background image

7

4.2.  Connecting pipes (Fig. 4-2)

Fig. 4-1 is a sample of piping system.
• Conduct suf

fi

 cient anti-condensation and insulation work to prevent water 

dripping from the refrigerant piping. (liquid pipe/gas pipe)

•  Increase insulation depending on the environment where the refrigerant piping is 

installed, or condensation may occur on the surface of the insulation material.
(Insulation material Heat-resistant temperature: 120 °C, Thickness: 15 mm or 
more)
*  When the refrigerant piping is used in locations subject to high temperature 

and humidity such as in the attic, further addition of insulation may be 
required.

•  To insulate the refrigerant piping, apply heat-resistant polyethylene foam between 

the indoor unit and insulation material as well as to the net between the insulation 
material 

fi

 lling all gaps.

(Condensation forming on the piping may result in condensation in the room or 
burns when contacting the piping.)

•  The indoor parts of the drain pipe should be wrapped with polyethylene foam insula-

tion materials (speci

fi

 c gravity of 0.03, thickness of 9 mm or more).

•  Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening 

fl

 are nut. 

A

•  Use two wrenches to tighten piping connections. 

B

• Use leak detector or soapy water to check for gas leaks after connections are 

completed. 

•  Apply refrigerating machine oil over the entire 

fl

 are seat surface. 

C

• Use the 

fl

 are nuts for the following pipe size. 

D

Indoor unit

Outdoor unit

15-50

63-140

100-140

Gas side

Pipe size (mm)

ø12.7

ø15.88

ø15.88

Liquid side Pipe size (mm)

ø6.35

ø9.52

ø9.52

•  When bending the pipes, be careful not to break them. Bend radius of 100 mm to 

150 mm is suf

fi

 cient.

•  Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

  Flare nuts must be tightened with a torque wrench.

2

 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site). 

•  When usual pipe sealing is used, refer to Table 3 for 

fl

 aring of R410A refrigerant 

pipes.

  The size adjustment gauge can be used to con

fi

 rm A measurements.

A  

(mm)

A

 Liquid pipe

B

 

Gas pipe

PUMY-P125,140

ø9.52

ø15.88

B, C, D 

(mm)

C

 Total capacity of indoor units

A

 Liquid pipe

B

 Gas pipe

ø9.52

ø15.88

a, b, c, d, e, f 

(mm)

D

 Model number

A

 Liquid pipe

B

 Gas pipe

15, 20, 25, 32, 40, 50

ø6.35

ø12.7

63, 80, 100, 125, 140

ø9.52

ø15.88

E

 Branch kit model

CMY-Y62-G-E

F

 4-Branching header

G

 8-Branching header

CMY-Y64-G-E

CMY-Y68-G-E

  Flare cutting dimensions

B  

Flare nut tightening torque

A

  Die

B

  Copper pipe

Fig. 4-2

A

Fig. 4-3

A

 (Fig. 

4-2)

B

 (Fig. 

4-2)

Table 3 (Fig. 4-3)

4.  Installing the refrigerant piping

A

H

B

C

L

D

e

a

h

b

c

d

A

a

b

c

d

e

f

H

h

L

A

 : Outdoor Unit

B

 : First Branch

C

 : Indoor unit

D

 : Cap

A+B+C+D+a+b+c+d+e   120 m
L = A+B+C+D+e   80 m

 = B+C+D+e   30 m

H   50 m (Outdoor lower H   20 m)
h   12 m

A+a+b+c+d+e+f   120 m
L = A+f   80 m, 

 = f   30 m

H   50 m (Outdoor lower H   20 m)
h   12 m

Fig. 4-1

90°± 0.5°

øA

45°± 2°

R0.4 - R0.8

Copper pipe O.D. (mm)

A (mm)

Flare tool for R410A

Flare tool for R22·R407C

Clutch type

ø6.35 (1/4

)

0 - 0.5

1.0 - 1.5

ø9.52 (3/8

)

0 - 0.5

1.0 - 1.5

ø12.7 (1/2

)

0 - 0.5

1.0 - 1.5

ø15.88 (5/8

)

0 - 0.5

1.0 - 1.5

ø19.05 (3/4

)

0 - 0.5

1.0 - 1.5

Copper pipe O.D. 

(mm)

Flare dimensions 

øA dimensions (mm) 

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

Copper pipe O.D. 

(mm)

Flare unt O.D. 

(mm) 

Tightening torque 

(N·m)

ø6.35

17

14 - 18

ø6.35

22

34 - 42

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø12.7

29

68 - 82

ø15.88

29

68 - 82

ø15.88

36

100 - 120

Summary of Contents for PUMY-P125

Page 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Page 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Page 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Page 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Page 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Page 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Page 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Page 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Page 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Page 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Page 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Page 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Page 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Page 14: ......

Page 15: ......

Page 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Reviews: