5-5. <REFERENCE DATA> PLATE HEAT EXCHANGER (ACH70-74 PLATES)
Nominal water flow
L/min
63.1
Heating
(A7/W35)
Capacity
kW
22.0
COP
4.20
Power input
kW
5.238
Heating
(A7/W45)
Capacity
kW
22.0
COP
3.25
Power input
kW
6.769
Heating
(A2/W35)
Capacity
kW
16.0
COP
3.11
Power input
kW
5.144
Heating
(A2/W45)
Capacity
kW
16.0
COP
2.36
Power input
kW
6.779
Nominal water flow
L/min
45.9
Cooling
(A35/W7)
Capacity
kW
16.0
EER
2.35
Power input
kW
6.808
Cooling
(A35/W18)
Capacity
kW
18.0
EER
4.28
Power input
kW
4.205
Rating conditions
Nominal operating condition
Heating (A7/W35)
Outside air temperature (Dry-bulb)
+ 7°C
Outside air temperature (Wet-bulb)
+ 6°C
Water temperature (inlet/outlet)
+ 30°C/+ 35°C
Heating (A7/W45)
Outside air temperature (Dry-bulb)
+ 7°C
Outside air temperature (Wet-bulb)
+ 6°C
Water temperature (inlet/outlet)
+ 40°C/+ 45°C
Heating (A2/W35)
Outside air temperature (Dry-bulb)
+ 2°C
Outside air temperature (Wet-bulb)
+ 1°C
Water temperature (inlet/outlet)
+ 30°C/+ 35°C
Heating (A2/W45)
Outside air temperature (Dry-bulb)
+ 2°C
Outside air temperature (Wet-bulb)
+ 1°C
Water temperature (inlet/outlet)
+ 40°C/+ 45°C
Cooling (A35/W7)
Outside air temperature (Dry-bulb)
+ 35°C
Outside air temperature (Wet-bulb)
+ 24°C
Water temperature (inlet/outlet)
+ 12°C/+ 7°C
Cooling (A35/W18)
Outside air temperature (Dry-bulb)
+ 35°C
Outside air temperature (Wet-bulb)
+ 24°C
Water temperature (inlet/outlet)
+ 23°C/+ 18°C
Note: "COP" and "Power input" in the above table do
NOT
contain the "pump input (based on EN 14511)".
(SW160)
Nominal water flow
L/min
71.7
Heating
(A7/W35)
Capacity
kW
25.0
COP
4.00
Power input
kW
6.250
Heating
(A7/W45)
Capacity
kW
25.0
COP
3.10
Power input
kW
8.064
Heating
(A2/W35)
Capacity
kW
20.0
COP
2.80
Power input
kW
7.142
Heating
(A2/W45)
Capacity
kW
20.0
COP
2.20
Power input
kW
9.090
Nominal water flow
L/min
57.3
Cooling
(A35/W7)
Capacity
kW
20.0
EER
2.25
Power input
kW
8.888
Cooling
(A35/W18)
Capacity
kW
22.0
EER
4.10
Power input
kW
5.365
(SW200)
OCH583