background image

SW1

CNDM

7

8. Special Functions

8.1. Low noise mode (on-site modi

fi

 cation) (Fig. 8-1)

The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.

1

  Complete the circuit as shown when using the external input adapter  

(PAC-SC36NA). (Option)

2

  SW1 ON: Low noise mode

  SW1 OFF: Normal operation

Note:
•  

The ability varies according to the outdoor temperature and conditions, etc.

•  

When the ambient temperature is high, this function may not work.

A

  Circuit diagram example

(low noise mode)

B

 On-site arrangement

C

  External input adapter 

 (PAC-SC36NA)

D

 Outdoor unit control board

E

 Max. 10 m

F

 Red

G

 Brown

H

 Orange

Fig. 8-1

7. Test run

Before test run

   After installation works are completed, check if there is no refrigerant leak-

age, no looseness in the power supply or control wiring, no wrong polarity, 
and no disconnection of one phase in the supply.

   Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0M

"

.

 Warning:

Do not use the air to water heat pump if the insulation resistance is less than 
1.0M

"

.

Insulation resistance

When installed the power source to the unit has been cut for an extended period, 
the insulation resistance may drop below 1 M

"

 due to the accumulation of refriger-

ant within the compressor. This is not a malfunction. Perform the following proce-
dures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

"

, the compressor may be faulty or sim-

ply the accumulation of refrigerant in the compressor makes the resistance drop.

3.  After connecting the wires to the compressor, the compressor starts to warm 

up once power is supplied. After supplying power for the times indicated below, 
remove the wires from the compressor and measure the insulation resistance 
again.

 

•  The insulation resistance drops due to the accumulation of refrigerant in the 

compressor. The resistance will rise above 1 M

"

 after the compressor is 

warmed up for 4 hours.
 (The necessary time to warm up the compressor varies according to atmo-
spheric conditions and refrigerant accumulation.)

• If the refrigerant accumulates within the compressor, the compressor must be 

warmed up at least 12 hours before starting the operation to prevent break-
down.

4.  If the insulation resistance rises above 1 M

"

, the compressor is not faulty.

 Caution:

•  

The compressor does not operate if the power supply phase connection is 
incorrect.

•  

Turn on the power at least 12 hours before starting operation.

-  

Starting operation immediately after turning on the main power switch can result 
in severe damage to internal parts. Keep the power switch turned on during the 
operating period.

Note : Occasionally, vapor that is made by the defrost operation may seem as    
           if smoke come up from the outdoor unit.

01̲ BH79D067L02̲EN.indd   7

01̲ BH79D067L02̲EN.indd   7

2009/06/03   9:51:03

2009/06/03   9:51:03

Summary of Contents for PUHZ-HW*HA series

Page 1: ...curo e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unit interna prima di installare il condizionatore d aria Nederlands Espa ol Italiano Dansk Svenska INSTALLA...

Page 2: ...ation has been completed make sure that refrigerant does not leak If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range poisonous gases will be...

Page 3: ...ods or telephone grounding lines If the unit is not properly grounded there may be a risk to get an electric shock Make sure to use circuit breakers ground fault interrupter isolating switch B fuse an...

Page 4: ...ion the unit so that the outlet air can blow at right angle to the seasonal wind direction if possible Fig 2 4 B Wind direction A M10 3 8 bolt B Base C As long as possible D Vent E Set deep in the gro...

Page 5: ...hin the allowable range specified in our technical data etc If the unit is used out of the allowable range the parts of unit might be damaged 5 2 Water quality condition The water in a system should b...

Page 6: ...terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national codes 2 Powe...

Page 7: ...er ant within the compressor This is not a malfunction Perform the following proce dures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulat...

Page 8: ......

Page 9: ...0 500 1000 400 600 1000 2000 300 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 5 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2...

Page 10: ...K BH79D067L02 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the resident...

Reviews: