4
6.5
B
J
O
N
F
Max. 300 mm [11-13/16 in]
[Fig. 6-10]
Correct piping
Wrong piping
A
Insulation (9 mm [3/8 in] or more)
B
Downward slope (Drain pipes should have an inclination of
1/100 or more.)
C
Support metal
K
Air bleeder
L
Raised
M
Odor trap
Grouped piping
D
O. D. ø32 mm [1-1/4 in] PVC TUBE
E
Make it as large as possible. About 10 cm [3-15/16 in].
F
Indoor unit
G
Make the piping size large for grouped piping.
H
Downward slope (Drain pipes should have an inclination of
1/100 or more.)
I
O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping.
(9 mm [3/8 in] or more insulation)
J
Up to 550 mm [21-21/32 in]
N
Drain hose (accessory)
O
Horizontal or slightly upgradient
[Fig.6-11]
C
B
A
L
D
D
D
E
K
M
B
H
I
Max. 20m [65 ft]
1.5-2 m [5 to 7 ft]
G
F
F
F
B
C
D
E
E
H
G
K
J
F
I
A
25 [1]
25 [1]
35
[1-13/32]
A
Indoor unit
B
Pipe cover (60 mm [3/8 in]) (accessory)
C
Tie band (accessory)
D
Visible part
E
Insertion margin
F
Drain hose (accessory)
G
Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supplied)
H
Insulating material (field supplied)
I
Tie band (accessory)
J
Max.180 ± 5 mm [7-3/32 ± 7/32 in]
K
To be gap free. The joint section of the insulation material meet must be at the top.
(Unit: mm [in])
[Fig. 6-13]
6.6
A
B
F
C
D
E
A
Insert pump's end 2 to 4 cm [13/16 to 1-19/32 in].
B
Remove the water supply port.
C
About 2000 cc
D
Water
E
Filling port
F
Screw
[Fig. 6-14]
SWE
<Indoor board>
[Fig.6-12]
A
Indoor unit
B
Pipe cover (30 mm [3/16 in]) (accessory)
C
Tie band (accessory)
D
Band fixing part
E
Insertion margin
F
Drain hose (accessory)
G
Drain pipe (O.D. ø32 PVC TUBE, field supplied)
H
Insulating material (field supplied)
I
Max.145 ± 5 mm
D
E
H
G
I
F
B
C
5
25
A
01_KB79U390H01_illust.p65
10.9.16, 17:47
4