15
Wiring
2.1.2
EMC filter
This inverter is equipped with a built-in EMC filter (capacitive filter) and common mode choke.
The EMC filter is effective for reduction of air-propagated noise on the input side of the inverter.
The EMC filter is factory-set to disable (OFF). To enable it, fit the EMC filter ON/OFF connector to the ON position.
The input side common mode choke, built-in the FR-F720-02330(FR-F740-01160) or lower inverter, is always valid
regardless of ON/OFF of the EMC filter ON/OFF connector.
The FR-F720-00046 and 00077 are not provided with the EMC filter ON/OFF connector. (Always ON)
<How to disconnect the connector>
(1) Before removing a front cover, check to make sure that the indication of the inverter operation panel is OFF, wait
for at least 10 minutes after the power supply has been switched OFF, and check that there are no residual voltage
using a tester or the like. (For the front cover removal method, refer to
page 6.
)
(2) When disconnecting the connector, push the fixing tab and pull the connector straight without pulling the cable or
forcibly pulling the connector with the tab fixed. When installing the connector, also engage the fixing tab securely.
If it is difficult to disconnect the connector, use a pair of long-nose pliers, etc.
CAUTION
⋅
Fit the connector to either ON or OFF.
⋅
Enabling (turning ON) the EMC filter increase leakage current.
(Refer to page 47)
WARNING
While power is ON or when the inverter is running, do not open the front cover. Otherwise you may get an electric shock.
EMC filter OFF
EMC filter OFF
EMC filter OFF
EMC filter ON
EMC filter ON
EMC filter ON
(initial setting)
(initial setting)
(initial setting)
V
U
W
EMC filter
ON/OFF
connector
FR-F720-00105 to 00250
FR-F740-00023 to 00126
FR-F720-00340, 00490
FR-F740-00170, 00250
FR-F720-00630 or higher
FR-F740-00310 or higher
FR-F720-00105 to 00250
FR-F740-00023 to 00126
FR-F720-00340, 00490
FR-F740-00170, 00250
FR-F720-00630
FR-F740-00310, 00380
FR-F720-00770 to 01250
FR-F740-00470, 00620
FR-F720-01540 or higher
FR-F740-00770 or higher
EMC filter
ON/OFF connector
(Side view)
Disengage connector fixing tab