32
4 FUNCTIONS
4.5 Conversion Method
Setting procedure
■
Sampling processing
Set "Average processing setting" to "Sampling processing".
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Basic
setting]
[Conversion system]
■
Average processing
1.
Set "Average processing setting" to "Time average", "Count average", or "Moving average".
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Basic
setting]
[Conversion system]
2.
Set a value for "Time average/Count average/Moving average setting".
*1 Set a value greater than the value calculated by the following formula as the time average.
Conversion speed
×
Number of conversion enabled channels
×
Minimum processing times (4 times)
Item
Setting range
Time average
When the input type is current, and voltage: 4 to 10000 (ms)
When the input type is resistance temperature detector, and thermocouple: 160 to 10000 (ms)
Count average
4 to 10000 (times)
Moving average
2 to 1000 (times)