6. Electrical work

Function table

Select unit number 00

Mode
Power failure automatic recovery

Indoor temperature detecting

LOSSNAY connectivity

Power voltage

Auto mode (only for PUZ)

Settings
Not available
Available

*1

Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
230 V
208 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled

Mode no.

Setting no. Initial setting

setting

01

1
2
1

02

2
3
1

03

2
3

04

1
2

05

1
2

Mode
Filter sign

Fan speed

No. of air outlets

Installed options (high-performance filter)

Up/down vane setting

Energy saving air flow
(Heating mode)

Settings
100Hr
2500Hr
No filter sign indicator
Standard (PLA)/Silent (PCA)
High ceiling 

1

 (PLA)/Standard (PCA)

High ceiling 

2

 (PLA)/High ceiling (PCA)

4 directions
3 directions
2 directions
Not supported
Supported
Equipped with vanes (vanes angle setup 

3

)

Equipped with vanes (vanes angle setup 

1

)

Equipped with vanes (vanes angle setup 

2

)

Disabled
Enabled

Mode no.

Setting no. Initial setting

setting

1

07

2
3
1

08

2
3
1

09

2
3

10

1
2

11

1
2
3

12

1
2

Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])

7. Test run

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

7.2. Test run

The following 3 methods are available.

7.2.1. Using wired remote controller (Fig. 7-1)

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.

7.2.2. Using wireless remote controller (Fig. 7-2)

1

Turn on the power to the unit at least 12 hours before the test run.

2

Press the 

TEST RUN

 button twice continuously.

(Start this operation from the status of remote controller display turned off.)

A

TEST RUN

 and current operation mode are displayed.

3

Press the 

MODE

 

 button to activate 

 mode, then check whether

cool air is blown out from the unit.

4

Press the 

MODE

 

 button to activate 

 mode, then check whether

warm air is blown out from the unit.

5

Press the 

FAN

 button and check whether fan speed changes.

6

Press the 

VANE

 button and check whether the auto vane operates properly.

7

Press the ON/OFF button to stop the test run.

Note:
• Point the remote controller towards the indoor unit receiver while following

steps 

2

 to 

7

.

• It is not possible to run the in FAN, DRY or AUTO mode.

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

TEST RUN

5

7

A

3

,

4

2

6

Fig. 7-2

Fig. 7-1

˚C

˚C

SIMPLE

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN
COOL, HEAT

A

F

C

E

D

B

M

I

H G

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line
temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time dis-
play

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

*1 When the power supply returns, the air conditioner will start 3 minutes later.

 BG79U795H01_en.pm6

05.12.1, 9:48 AM

12

Summary of Contents for Mr.Slim PLA-A

Page 1: ...rrect use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este ma...

Page 2: ...edical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communic...

Page 3: ...the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side o...

Page 4: ...mm 11 16 7 8 inch Damage could result by failing to adhere to this range Fig 3 7 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior...

Page 5: ...Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness o...

Page 6: ...adhesive Observe the figure for piping work Use the included drain hose to change the extraction direction Max 65ft 5 to 7ft A B C B M L K D E D H I G D F F F Max 6inch J F Fig 5 1 Fig 5 2 1 Correct p...

Page 7: ...uded with the manuals near each wiring diagram for the indoor and outdoor units 1 Max 50 m 165 ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 500 m 1500 ft 3 The figures a...

Page 8: ...troller accessory Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires ra...

Page 9: ...V DC12V DC12V DC12V DC12V DC12V DC12V Circuit rating Wiring Wire No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S...

Page 10: ...ntrollers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remo...

Page 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Page 12: ...on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode sel...

Page 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Page 14: ...or voltage shortage and abnormal synchronous signal to main circuit Current sensor error 12 13 14 Others Other errors Refer to the technical manual for the outdoor unit 1 If the beeper does not sound...

Page 15: ...d remote controller 1 for PLP 42AAMD 9 Installing the grille 1 4 5 6 2 0 2 3 Fig 9 1 Fig 9 2 A D C B A 11 16 3 16 0 Fig 9 3 B A C 1 1 D E 2 F G F B 1 9 2 Preparing to attach the grille Fig 9 2 With th...

Page 16: ...the connector is not covered with the glass tube tracking resulting in fire may occur 9 Installing the grille C B A D B A D Fig 9 9 A Button B Vane motor C Up down vanes D Connector A Clamp B Cable C...

Page 17: ...on procedures while waiting for the stable operation 10 Easy maintenance function This function only for A control By using the maintenance mode you can display many types of maintenance data on the r...

Page 18: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Reviews: