40
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
Pipe temperature/Liquid (TH3) when
error occurred.
−40•to•90
−40•to•90
(When the coil thermistor detects 0
:
or below, “–”
and temperature are displayed by turns.)
(Example)•When•−15
:
;
0.5 s 0.5 s 2 s
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Discharge temperature (TH4) when error
occurred.
3 to 217
Compressor current when error occurred.
0 to 50
Error history (1) (latest)
Alternate display of faulty unit
number and check code
Error history (2)
Alternate display of faulty unit
number and check code
3 to 217
(When the temperature is 100
:
or more, the
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 130
:
;
0.5 s 0.5 s 2 s
:
A
Code
display
Code
display
0 to 50
When no error history,
“ 0 ” and “– –” are displayed by turns.
When no error history,
“ 0 ” and “– –” are displayed by turns.
1
ON
2 3 4 5 6
Compressor operation duration
0 to 999
0 to 999
(When it is 100 minutes or more, the hundreds digit,
tens digit and ones digit are displayed by turns.)
(Example) When 245 minutes;
0.5 s 0.5 s 2 s
Minute
15
1
30
2
45
1
ON
2 3 4 5 6
Capacity settings
The outdoor capacity code is shown as below
Code
display
Model
PUHZ-W85
Code
14
1
ON
2 3 4 5 6
LEV-B opening when error occurred
Pulse
0 to 500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 s 0.5 s 2 s
1
50