3. Loading and Installation
3.1 Handling Precautions
(1) Do not drop or apply severe shock to the module case since it is made of
resin.
(2) Always make sure to touch the grounded metal to discharge the electricity
charged in the body, etc., before touching the module.
Failure to do so may cause a failure or malfunctions of the module.
(3) Tighten the screws such as module fixing screws within the following range.
Screw location
Tightening torque range
External power supply terminal screw (M2.5 screw) ( 1) 0.40
N•m
Module fixing screw (usually not required) (M3 screw) ( 2)
0.36 to 0.48 N•m
1: This terminal is used as an external power input terminal for supplying power to the
transceiver when being connected to a 10BASE5.
2: The module can be easily fixed onto the base unit using the hook at the top of the
module. However, it is recommended to secure the module with the module fixing
screw if the module is subject to significant vibration.
3.2 Installation Environment
For further details, refer to the user's manual for the CPU module to use.
4. Part Names
1)
3)
5)
1)
4)
1)
2)
6)
6)
6)
Name
Name
1) LED display (Refer to 1) )
2)
10BASE-T/100BASE-TX
connector (RJ45) ( 1)
5)
External power supply terminal
(Transceiver power supply)
(Input power supply reference value: 13.28 V to 15.75 V)
3) 10BASE5
connector
4) 10BASE2
connector
6) Serial number plate ( 2)
1: The orientation of the connector is different (rotated) depending on the serial No.
Although an LED may be built in the connector depending on the serial No. of the module,
it will not turn on.
2: Indicates the serial No. of the Ethernet module.
Summary of Contents for MELSEC QJ71E71-100