OC196A-34
(3) Auto vane control
Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Vane position set mode & swing mode.
( i ) Every time AIR DISCHARGE button is pressed, setting will be changed .
( ii ) Airflow direction can be changed with AIR DISCHARGE button.
When 60° or 70° discharge is selected with the low fan speed in COOL operation, “AUTO RETURN” will appear below the
temperature display. One hour later, the discharge direction returns to 10° automatically and “AUTO RETURN” will disap-
pear. If the discharge direction is set to 10° during “AUTO RETURN” indication, the time counting for AUTO RETURN is
cancelled.
1
Fan speed : LOW
2
Fan speed : HIGH
10°
60°
70°
10°
60°
70°
SWING
SWING
30°
10°
60°
70°
2
Fan speed : HIGH
10°
60°
70°
30°
AUTO
RETURN
AUTO
RETURN
<AUTO RETURN>
1
Fan speed : LOW
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to low. Five minutes later, if the differ-
ence is still out of
RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote
controller.
RANGE A : Pipe temperature is more than 9 degrees above room temperature.
RANGE B : Pipe temperature is within 9 degrees either way of room temperature.
RANGE C : Pipe temperature is more than 9 degrees below room temperature.
Pipe temperature
minus room temperature
+9
0
-9
RANGE A
RANGE B
RANGE C
(degree)