background image

6

2.4.3.  Windy location installation

When installing the outdoor unit on a rooftop or other location unprotected from the 
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds. 
Strong wind entering the air outlet may impede the normal air

fl

 ow and a malfunction 

may result.
The following shows two examples of precautions against strong winds.

1

 Install an optional air guide if the unit is installed in a location where strong winds 

from a typhoon, etc. may directly enter the air outlet. (Fig. 2-15)

A

 Air guide

2

  Position the unit so that the air outlet blows perpendicularly to the seasonal wind 

direction, if possible. (Fig. 2-16)

B

 Wind direction

Fig. 2-15

Fig. 2-16

2. Installation location

3.  Installing the outdoor unit

(mm)

•  Be sure to install the unit in a sturdy, level surface to prevent rattling noises during 

operation. (Fig. 3-1)

<Foundation speci

fi

 cations>

Foundation bolt

M10 (3/8

)

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

•  Make sure that the length of the foundation bolt is within 30 mm of the bottom 

surface of the base.

•  Secure the base of the unit 

fi

 rmly with four-M10 foundation bolts in sturdy loca-

tions.

Installing the outdoor unit

•  Do not block the vent. If the vent is blocked, operation will be hindered and break-

down may result.

•  In addition to the unit base, use the installation holes on the back of the unit to 

attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 

×

 15 

mm or less) and install on site.

 Warning:

•  The unit must be securely installed on a structure that can sustain its weight. 

If the unit is mounted on an unstable structure, it may fall down and cause 
damage or injuries.

•  The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

Fig. 3-1

A

    M10 (3/8") bolt

B

  Base

  As long as possible.

D

  Vent

E

    Set deep in 

the ground

4.  Installing the refrigerant piping

4.1. Precautions for devices that use R410A refriger-

ant

•  Refer to page 3 for precautions not included below on using air conditioners 

with R410A refrigerant.

•  Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the 

fl

 ared sections.

•  Use C1220 copper phosphorus, for copper and copper alloy seamless pipes, 

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses 
speci

fi

 ed in the table to the below. Make sure the insides of the pipes are clean 

and do not contain any harmful contaminants such as sulfuric compounds, 
oxidants, debris, or dust.

 Warning:

 When installing or relocating, or servicing the air conditioner, use only the 
speci

fi

 ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it with 

any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pres-
sure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that speci

fi

 ed for the system will cause 

mechanical failure or system malfunction or unit breakdown. In the worst case, 
this could lead to a serious impediment to securing product safety.

Indoor unit type

15-50

63-140

Liquid pipe

ø6.35 thickness 0.8 mm

ø9.52 thickness 0.8 mm

Gas pipe

ø12.7 thickness 0.8 mm

ø15.88 thickness 1.0 mm

•  Do not use pipes thinner than those speci

fi

 ed above.

Max.30

600

600

Min.360

Min.10

950

175

175

25

370

330

Summary of Contents for PUMY-P125

Page 1: ...ir Conditioners PUMY P125 140VHMS PUMY P125 140YHMS INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air condition...

Page 2: ...ent to securing product safety Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly installed water leakag...

Page 3: ...refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tool...

Page 4: ...portation handles of the outdoor unit to transport the unit If the unit is carried from the bottom hands or fingers may be pinched 2 3 Outline dimensions Outdoor unit Fig 2 1 Constraints on indoor uni...

Page 5: ...ir outlet guides for upward airflow 2 4 2 When installing multiple outdoor units Leave 10 mm space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only Fig 2 9...

Page 6: ...it may fall down and cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly...

Page 7: ...ak them Bend radius of 100 mm to 150 mm is sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit F...

Page 8: ...re does not decrease 2 Pressurize to 1 5 MPa 15 kgf cm2 G wait five minutes and make sure the pressure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm2 G and measure the surrounding tem peratur...

Page 9: ...electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work 5 Never connect the main power source to terminal block of transmission line If connect...

Page 10: ...50 M NET R C Main 101 to 150 Set at an IC Main address within the same group plus 100 M NET R C Sub 151 to 200 Set at an IC Main address within the same group plus 150 MA R C Unnecessary address sett...

Page 11: ...S TB3 M1M2 S M1M2 S A B M1M2 M1M2 S M1M2 S F A B C E D TB7 IC 51 TB15 TB15 TB15 MA 01 IC TB5 03 IC TB5 TB5 02 IC TB5 04 IC 05 IC 07 IC 06 L1 MA MA MA OC 53 OC 1 m4 3 Power Supply Unit L3 L 7 L4 m 3 1...

Page 12: ...fuse with correct capacity Using fuse and wire or copper wire with too large capacity may cause a malfunction of unit or fire IMPORTANT Make sure that the current leakage breaker is one compatible wit...

Page 13: ...or the compressor will start to warm up after power is supplied After supplying power for the times indicated below measure the insulation resistance again The insulation resistance drops due to accum...

Page 14: ......

Page 15: ......

Page 16: ...BH79D109H05 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer...

Reviews: