4. Installing the refrigerant piping

4.1. Precautions

4.1.1. For devices that use R410A refrigerant

• Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration

oil applied to the flared sections.

• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,

to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.

 Warning:

When installing or moving the air conditioner, use only the specified refriger-
ant (R410A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.

A12, A18

A24, A30, A36, A42

Liquid pipe

ø6.35 mm, ø1/4 inch

ø9.52 mm, ø3/8 inch

thickness 0.8 mm, 1/32 inch

thickness 0.8 mm, 1/32 inch

Gas pipe

ø12.7 mm, ø1/2 inch

ø15.88 mm, ø5/8 inch

thickness 0.8 mm, 1/32 inch

thickness 1.0 mm, 3/64 inch

• Do not use pipes thinner than those specified above.

4.2. Connecting pipes (Fig. 4-1)

• When commercially available copper pipes are used, wrap liquid and gas pipes

with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or
more, thickness of 12 mm, 1/2 inch or more).

• The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-

lation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).

• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening

flare nut.

• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-

late carefully.

B

Flare nut tightening torque

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm, inch)

(mm, inch)

 (N·m, ft·lbs)

ø6.35, 1/4”

17, 43/64

14 - 18, 10 -13

ø9.52, 3/8”

22, 7/8

34 - 42, 25 - 30

ø12.7, 1/2”

26, 1-3/64

49 - 61, 35 - 44

ø15.88, 5/8”

29, 1-9/64

68 - 82, 49 - 59

C

Apply refrigerating machine oil over the entire flare seat surface.

D

Use correct flare nuts meeting the pipe size of the outdoor unit.

Available pipe size

A12, A18

A24, A30, A36, A42

Liquid side

ø6.35

ø9.52

ø12.7

Gas side

ø15.88

?

 : Factory flare nut attachment to the heat-exchanger.

A

Flare cutting dimensions

Copper pipe O.D.

Flare dimensions

(mm, inch)

 øA dimensions (mm, inch)

ø6.35, 1/4”

8.7 - 9.1, 11/32 - 23/64

ø9.52, 3/8”

12.8 - 13.2, 1/2 - 33/64

ø12.7, 1/2”

16.2 - 16.6, 41/64 - 21/32

ø15.88, 5/8”

19.3 - 19.7, 49/64 - 25/32

C

D

Fig. 4-1

(inch)

 BG79U795H01_en.pm6

05.12.1, 9:48 AM

5

Summary of Contents for Mr.Slim PLA-A

Page 1: ...rrect use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este ma...

Page 2: ...edical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communic...

Page 3: ...the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side o...

Page 4: ...mm 11 16 7 8 inch Damage could result by failing to adhere to this range Fig 3 7 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior...

Page 5: ...Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness o...

Page 6: ...adhesive Observe the figure for piping work Use the included drain hose to change the extraction direction Max 65ft 5 to 7ft A B C B M L K D E D H I G D F F F Max 6inch J F Fig 5 1 Fig 5 2 1 Correct p...

Page 7: ...uded with the manuals near each wiring diagram for the indoor and outdoor units 1 Max 50 m 165 ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 500 m 1500 ft 3 The figures a...

Page 8: ...troller accessory Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires ra...

Page 9: ...V DC12V DC12V DC12V DC12V DC12V DC12V Circuit rating Wiring Wire No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S...

Page 10: ...ntrollers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remo...

Page 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Page 12: ...on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode sel...

Page 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Page 14: ...or voltage shortage and abnormal synchronous signal to main circuit Current sensor error 12 13 14 Others Other errors Refer to the technical manual for the outdoor unit 1 If the beeper does not sound...

Page 15: ...d remote controller 1 for PLP 42AAMD 9 Installing the grille 1 4 5 6 2 0 2 3 Fig 9 1 Fig 9 2 A D C B A 11 16 3 16 0 Fig 9 3 B A C 1 1 D E 2 F G F B 1 9 2 Preparing to attach the grille Fig 9 2 With th...

Page 16: ...the connector is not covered with the glass tube tracking resulting in fire may occur 9 Installing the grille C B A D B A D Fig 9 9 A Button B Vane motor C Up down vanes D Connector A Clamp B Cable C...

Page 17: ...on procedures while waiting for the stable operation 10 Easy maintenance function This function only for A control By using the maintenance mode you can display many types of maintenance data on the r...

Page 18: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Reviews: