5
- 117
5.7 Memory Copy From Control System To Standby System
5
(b) Operations when executing Memory Copy
The operation at memory copy execution is shown in Diagram 5.85.
(3) Memory Copy From Control System to Standby System Using Special
Relays and Special Registers
The following provides the procedure for executing memory copy function using the
special relays and special registers and the relevant operations
(a) Steps
1) Connect the control system and the standby system with the tracking cable,
and turn the standby system power ON.
* 1: If the standby system CPU module is replaced and the parameters are not stored in the new CPU
module, the "MISSING PARA. (error code: 2200)" stop error will occur.
2) Make sure SM1596 and SM1597 are turned OFF.
If SM1596 or SM1597 is ON, turn it OFF.
Diagram 5.85 shows the operation performed when memory copy is executed.
Diagram 5.86 LED Indications when Tracking Cable Is Connect
Control system
Standby system
Tracking cable
[Specify memory copy]
GX Developer
Control system
Standby system
Tracking cable
[Perform memory copy]
Control system
Standby system
Tracking cable
[Memory copy completed]
GX Developer
GX Developer
2) Begin copying to the standby system CPU
3) Copying to the standby system CPU complete
1) Memory copy from GX Developer
Q12PRHCPU
MODE
RUN
ERR.
USER
BAT.
BOOT
BACKUP
CONTROL
SYSTEM A
SYSTEM B
Q12PRHCPU
MODE
RUN
ERR.
USER
BAT.
BOOT
BACKUP
CONTROL
SYSTEM A
SYSTEM B
Control system CPU module
Standby system CPU module
ON (red)
ON (red)
Flashing (red)*
1
ON (red)