6
PVA-A·AA4 series
Medium Cabinet
Large Cabinet
Item Model
PVA-A30AA4
PVA-A36AA4
PVA-A42AA4
Power source
208/230V, 1-phase, 60Hz
Cooling capacity/Heating capacity
Btu/h
30,000 / 32,000
34,000 / 38,000
42,000 / 48,000
kW
8.8 / 9.4
10.0 / 11.1
12.3 / 14.1
Tonnage
2.5
3
3.5
Dimensions
Height
mm [in]
1378 [54-1/4]
1511 [59-1/2]
Width
mm [in]
534 [21]
635 [25]
Depth
mm [in]
548 [21-5/8]
Net weight
kg [lb]
64 [141]
78 [172]
Fan
Air
À
ow rate (Low-Mid-High)
CFM
613 - 744 - 875
788 - 956 - 1125
1040 - 1262 - 1485
External static
pressure
in. WG
0.30 - 0.50 - 0.80
[Pa]
75 - 125 - 200
Sound Pressure (Low-Mid-High)
[dB]
32 - 36 - 40
32 - 36 - 40
36 - 40 - 44
6. Trouble Shooting
Having trouble?
Here is the solution. (Unit is operating normally.)
Noise is louder than speci
¿
cations.
Ŷ
The indoor operation sound level is affected by the acoustics of the
particular room as shown in the following table and will be higher than
the noise speci
¿
cation, which was measured in an echo-free room.
High sound-
absorbing rooms
Normal rooms
Low sound-
absorbing rooms
Location
examples
Broadcasting
studio, music
room, etc.
Reception
room, hotel
lobby, etc.
Of
¿
ce, hotel
room
Noise levels
3 to 7 dB
6 to 10 dB
9 to 13 dB
Nothing appears in the wireless remote controller display, the display is
faint, or signals are not received by the indoor unit.
Ŷ
The batteries are low.
Replace the batteries and press the Reset button.
Ŷ
If nothing appears even after the batteries are replaced, make sure that
the batteries are installed in the correct directions (+, –).
7. Speci
¿
cations
Notes: 1. Rating conditions (cooling)
Indoor : 80 °F [26.7 °C] D.B., 67 °F [19.4 °C] W.B. Outdoor
:
95 °F [35 °C] D.B.
2. Rating conditions (heating)
Indoor : 70 °F [21.1 °C] D.B.
Outdoor
:
47 °F [8.3 °C] D.B., 43 °F [6.1 °C] W.B.
3. The indicated capacity is the value when one indoor unit is connected to the outdoor unit.
4.
Speci
¿
cations subject to change without notice.
5. The external static pressure is set to 0.50 in. WG (125 Pa) at factory shipment.
Guaranteed operating range
Indoor
Cooling
Upper limit
95 °F [35 °C] D.B.
71 °F [21.7 °C] W.B.
Lower limit
67 °F [19.4 °C] D.B.
57 °F [13.9 °C] W.B.
Heating
Upper limit
80 °F [26.7 °C] D.B.
–
Lower limit
70 °F [21.1 °C] D.B.
–
Notes: 1. Units should be installed by licensed electric contractor accordingly to local code requirement.
2. For outdoor units to be connected, refer to the Installation Manual that comes with the units.