing sound is loud replace the bearing When the resistance value is 1 M or less replace the motor 20 000 Hr Bearing Regular lubrication is required Audible inspection There should be no abnormal sound generation Replace parts regularly 15 000 Hr Consumable components Automatic louver motor Insulat...

Page 21: ...cted 5 years Cleaning object item Due to atmospheric dirt Piping in the unit Sympathetic vibration contact and corrosion of the piping in the unit Sympathetic vibration and contact of capillary tube Visual inspection Visual inspection There should be no abnormal sympathetic vibration sound or corrosion There should be no abnormal sympathetic vibration or contact wear Replace it or readjust the pip...

Page 22: ...sited foreign matter Retighten it if it is loose Clean with a brush in case of deposited foreign matter adhesion 25 000 Hr Electrical component including boards etc HIC board short circuit check Visual check of dirt adhesion to the board etc Self diagnosis mode appearance check Tester Visual inspection Visual inspection Should be of a specified resistance value There should be no deposited foreign...

Page 23: ...22 ...

Page 24: ...Tel 44 20 7025 2750 Fax 44 20 7025 2751 http www mhiae com MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONERS AUSTRALIA PTY LTD 9C Commercial Road Kingsgrove NSW 2208 PO BOX 318 Kingsgrove NSW 1480 Tel 61 2 8571 7977 Fax 61 2 8571 7992 http www mhiaa com au MITSUBISHI HEAVY INDUSTRIES MAHAJAK AIR CONDITIONERS CO LTD 220 Soi Chalongkrung 31 Kwang Lamplatiew Khet Lad Krabang Bangkok 10520 Thailand Tel 66 ...

Reviews: