17
E6
1
Contact failure, short circuit or,
miswiring (converse wiring) of
indoor/outdoor unit connecting
wire
2
Defective transmitting/receiv-
ing circuit of indoor controller
board
3
Defective transmitting/receiving
circuit of indoor controller board
4
Noise has entered into indoor/
outdoor unit connecting wire.
1
Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor unit or
outdoor unit.
Check all the units in case of twin indoor unit
system.
2
-
4
Turn the power off, and on again to
check. If abnormality generates again,
replace indoor controller board or outdoor
controller circuit board.
* Other indoor controller board may have
defect in case of twin indoor unit system.
E7
Indoor/outdoor unit communication
error (Transmitting error)
Abnormal if “1” receiving is detected 30
times continuously though indoor controller
board has transmitted “0”.
1
Defective transmitting receiving
circuit of indoor controller board
2
Noise has entered into power
supply.
3
Noise has entered into outdoor
control wire.
1
-
3
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
Indoor/outdoor unit communication
error (Signal receiving error)
1
Abnormal if indoor controller board
cannot receive any signal normally for 6
minutes after turning the power on.
2
Abnormal if indoor controller board
cannot receive any signal normally for 3
minutes.
3
Consider the unit abnormal under the
following condition: When 2 or more
indoor units are connected to one
outdoor unit, indoor controller board
cannot receive a signal for 3 minutes
from outdoor controller circuit board, a
signal which allows outdoor controller
circuit board to transmit signals.
Error Code
Abnormal point and detection method
Cause
Countermeasure
Fb
(FB)*
Indoor controller board
Abnormal if data cannot be normally read
from the nonvolatile memory of the indoor
controller board.
1
Defective indoor controller
board
1
Replace indoor controller board.
* The check code in the parenthesis indicates
PAR-30MAA model.
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2
Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1
Defective remote controller
1
Replace remote controller.
E3
or
E5
Remote controller transmission
error(E3)/signal receiving error(E5)
1
Abnormal if remote controller could not
find blank of transmission path for 6
seconds and could not transmit.
(Error code: E3)
2
Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E3)
1
Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2
Indoor controller board receives
transmitted data at the same time,
compares the data, and when detecting
it, judges different data to be abnormal
30 continuous times. (Error code: E5)
1
Set a remote controller to main, and the
other to sub.
2
Remote controller is connected with only one
indoor unit.
3
The address changes to a separate setting.
4
~
6
Diagnose remote controller.
a) When “RC OK” is displayed, remote con-
trollers have no problem.
Turn the power off, and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “RC NG” is displayed, replace
remote controller.
c) When “RC E3” or “ERC 00-66” is displayed,
noise may be causing abnormality.
1
2 remote controllers are set as
“main.”
(In case of 2 remote controllers)
2
Remote controller is connected
with 2 indoor units or more.
3
Repetition of refrigerant
address
4
Defective transmitting/receiving
circuit of remote controller
5
Defective transmitting/receiving
circuit of indoor controller board
6
Noise has entered into transmis-
sion wire of remote controller.
OCH493D